LE7M-2 Weekly/Yearly Timer W72xH72mm, Weekly/Yearly timer (A) Photo electric sensor Features (B) Fiber optic sensor Easy to check and change the program setting Customizable weekly or yearly unit time setting and control by user Includes daylight saving time function Built-in 2 independent control output (relay) Flush and surface mounting are in one unit Enable to mount on DIN rail with base plate (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor Please read "Caution for your safety" in operation manual before using. (F) Rotary encoder (G) Connector/ Socket Ordering information LE7 M 2 (H) Temp. controller Output Size Item 2 2 Relay outputs M DIN W72xH7mm LE7 Weekly/Yearly timer (I) SSR/ Power controller (J) Counter (K) Timer Specifications Model LE7M-2 Power supply 100-240VAC 50/60Hz Allowable voltage range 90 to 110% of rated voltage Power consumption Max. 4.2VA RETURN input Short-circuit or open by switch or relay Timing program 48 steps for weekly, 24 steps for yearly Operation mode ON/OFF mode, cycle mode, pulse mode Mounting Front panel, surface, DIN rail Time deviation 15sec./month(ambient temperature: 25) (4sec. /week) Temperature error 0.01% 0.05sec.(ratio by set time) Memory protection Over 5 years(at 25) Control Output Contact type SPDT(Single Pole Double Throw) Contact capacity 250VAC 10A resistive load Output number Independent 2 output(1c x 2) Mechanical Relay life cycle Electrical Min. 5,000,000 operations(switching capacity: 30 times/min) Insulation resistance Min. 100M(at 500VDC megger) Dielectric strength 2000VAC 50/60Hz for 1minute Noise strength 2kV the square wave noise(pulse width: 1) by the noise simulator Environ -ment Unit weight (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device Min. 50,000 operations Ambient temperature -10 to 55, storage: -25 to 65 Ambient humidity 35 to 80%RH (T) Software (U) Other Approx. 272g Environment resistance is rated at no freezing or condensation. K-75 LE7M-2 Connections OUT2 N.C. RETURN INPUT N.O. COM 6 7 8 9 10 1 2 3 4 5 COM N.C. N.O. OUT1 SOURCE CONTACT OUT 250VAC 10A RESISTIVE LOAD 100-240VAC 50/60 4.2VA Load connection You must connect a surge absorber to the both ends of the load to prevent from damage or malfunction of this unit when controlling non-resistive load (ex: magnetic switch, etc). In case of controlling the load directly N.O. N.C. COM 1 Power circuit for load operation 2 3 4 5 SOURCE Load In case of controlling the load by using a magnetic switch [Single phase] Power of single phase N.O. [Three phase] Power of three phase N.C. COM 1 2 S/A 3 4 5 COM 1 SOURCE 2 S/A 3 4 5 SOURCE Magnetic Switch Magnetic Switch Load K-76 N.C. N.O. S/A : Surge Absorber Load S/A : Surge Absorber Weekly/Yearly Timer Dimensions & Mounting (unit: mm) 1) Front panel mounting Panel cut-out 60 Min. 91 67.5 2) Surface mounting 64 55 (B) Fiber optic sensor Min. 91 72 (C) Door/Area sensor 68 +0.7 0 7 86 (A) Photo electric sensor 68 +0.7 0 (D) Proximity sensor (E) Pressure sensor 67 13.5 Panel hole cut-out Panel (F) Rotary encoder 4-M3 TAP 85 95 85 (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller 55 3) DIN rail mounting 64 76.5 Base Plate 9.5 (J) Counter 9 67.6 (K) Timer (L) Panel meter 95 95 DIN rail (M) Tacho/ Speed/ Pulse meter Base plate (N) Display unit How to switch from the flush mounting to surface mounting type Remove terminals from the body after unscrewing terminal screws, and then assemble terminals to the body after rotating terminals as shown below. Unscrew 4 bolts from terminal block. Detach terminal block from case and then rotate it 180 degree. (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (Front panel mounting) (S) Field network device Assemble terminal block to case by using the 4 bolts. (T) Software (U) Other (Surface mounting) K-77 LE7M-2 Parts description 10 1 11 2 12 3 13 4 14 5 15 6 16 7 17 8 18 9 19 20 23 21 24 22 1. Day indicator 2. Day display Light : Day is selected. Light-out : Day is not selected. 