Electrical data
Primary nominal Primary current, Type RoHS since
current rms measuring range date code
IPN (mA) IPM (mA)
100 ± 200 CT 0.1-P 46129
200 ± 400 CT 0.2-P 46054
400 ± 800 CT 0.4-P 46234
VCSupply voltage (± 5 %) ± 15 V
I CCurrent consumption ± 45 mA
RIS Isolation resistance @ 500 VDC > 500 MΩ
VOUT Output voltage (Analog) @ ± IPN, RL= 10kΩ, TA=25°C ± 5 V
ROUT Output internal resistance < 51 Ω
RLLoad resistance ≥ 10 kΩ
CLCapacitive loading ≤ 5nF
Accuracy-Dynamic performance data
XAccuracy (excluding offset) @ IPN, TA = 25°C, RL = 10kΩ< ± 1 %of IPN
εLLinearity error (0 .. ± IPN)< ± 0.5 %of IPN
TCVOUT Temperature coefficient of VOUT (of reading) < ± 0.05 %/K
VOE Electrical offset voltage @ IP = 0, TA = 25°C < ± 100 mV
VOH Hysteresis offset voltage
@ IP = 0; after an excursion of 1 x IPN < ± 2 mV
@ IP = 0; after an excursion of 100 x IPN < ± 20 mV
TCVOE Temperature coefficient of VOE @ -20..+85°C CT 0.1-P < ± 8 mV/K
CT 0.2-P < ± 4 mV/K
CT 0.4-P < ± 2 mV/K
t rResponse time to 80% of IPN step ≤ 20 ms
90% of IPN step ≤ 60 ms
BW Frequency bandwidth (- 3 dB) CT 0.1-P DC 40..7000Hz
CT 0.2-P DC 40..11000Hz
CT 0.4-P DC 40..18000Hz
General data
TAAmbient operating temperature - 20 .. + 85 °C
TSAmbient storage temperature - 25 .. + 85 °C
dCp Creepage distance > 5.5 mm
dCl Clearance distance > 5.5 mm
CTI Comparative tracking index (Group IIIa) > 220
mMass 25 g
Standards EN 50178: 1997
Current Transducers CT 0.1 .. 0.4-P
For the electronic measurement of small currents: AC,DC, mixed,
with a galvanic isolation between the primary circuit and the
secondary circuit.
IPN = ± 100..400 mA
VOUT = ± 5 V
Features
•DC & AC earth leakage current
transducer using a flux-gate
principle
•PCB mounting
•±15V power supply
•±5V output @ IPN
•Isolated plastic case recognized
according to UL94-V0.
Advantages
•Small size
•Bandwidth :
DC and 40 up to 7..18 kHz
•Response time better than 60 ms
•Cost effective, compact
alternative to classical RCDs
(Residual Current Device)
Applications
•Earth leakage detection in
transformerless solar inverters
•1st human contact protection of
PV arrays
•Failure detection in power sources
•Symmetrical fault detection
(e.g. after motor inverter)
•Current leakage detection in
stacked DC sources
•Single phase or three phase
differential current measurement up
to ±30A per wire (DC or AC)
Application domain
•Industrial
copyright protected
080909/14 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
Notes : Performance data are given for steady phase of the transducer.
Transitory period after power on lasts typically less than 2 min.
Please refer to characterization report for details.
Please don't put the high voltage between the secondary pins and fixing
pins. If it must be so, don't exceed the 2.5 kV between these pins with the
maximum isolation distance.