[Ui] rated insulation
voltage
600 V for signalling circuit conforming to CSA C22.2 No
14
600 V for power circuit conforming to CSA C22.2 No 14
600 V for signalling circuit conforming to UL 508
690 V for signalling circuit conforming to IEC 60947-5-1
690 V for signalling circuit conforming to IEC 60947-4-1
690 V for power circuit conforming to IEC 60947-4-1
600 V for power circuit conforming to UL 508
Electrical durability 1.3 Mcycles 12 A AC-3 at Ue <= 440 V
0.3 Mcycles 20 A AC-1 at Ue <= 440 V
Mounting support Plate
Rail
Standards BS 5424
IEC 60947
NF C 63-110
VDE 0660
Product certifications CSA
UL
Connections - terminals Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5
mm²) - cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4
mm²) - cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4
mm²) - cable stiffness: solid
Screw clamp terminals 1 cable(s) 0...0 in² (0.34...2.5
mm²) - cable stiffness: flexible - with cable end
Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4
mm²) - cable stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4
mm²) - cable stiffness: solid
Tightening torque 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with
screwdriver flat Ø 6 mm
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with
screwdriver Philips No 2
Operating time 10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
Safety reliability level B10d = 20000000 cycles contactor with mechanical load
conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
Mechanical durability 10 Mcycles
Operating rate 3600 cyc/h
Complementary
Control circuit voltage limits 0.2...0.75 Uc at <= 122 °F (50 °C) drop-out
0.8...1.15 Uc at <= 122 °F (50 °C) operational
Inrush power in VA 30 VA at 68 °F (20 °C)
Hold-in power consumption in VA 4.5 VA at 68 °F (20 °C)
Heat dissipation 1.3 W
Auxiliary contacts type Type instantaneous (1 NO)
Signalling circuit frequency <= 400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non overlap distance 0.02 in (0.5 mm)
Insulation resistance > 10 MOhm for signalling circuit