2
Non resettable fuses
SP 6.3x32 www.schurter.com/PG01_2
Fuses
Time-Current-Curves
Time in Seconds
0.001
0.01
0.1
1
10
100
1000
10000
10
≤ 4 A
_
> 5 A
Multiple of Rated Current In
All Variants
Rated Cur-
rent [A]
Rated Vol-
tage [VAC]
Breaking
Capacity
Voltage Drop
1.0 In max.
[mV]
Voltage Drop
1.0 In typ.
[mV]
Power Dissi-
pation 1.5 In
typ. [mW]
Melting I²t 10.0
Intyp. [A²s]
Order Number
0.5 250 1) 3000 1000 3000 0.13 0001.1021
0.63 250 1) 2500 2500 3800 0.003 0001.1022
0.8 250 1) 2200 520 1200 0.06 0001.1023
1 250 1) 1900 410 1200 0.4 0001.1024
1.25 250 1) 1600 1600 5400 - 0001.1025
1.6 250 1) 1300 460 2100 1.2 0001.1026
2 250 1) 1000 340 2000 2.4 0001.1027
2.5 250 1) 700 350 2800 4.1 0001.1028
3.15 250 1) 600 270 3000 7.9 0001.1029
4 250 1) 550 270 3500 15 0001.1030
5 250 1) 500 240 3700 32 0001.1031
6.3 250 1) 450 170 4700 38 0001.1032
8 250 1) 400 250 6700 62 0001.1033
10 250 1) 350 150 5200 140 0001.1034 █
12.5 250 2) 300 150 7600 230 0001.1035
16 250 2) 250 130 8400 455 0001.1036 █
20 250 2) 250 130 11500 846 0001.1037 █
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) 1500 A @ 250 VAC , p.f. = 0.7 - 0.8
2) 1000 A @ 250 VAC , p.f. = 0.7 - 0.8
Packaging Unit Small Box Pack (10 pcs.)
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
26.03.2015