Data sheet
VSPC BASE 2/4CH FG Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date February 16, 2021 10:35:34 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 3
Connection data
Type of connection Screw connection Stripping length, rated connection 7 mm
Tightening torque, min. 0.5 Nm Tightening torque, max. 0.8 Nm
Clamping range, min. 0.5 mm² Clamping range, max. 4 mm²
Wire cross-section, solid, min. 0.5 mm² Wire cross-section, solid, max. 4 mm²
Wire connection cross section, finely
stranded, max. 2.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), min. 0.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), max. 2.5 mm²
Connection cross-section, stranded, min.
0.5 mm²
Connection cross-section, stranded,
max. 2.5 mm²
Blade size
0.6 x 3.5 mm
Ratings IECEx/ATEX/cUL
cUL certificate cUL Certificate
Classifications
ETIM 6.0 EC000472 ETIM 7.0 EC000472
ECLASS 9.0 27-13-08-03 ECLASS 9.1 27-13-08-07
ECLASS 10.0 27-13-08-03 ECLASS 11.0 27-13-08-03
Tender specification sheets
Long specification Base element can take
a protected plug for up
to four floating-ground
powered cables. When
the base unit is fitted, a
simultaneous sparkover
gap to high impedance
earth is made between
the mounting rail (earth)
and the reference potential
(ground) of the protective
switch in the plug.
Mechanical coding of
the base element to the
protected plug according
to switching type and rated
voltage. The base unit is
coded itself by the first
insertion of a protected
plug. Possible to mark all
terminals
Short specification
Base element receives
a protected plug for up
to four floating-ground
powered cables with
indirect earthing
Approvals
Approvals
ROHS Conform
UL File Number Search E311081