SCD Number
SPECIFICATION CONTROL DRAWING 44A0711
Page 2 of 2
Revision
F
TEMPERATURE RATING: 150°C
Maximum continuous conductor temperature
VOLTAGE RATING: 600 volts (rms) at sea level
ACCELERATED AGING: 300 ± 2°C for 6 hours
Identification legibility, (AWG 24-4 only) 225 ± 2°C for 6 hours
BLOCKING: 150 ± 2°C for 24 hours
BRAID COLOR: Per MIL-STD-104, Class 2, except that light brown shall
be within munsell color limits (see Table III); nominal, 2.5 YR 3/6
FLAMMABILITY: 30 seconds (maximum); 3 in. (maximum);no flaming of facial tissue
HUMIDITY RESISTANCE: Insulation Resistance, 5000 Megohms for 1000 ft. (minimum)
IDENTIFICATION, STRIPING, OR BAND DURABILITY (AWG 24-4 only):
125 cycles (250 strokes) (minimum), 500 g weight
IMMERSION: Diameter increase 5% (maximum); no cracking, no dielectric breakdown
INSULATION ELONGATION AND TENSILE STRENGTH:
Primary Insulation,
Tensile Strength, 2500 lbf/in² (minimum), AWG 24-12
2000 lbf/in² (minimum), AWG 10-0
Elongation, 150% (minimum)
INSULATION FLAWS:
Primary Insulation,
SparkTest, 3.0 kV (rms) at 60 Hz
4.2 kV (rms) at 3 kHz
Impulse DielectricTest, 6.0 kV (peak)
Finished Wire;
SparkTest, 5.7 kV (rms) at 3 kHz
Impulse DielectricTest, 8.0 kV (peak)
INSULATION RESISTANCE: 5000 Megohms for 1000 ft. (minimum)
JACKET COLOR (AWG 2-0 only): White
LIFE CYCLE: 200 ± 2°C for 168 hours
LOW TEMPERATURE-COLD BEND: -65 ± 2°C for 4 hours
SHRINKAGE: 300 ± 2°C, 0.125 in. (maximum) in 12 in., AWG 24-12
300 ± 2°C, 0.250 in. (maximum) in 12 in., AWG 10-0
SMOKE: 200 ± 2°C. No visible smoke.
SOLDERABILITY: Per MIL-STD-202, Method 208, except without steam aging, Type RMA Flux
SURFACE RESISTANCE: 500 megohms-in. (minimum), both readings
THERMAL SHOCK: 150 ± 2°C, 0.060 in. (maximum), primary insulation and jacket only.
VOLTAGE WITHSTAND (POST ENVIRONMENTAL): 2500 volts (rms), 60 Hz, 5 minutes
WICKING: 2.25 in. (maximum) between primary insulation and jacket.
PART NUMBER: The "*" in the part numbers on page 1 shall be replaced by
color code designators except that Lt. brown shall be designated as -1L
For AWG 2-0, only the braid color shall be designated.
1/ Example:
AWG 20, white: 44A0711-20-9
AWG 20, white with black stripe: 44A0711-20-90
AWG 2, white jacket, Lt. brown braid: 44A0711-2-1L
1/ See footer section on page 1
WIRE RATINGS AND ADDITIONAL REQUIREMENTS
+ NOTE: For AWG 2-0, these tests are conducted prior to application of the braid.
+
+
+
+
HUE
VALUE
CHROMA
5R - 5YR
3.0 - 5.0
4.0 - 6.0
TABLE III.
MUNSELL COLOR LIMITS