D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 1 of 8
www.murata-ps.com/support
www
.murata-ps.com
/
en
/
3d
/
acdc.htm
l
ww
w
.murata-ps.com
/
en
/
3d
/
acdc.htm
l
ww
w
.murata-
p
s.com/en/3d/acdc.htm
l
ww
w
.murata-ps.com
/
en
/
3d
/
acdc.htm
l
ww
w
.murata-
p
s.com/en/3d/acdc.htm
l
ww
w
.murata-ps.com
/
en
/
3d
/
acdc.htm
l
PRODUCT OVERVIEW
The D2U5T-H3-5000-380-HU3C is a High Efficiency 3500/5000 watt, power factor corrected three phase
power supply for 230/480Vac lines with a 380V high voltage (HVDC) main output and a selectable 5V or
3.3V (20W) standby. The unit is provided with Droop Sharing and up to three (3) power modules may be
operated in parallel.
The power module is hot pluggable. The module is able to protect and recover from over temperature
faults, and has status LEDs on the front panel and additional logic and PMBus status signals.
Their 2U package and >16.5W/cubic inch power density make them ideal for delivering reliable,
efficient power to servers, workstations, storage systems and other 380V HVDC distributed power
systems. An optional power shelf is also available that accommodates up to three (3) power modules.
FEATURES
5KW (480Vac), 3.5KW (230Vac) Output
Power
Very High Efficiency; 95.4% @ 50% FL
380V High Voltage Main Output
3.3V or 5V Standby Output
Nominal Dim’s: 5.1"(W) x 18"(L) x 3.3" (2U
16.5 watts/cubic inch power density
N+1 redundant (including hot docking)
Droop sharing on Main Output
Over-voltage, over-current, over-
temperature protections
Internal cooling fan
I2C Bus Interface with status indicators
Optional 19" power shelf
RoHS compliant
Two-year warranty
Available now at:
www.murata-ps.com/en/3d/acdc.html
ORDERING GUIDE
Model Number
Main Output
Standby Output
Airflow
D2U5T-H3-5000-380-HU3C
5000W 380V
3.3V or 5V
(Selectable) Front to Back
INPUT CHARACTERISTICS
Parameter
Conditions
Min
Typ
Max
Units
Input Frequency
47
50/60
63
Hz
Input Voltage Operating Range
Range 1
180
264
Vac
Range 2
320
528
Vac
Turn-on Voltage (Ramp-up)
Range 1
170
Vac
Range 2
280
Vac
Turn-off Voltage (Ramp-down)
Range 1
150
Vac
Range 2
260
Vac
Maximum Input Current
13
Arms
Inrush Current
Cold Start
30
Apk
Power Factor, Range 1, 60Hz
600W, 230 Vac
0.992
1750W (50%), 230 Vac
0.998
3500W (100%), 230 Vac
0.998
Power Factor, Range 2, 60Hz
600W, 480 Vac
0.910
2500W (50%), 480 Vac
0.995
5000W (100%), 480 Vac
0.995
OVERALL CHARACTERISTICS
Parameter
Conditions
Min
Typ
Max
Units
Output Power
Range 1
3500
W
Range 2
5000
Efficiency, Range 1
700W (20%), 230Vac
89.5
%
1750W (50%), 230Vac
93.6
3500W (100%), 230Vac
94.2
Efficiency, Range 2
500W (20%), 230Vac
92.6
2500W (50%), 230Vac
95.4
5000W (100%), 230Vac
95.4
The following curves represent the achieved efficiency performance for the D2U5T-H3-5000-380-HU3C
product compared against a recognized industry standard for efficiency rating.
The D2U5T-H3-5000-380-HU3C offers performance in excess of the industry standard limit as a required
percentage of loading.
Test methodology as per Ecova Generalized Test Protocol for Calculating the Energy Efficiency of Internal
AC-DC and DC-DC Power Supplies Revision 6.7
For
full details go to
www
.murata-ps.com/rohs
Test Certificate
and Test Report
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 2 of 8
www.murata-ps.com/support
EFFICIENCY PERFORMANCE CURVES
OUTPUT VOLTAGE CHARACTERISTICS
Output
Parameter
Conditions
Min
Typ
Max
Units
380V
Output Current
Range 1
0
9.2
Adc
Range 2
0
13.34
Voltage Set Point
@4.6A Range 1
380
Vdc
@6.67A Range 2
380
Voltage Droop
Min to Max Current, Range 1
7
Min to Max Current, Range 2
11
Line Regulation
0.1
%
Ripple Voltage & Noise
1
1
Vp-p
Load Capacitance
100
1000
μF
3.3VSB
Voltage Set Point
3.3
Vdc
Line and Load Regulation
3.14
3.46
Ripple Voltage & Noise
2
20MHz Bandwidth
75
mVp-p
Output Current
0
6
A
Load Capacitance
20
1000
μF
5VSB
Voltage Set Point
5
Vdc
Line and Load Regulation
4.76
5.24
Ripple Voltage & Noise2
20MHz Bandwidth
100
mVp-p
Output Current
0
4
A
Load Capacitance
20
1000
μF
1 Ripple and noise are measured with
22nF (U2J 630V) ceramic + 15 μF (UCC
KXJ) of electrolytic de-coupling
capacitors at the output connector load
side. A short coaxial cable with 50ohm
scope termination is used.
2 Ripple and noise are measured with
0.1 uF of ceramic capacitance and 10
uF of tantalum capacitance across the
power supply outputs at the output
connector load side. A short coaxial
cable with 50ohm scope termination is
used.
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 3 of 8
www.murata-ps.com/support
OUTPUT CHARACTERISTICS
Parameter Conditions Min Typ Max Units
Startup Time AC ramp up
3 s
Transient Response
380V, 50-100% load step, 0.1A/μs di/dt
15
Vp-p
5VSB, 50-100% load step, 1A/μs di/dt
250
mVp-p
3.3VSB, 50-100% load step, 1A/μs di/dt
165
mVp-p
Current sharing accuracy (up to 3 in parallel) 380V @100% load
+/-10 %
Hot Swap Transients All outputs within regulation
Holdup Time 380V @100% load 25
ms
VSB @100% Load 500
GENERAL CHARACTERISTICS
Parameter
Conditions
Min
Typ
Max
Units
Storage Temperature Range
-40
70
°C
Operating Temperature Range
-15
50
°C
Operating Humidity
Non-condensing
10
90
%
Storage Humidity
Non-condensing
5
90
%
Altitude
(Without derating at 40°C)
3000
m
(Without derating at 50°C)
1800
Shock
30G non-operating
Sinusoidal Vibration
0.5G, 5 – 500 Hz
MTBF
Calculated per Telcordia SR-332 @40°C
220K
hrs
Weight
7
kg
Safety Approvals
CAN/CSA C22.2 No 60950-1-07, Am.1:2011, Am 2:2014
ANSI/UL 60950-1-2014
IEC60950-1:2005 (2nd Ed.), Am 1:2009 + Am 2:2013
EN 60950-1:2006+A11:2009 +A1:2010 +A12:2011 +A2:2013
Input Fuses Power Supply has one internal 16A/500V fast blow fuse on each of the three AC line inputs.
Material Flammability UL 94V0
PROTECTION CHARACTERISTICS
Output Parameter Conditions Min Typ Max Units
Over-temperature (intake) Auto-restart 57 60 63 °C
380V
Over Voltage Latching 418
445 V
Over Current Range 1 Hiccup or Latching 105
130 %
Over Current Range 2 Hiccup or Latching 105
130 %
3.3VSB Over Voltage Latching 3.9
4.3 V
Over Current Hiccup 6.3
9 A
5VSB Over Voltage Latching 5.6
6.0 V
Over Current Hiccup 4.2
6 A
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 4 of 8
www.murata-ps.com/support
EMISSIONS AND IMMUNITY
Characteristic
Standard
Compliance
Input Current Harmonics
IEC/EN 61000-3-2
Complies
Conducted Emissions FCC 47 CFR Parts 15
CISPR 22 EN55022
Class A, 6dB margin
Radiated Emissions (in the application) Class A, 6dB margin
ESD Immunity IEC/EN 61000-4-2 Level 3 criteria A
Radiated Field Immunity IEC/EN 61000-4-3 Level 3 criteria B
Electrical Fast Transients/Burst Immunity
IEC/EN 61000-4-4
Level 3 criteria A
Surge Immunity IEC/EN 61000-4-5 Level 3 criteria A
RF Conducted Immunity IEC/EN 61000-4-6 Level 3 criteria A
Magnetic Field Immunity IEC/EN 61000-4-8 3 A/m criteria B
Voltage Dips & Interruptions
IEC/EN 61000-4-11
400Vrms Input Voltage
Main & VSB Outputs, Performance a)
100% load, Phase 0°, Dip 100% Duration 10ms
50% load, Phase 0°, Dip 100% Duration 20ms
Main & VSB Outputs, Performance b)
100% load, Phase 0°, Dip 100% Duration >10ms
Any Load, Phase 0°, Dip 100% Duration >100ms
Voltage imbalance
(Circuit will stop when input voltage imbalance exceeds
8% for more than 100ms. Unit will restart when
imbalance returns below 8%)
Any valid Input Voltage, any load
Main & VSB Outputs, Performance a)
Dip 30% on single Phase or Line, Duration 100ms
Main & VSB Outputs, Performance b)
Dip 30% on single Phase or Line, Duration >100ms
ISOLATION CHARACTERISTICS
Parameter Conditions Min Typ Max Units
Insulation Safety Rating/Test Voltage
Input to Output Reinforced 3000 Vrms
Input to Chassis Basic
1500 Vrms
Output to Chassis Basic
1150 Vrms
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 5 of 8
www.murata-ps.com/support
STATUS INDICATORS (LEDs)
Status Indicators Input OK (Green) Output OK (Green) Fault4 (Yellow)
