73
L
N
L
N
L
N
L3L32 L
STEGO - PRODUCT CATALOGUE REGULATING
TECHNICAL DATA
Switch temperature difference 5 K (-3/+2 K tolerance)¹
Sensor element thermostatic bimetal
Contact type change-over snap-action contact
Service life > 100,000 cycles
Min. switching capacity 10 mA
Max. switching capacity, NC AC 250 V / AC 120 V, 10 (4) A
DC 30 W
Max. switching capacity, NO AC 250 V / AC 120 V, 5 (2) A
DC 30 W
Max. inrush current AC 16 A for 10 sec.
Connection
4-pole terminal, clamping torque 0.5 Nm max.:
rigid/stranded² wire 2.5 mm² (AWG 14)
Mounting clip for 35 mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 38 mm
Weight approx. 0.1 kg
Fitting position variable
Operating/Storage temperature -45 to +65 °C (-49 to +149 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type IP20
Approvals UL File No. E164104, EAC
¹ If the Normally Closed contact is used, the switch temperature difference could be reduced by connecting terminal "N"
(RF heating resistor). It causes the thermal feedback which is subject to surrounding conditions and thus has to be determi
ned
for each individual application.
² When connecting with wires, wire end ferrules must be used.
The mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices.
The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action
contact. Functionality: The temperature setting on the scale equals to the upper switch point, which means that
the NC contact opens. The temperature setting minus switch temperature difference (and tolerances) equals to
the lower switch point, which means that the NC contact closes.
> Adjustable temperature
> High switching capacity
> Small hysteresis
> Change-over contact
> Clip fixing
Connection diagram
Heater Thermostat
FZK 011
Thermostat
FZK 011
e.g. Filter fan
for cooling
e.g. Signal device Thermostat
FZK 011
Examples of connection
Heater
Filter fan,
Cooling equipment,
Signal device
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may
change. This can lead to a voltage drop and/or self-heating of the contacts.
MECHANICAL THERMOSTAT
FZK 011
Art. No. Operating voltage Setting range
01170.0-00 AC 230 V +5 to +60 °C
01170.0-01 AC 230 V +40 to +140 °F
01170.0-02 AC 230 V -20 to +35 °C
01170.9-00 AC 120 V +40 to +140 °F
01170.9-01 AC 120 V +5 to +60 °C
19.03.2019 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
73
TECHNICAL DATASHEET