Emergency stop module with 1 channel
-
22,5 mm
-
KNA (C) 3
-
YS KNA3
-
YS Part number 85102035
"Emergency stop" & "Gate monitoring" functions
Single channel operation
Security with redundancy and feedback circuit
3 "NO" security contacts
1 "NC" monitoring contact
Security category 3 (according to EN 954-1)
Performance Level (PL) d, safety category 3 to EN ISO 13849-1
SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
Terminals : fixed screw terminals or plugin cage clamp terminals
Part numbers
Specifications
Type
Terminals
Voltages
Supply frequency range (Hz)
85102035
KNA3
-YS
Screws
230 VAC
50/60
Operating characteristics
Functions
Emergency stop
Monitoring of safety gates
Operation
1 channel
Control input
Manual restart with On-button (Y1 - Y2 terminals)
Automatic restart (Y1 - Y2 linked)
Failure detection
Between terminal Y1 and common
Display of output state by LED
Power supply : PWR
Outputs : OUT (relays K1 & K2)
Supply
Supply voltage
85 102 031 / 85 103 031 : 24 VDC
85 102 034 / 85 103 034 : 110 VAC
85 102 035 / 85 103 035 : 230 VAC
Supply frequency range (Hz)
50 / 60 for AC versions
Operating range
AC : -
15 % / +10 % U
DC :
±
10 % U (at 10 % residual ripple)
DC :
- 15 % / +10 % U (at 48 % residual ripple)
Consumption
1,5 W (24 VDC)
3,5 VA (230 VAC)
Initialization time
0,5 s
Precision
Maximum reset time
40 ms (24 VDC)
200 ms (230 VAC)
Maximum response time on emergency stop
70 ms (24 VDC)
35 ms (230 VAC)
Output specification
Type
Forcibly guided relays (positively driven)
Number of safety circuits
3 NO
Number of data circuits
1 NF
Nominal output voltage
250 VAC max.
Max. thermal current I for each contact
5 A
Maximum power rating
According to AC15 (NO contacts) : 3 A / 230 V AC
According to AC15 (NC contacts) : 2 A / 230 VAC
According to DC13 (NO contacts) : 4 A / 24 VDC ; 0,5 A / 110 VDC
According to DC13 (NC contacts) : 4 A / 24 VDC
Electrical endurance
At 5 A, 230 VAC, cos φ
=
1 : 1,5 x 105 switching cycles
At 8 A, 24 VDC, according to DC 13 (NO contacts) : 25 x 103
(ON : 0,4 s ; OFF : 9,6 s)
Mechanical life
20 x 106 switching cycles
Maximum rate
600 switching cycles / h
Protection against short circuits
Max. fuse rating : 10 A gL
Line circuit breaker : B 6 A
Climatic environment
Operating temperature (
o
C)
-
15→+55°C
Storage temperature (0
C)
-
25→+85°C
Altitude
< 2000m
Climate resistance according to IEC/EN 60068
-1
15 / 055 / 04
Mechanical environment
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Vibration resistance according to IEC/EN 60068
-2-6
Amplitude : 0,35 mm
Frequency:10→55Hz
Electromagnetic environment
Immunity to electrostatic discharges acc.
IEC/EN 61000
-4-
2
8 kV (air)
Immunity to radiated, radio
-frequency, electromagnetic
field acc. IEC/EN 61000
-4-3
10 V / m
Immunity to rapid transient bursts acc. to IEC/EN 61000
-4-
4
2 kV
Immunity to shock waves according to IEC/EN 61000
-4-5
Between wires for power supply : 1 kV
Between wires and ground : 2 kV
Immunity to radio frequency in common mode acc. to
IEC/EN 61000
-4-6
10 V
Interference suppression according to IEC/EN 55011
Limit value class B
Housing
Material : self
-extinguishing (UL94VO)
Thermoplastic with V0 extinction behaviour
Protection (IEC/EN 60529)
-
Casing
IP40
Protection (IEC/EN 60529)
-
Term. block
IP20
Mounting
DIN
-
rail
Weight (g)
200 (24 VDC)
270 (230 VAC)
Safety standards
Approvals
CE, TÃœV, UL/CSA
Environmental directive 2002/95/CE
RoHS
Environmental regulation 1907/2006
Reach
Security data according to EN ISO 13849
-1
Performance Level (PL) : d
Category : 3
SIL Claimed Level (SIL CL) to IEC/EN 62061
2
Safety Integrity Level (SIL) according to CEI/EN 61508
2
Safety category to EN 954-1
3
Principles
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Dimensions (mm)
Dimensions (mm)
KNA3
-
YS
- Screw terminals
Curves
Function diagram
Connections
Front face drawing KNA3-
YS
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A1 (+)
: + / L
A2 : -
/ N
Y1, Y2
: Validation Input
Y21 (-) : Measure Output (-) of secondary used for example in IT networks for insulation control 13, 14, 23, 24, 33, 34 : Safety circuit outputs
(forcibly guided NO contacts) 41, 42 : Monitoring output (forcibly guided NC contact)
Connections
Contacts
Applications
Single channel emergency-stop circuit without feed back loop, with or without automatic restart
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
For automatic restart, terminals Y1 -
Y2 must be linked. No ON
-pushbutton necessary
For currents > 5 A, the output contacts can be reinforced by external contactors. Functioning of the external contactors is monitored by looping the NC contacts into the start circuit (Y1-Y2)
Applications
Contact reinforcement by external contactors
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Crouzet:
85102035