AC input voltage is not present Off Off Off
AC present and within the required operational range
Standby ON; Main Output OFF (disabled)
Solid Green
Blinking
Off
AC present, but its level is not within the required operational range
Blinking Green at 1Hz
rate
(0.5s on, 0.5s off)
Off
Off
When hot-unplugging the power supply from a power shelf3
Blinking Green at 1Hz
rate
(0.5s on, 0.5s off)
Off
Off
AC present and within the required operational range
Standby ON and within the specified regulation range
Main Output ON and within the specified regulation range
Solid Green
Solid Green
Off
AC present and within the required operational range
Standby ON and within the specified regulation range
Main Output ON and within the specified regulation range
Main output overcurrent condition are indicated depending upon severity and application of
overload and specific detection mechanism responding:
Output power warning
Pout overpower fault
Iout overcurrent fault
Solid Green
Solid Green
Solid Green
Solid Green
Solid Green
Blinking Green
Blinking 1Hz
On
On
Any warning Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
No Change
No Change
Blinking 1Hz
Any Fault Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN) Depends on PS
Depends on PS Status
Depends on PS Status
3 The Input OK LED blinks to indicate that there is still energy inside the power supply until the input bulk capacitors are completely discharged or the
housekeeping circuit is shut down.
4 The Fault LED and PS Fault signal shall be turned on to indicate that there is one or more of the following internal faults currently detected inside the power supply:
VSB out of range
Output stage OT
Fan fault
ORING fault (Output voltage less than bus voltage)
OC shutdown
OT shutdown
OV shutdown
Input stage OT
Fault induced shutdown occurred
Thermal sensor fault
Vout out of range
PFC Boost Vbulk fault
As soon as all of the above faults are removed and the power supply operates normally, the Fault LED and PS Fault signal
shall be turned off. LED Definition: Three LEDs shall be located on the front faceplate; these are:
LED
Status
Input OK = ON
Output OK = ON
Fault = ON
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 6 of 8
www.murata-ps.com/support
CONTROL SIGNALS
Signal (I/O)
Description
PS_ON_H
Internal 10K pull-up resistor to internal VDD.5
Leaving signal pin open = Main Output ON
Tying signal pin to GND = Main Output OFF
PS_KILL
Short pin; internal 10K pull-up resistor to internal VDD.5
Leaving signal pin open = All Outputs off
Tying signal pin to GND = All Outputs enabled
PS_PRESENT
Interanally shorted to SIG_GND, STBY_RTN
used by system (where signal may be pulled up) for detection of a power module being installed into backplane.
PS_FAULT_L
Internal 10K pull-up resistor to internal VDD5
PSU Fault Status
PWR_GOOD_H
Internal 10K pull-up resistor to internal VDD.5
Main Output Status OK
STBY_SEL_IN
Internal 10K pull-up resistor to internal VDD5
Leaving signal pin open = +5VSTBY
Tying signal pin to GND = +3V3STBY
AC_OK_H
Internal 10K pull-up resistor to internal VDD.
5
AC OK Status
SMB_ALERT_L
Internal 10K pull-up resistor to internal VDD5
SMB Alert signal output
VOUT_PRE-CHARGE, +/-
Input to Power Module for hotswap function.
+ VOUT_PRE_CHARGE: internally pulled up via 1K OHM resistor to main output return “+“
- VOUT_PRE_CHARGE: internally pulled up via 1K OHM resistor to main output return “-“
A0, A1 & A2
Addressing bit lines used can be used to assign the power supply’s controller and EEPROM device PMBus address. The table below
lists the possible address combinations that can be assigned.
DEVICE ADDRESS PIN STRAPPING ADDRESS OPTIONS
Serial Address Bits
Corresponding Power Module Slave Device
A
ddr
ess
A2
Bit 2
A1
Bit 1
A0
Bit 0
PSU Main Controller
(
S
e
c
onda
ry)
PSU EEPROM
(External)
LO
W
LO
W
LO
W
0
x
B0
0
xA0
LOW
LOW
HIGH
0XB2
0xA
2
LOW
HIGH
LOW
0xB4
0xA
4
LOW
HIGH
HIGH
0XB6
0xA
6
HIGH
LOW
LOW
0XB8
0XA
8
HIGH
LOW
HIGH
0xBA
0xA
A
HIGH
HIGH
LOW
0xBC
0xA
C
HIGH
HIGH
HIGH
0xBE
0xAE
Each address line is pulled up via 10K to internal VDD
All three (3) pins unterminated result in address BE and AE respectively
Refer to Applcation notes ACAN-61 and ACAN-63 for further details
5 VDD depends on Standby Voltage selection of either 3.3V or 5V.
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 7 of 8
www.murata-ps.com/support
OUTPUT CONNECTOR & PIN ASSIGNMENT (Power Module Connector: FCI Power Blade Part # 51915-424 (MATING CONNECTOR: FCI 51939-826LF)
Pin
Designation
Function
Signal Direction
Pin
Designation
Function
Signal Direction
P13
-VOUT_PRE-CHARGE
Hot Swap Pre Charge
Output
B1
A2
I2C Address Bit 2 Signal
Input
P12
-VOUT
380Vdc return
Output
B2
PS_ON_H
Enable PSU
Input
P11
+VOUT_PRE-CHARGE
Hot Swap Pre Charge
Output
B3
+VSB
+3.3V/5V STBY Out
Output
P10
+VOUT
380Vdc
Output
B4
SDA
I2C Data Signal
Bi-Directional
P9
Not fitted
-
-
B5
PS_KILL
Enable PSU
Input
P8
Not fitted
-
-
B6
VSB_RTN
VSTBY_RT
Output
P7
AC1
AC Line Voltage Ph 1
Input
C1
STBY_SEL_IN
Selects +3V3 or +5VSTBY
Input
P6
Not fitted
-
-
C2
AC_OK_H
AC(DC) OK Status
Output
P5
AC2
AC Line Voltage Ph 2
Input
C3
+VSB
+3.3V/5V STBY Out
Output
P4
Not fitted
-
-
C4
+VSB
+3.3V/5V STBY Out
Output
P3
AC3
AC Line Voltage Ph 3
Input
C5
VSB_RTN
VSTBY_RT
Output
P2
Not fitted
-
-
C6
VSB_RTN
VSTBY_RT
Output
P1
GND
Safety ground
Input
D1
SMB_ALERT_L
SMB Alert signal output
Output
A1
A1
I2C Address Bit 1 Signal
Input
D2
PWR_GOOD_H
Power OK Status
Output
A2
PS_FAULT_L
PSU Fault Status
Output
D3
+VSB
+3.3V/5V STBY Out
Output
A3
A0
I2C Address Bit 0 Signal
Input
D4
+VSB
+3.3V/5V STBY Out
Output
A4
PS_PRESENT
PSU Seated into Connector
Output
D5
VSB_RTN
VSTBY_RT
Output
A5
SCL
I2C Clock Signal
Bi-Directional
D6
VSB_RTN
VSTBY_RT
Output
A6
SGND
Signal ground (return)
Output
CHANICAL
DIMENSIONS
D2U5T-H3-5000-380-HU3C
AC-
DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C.A04 Page 8 of 8
www.murata-ps.com/support
MECHANICAL DIMENSIONS
OPTIONAL ACCESSORIES
Description Part Number
12V D2U5T-380 Output Connector Card D2U5T-380-CONC
APPLICATION NOTES
Document Number Description Link
ACAN-62 D2U5T-380-CONC Customer Interface Connector Card
http://power.murata.com/datasheet?/data/apnotes/acan
-62.pdf
ACAN-63 PMBusTM Communication Protocol for:
D2U5T-H3-5000-380-Hu3C
http://power.murata.com/datasheet?/data/apnotes/acan
-63.pdf
Murata Power Solutions, Inc.
129 Flanders Road
Westborough, MA 01581
ISO 9001 and 14001 REGISTERED
This product is subject to the following operating
require
ments and the Life and Safety Critical Application Sales
Policy.
Refer to: http://www
.murata-ps.com/requirements/
Murata Power Solutions, Inc. (“Murata”) makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon
existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Buyer represents and agrees that
it
has all
the necessary expertise to create and implement safeguards that anticipate dangerous consequences of failures, monitor failures and their consequences, lessen the likelihood of failures that might cause harm, and
take appropriate remedial actions. Buyer will fully indemnify Murata, its affiliated companies, and its representatives against any damages arising out of the use of any Murata products in safety-critical applications.
Specifications are
subject
to change without
notice.
©
2018 Murata Power Solutions,
Inc.