https://www.phoenixcontact.com/us/products/2906829
04/11/2017Page2/4
Surge protection device-TTC-6-TVSD-C-12DC-UT-I-2906829
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C3
Nominal voltage UN12 V DC
Maximum continuous voltage UC15 V DC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs (core-earth) 300 A
Voltage protection level Up (core-ground) ≤ 25 V (C1 - 0,6 kV / 300 A)
≤ 22 V (C3 - 25 A)
≤ 25 V (C3 - 60 A)
Response time tA (core-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 340 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 1.1 MHz
Capacity (core-earth) 2 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C1 - 0.6 kV/300 A
C3 - 60 A
Connection data
Connection method Screw connection
Connection method IN Screw terminal blocks
Connection method OUT Screw terminal blocks
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm