Release date 2014-08-19 09:56 Date of issue 2015-02-16 231197_eng.xml
KFU8-UFC-Ex1.D
1
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Frequency Converter with Trip Values
Zone 0, 1, 2
Div. 1, 2
KFU8-UFC-Ex1.D
3-
1+
16
17
18
10
11
12
I
II
19+
20-
III
13+
14-
7-
8+ IV
AC/DC
23
24
mA
10 k10 k
400 Ω ≤ R 2 k
Connection
Assembly
1-channel isolated barrier
Universal usage at different power supplies
Input for NAMUR sensors or dry contacts
Input frequency 1 mHz ... 5 kHz
Current output 0/4 mA ... 20 mA
Relay and transistor output
Start-up override
Line fault detection (LFD)
Up to SIL2 acc. to IEC 61508/IEC 61511
Function
This isolated barrier is used for intrinsic safety applications.
The device is a universal frequency converter that changes a
digital input signal into a proportional free adjustable
0/4 mA ... 20 mA analog output signal and functions as a
switch amplifier and a trip alarm.
The functions of the switch outputs (2 relay outputs and
1 potential free transistor output) are easily adjustable [trip
value display (min/max alarm), serially switched output, pulse
divider output, error signal output].
The device is easily configured by the use of keypad or with
the PACTware configuration software.
A fault is signalized by LEDs acc. to NAMUR NE44.
For additional information, refer to the manual and
www.pepperl-fuchs.com.
2
Features
ESC
OK
KFU8-UFC-
Ex1.D
RS232
PWR1
12
3
IN/
CHK
OUT
19 21
15
9
13
7
20
14
8
22 24
18
12
16
10
23
17
11
13
24
6
5
Front view
Removable terminals
green
Removable terminal
blue
Keypad
LC display
LED green:
Power supply
LED yellow/red:
Input pulses/
fault signal
LED yellow:
Output I ... III
Programming jack
Place for labeling
Release date 2014-08-19 09:56 Date of issue 2015-02-16 231197_eng.xml
Technical data KFU8-UFC-Ex1.D
2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
General specifications
Signal type Digital Input
Supply
Connection terminals 23, 24
Rated voltage Un20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Power loss/power consumption 2 W ; 2.5 VA / 2.2 W ; 3 VA
Input
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration > 50 µs
Input frequency 0.001 ... 5000 Hz
Lead monitoring breakage I 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit
current
18 V / 5 mA
Output
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ 0.7 ; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III electronic output, passive
Contact loading 40 V DC
Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current 10 µA)
Output IV analog
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage 24 V DC
Load 650
Fault signal downscale I 3.6 mA , upscale 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Input I
Measurement range 0.001 ... 5000 Hz
Resolution 0.1 % of the measurement value , 0.001 Hz
Accuracy 0.1 % of the measurement value , > 0.001 Hz
Measuring time < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay 200 ms
Output IV
Resolution < 10 µA
Accuracy < 20 µA
Influence of ambient temperature 0.005 %/K (50 ppm)
Electrical isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Start-up override/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Release date 2014-08-19 09:56 Date of issue 2015-02-16 231197_eng.xml
Technical data KFU8-UFC-Ex1.D
3
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate TÜV 99 ATEX 1471 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C Tamb 60 °C)
Supply
Maximum safe voltage Um253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Input I terminals 1+, 3- Ex ia IIC, Ex iaD
Voltage Uo 10.1 V
Current Io 13.5 mA
Power Po 34 mW (linear characteristic)
Input II terminals 13+, 14- non-intrinsically safe
Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage Um253 V (Attention! The rated voltage can be lower.)
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Output III terminals 19+, 20- non-intrinsically safe
Maximum safe voltage Um Um40 V (Attention! Um is no rated voltage.)
Output IV terminals 8+, 7- non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
Interface RS 232
Maximum safe voltage Um40 V (Attention! Um is no rated voltage.)
Electrical isolation
Input I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007
International approvals
FM approval
Control drawing 16-538FM-12
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
PACTware
Device-specific drivers (DTM)
Adapter K-ADP1
Programming adapter for parameterisation via the serial RS 232 interface of a PC/Notebook
For programming, please use the new version of adapter K-ADP1 (part no. 181953, connector length 14mm). When using the
previous version K-ADP1 (connector length 18 mm) the plug is exposed by approx. 3 mm. The function is not affected.
Adapter K-ADP-USB
Programming adapter for parameterisation via the serial USB interface of a PC/Notebook
Accessories