3. Current time setting mode indicator 4. DST display(Daylight saving time) 5. AM/PM display 6. Season display 7. Program display 8. Display ON time/day, OFF time/day, ON time width, OFF time width 9. AM/PM display 10. YEAR display : It turns ON when set, check, modify, delete yearly program, set yearly holidays and operate yearly program. 11. Yearly START/STOP day display 12. Main display 13. Remaining step display 14. Operation mode display 15. Power restore input display 16. Output mode display 17. Year, month, date display 18. Unit of pulse width display 19. Sub-display 20. CHECK key 21. MODE key 22. Operation key 23. Output selection switch AUTO : Control output according to the set program. ON : Output is ON.(Operation) OFF : Output is OFF. Output 1(OUT1) and Output 2(OUT2) are selected independently. 24. SET key Functions Program setting and output operation Output1/Output2 operates according to Program1 and Program2. Definitions Weekly ON/OFF mode Output operation by ON/OFF set time. * Min. time setting unit : 1 min. * It is able to set ON/OFF day separately. * One record in two Steps(ON day/ON time, OFF day/OFF time) Record : A part of program that controls output operation. Step : Basic component of record. Operation modes If the operation mode of Program1(Program2) is set on pulse mode initially, the pulse mode is fixed for additional programs. If the operation mode of Program1(Program2) is set on ON/OFF or cycle mode initially, pulse mode cannot be used for additional programs. K-78 ON time OFF time Weekly Cycle mode Output turns ON for ON time and turns OFF for OFF time. And the ON/OFF cycle is repeated. Weekly/Yearly Timer * Set range for ON/OFF time width : 1min. to 12 hour 59min. * One record in 3 steps(ON day/ON time, OFF day/OFF time, ON time width/OFF time width) OFF width ON time ON width OFF time Weekly pulse mode Output turns ON at ON time for a specified pulse width. (Pulse width : 1 to 59sec., 1 to 60min.) * One record in two steps(ON day/ON time, pulse width) Pulse width (1 to 59sec., 1 to 60min.) ON Time Yearly ON/OFF mode Output turns ON at ON time on START date and turns OFF at OFF time on STOP date. * One record in three steps(START/STOP date, ON/OFF time) Yearly pulse mode Output turns ON at ON time on START date and turns OFF at OFF time on STOP time for a specified pulse width repeatedly.(Pulse width : 1 to 59sec., 1 to 60min.). * One record in three steps(START/STOP date, ON time, pulse width) Program operation Weekly setting 1 of Program1 Weekly setting 2 of Program1 Yearly setting 1 of Program1 Program1 mode to : Operated by weekly setting 1 of Program 1. to : Operated by weekly setting 2 of Program 1. to : Operated by weekly setting 1 of Program 1. to : O perated by yearly setting 1 of Program 1. (During weekly program operation at 12:00 AM on START date, the weekly program operation stops, and it changes to yearly program operation mode. The yearly program operation stops at 12:00 AM on the next day of STOP date.) Display and change of next mode The day of next mode in Program1 or Program2 is displayed on the day indicator, and the time of next mode + is displayed on the lower row of screen. Press in RUN mode it is changed from program1 to program2 or from program2 to program1. In ON/OFF operation mode, set ON time and OFF time to next mode. In Pulse operation mode, set Pulse ON time to next mode. Power restore mode In setting group 2-Level 2(Power restore), select auto [AT] or key, and press key to set. or normal [NOR] by Auto [AT] power restore mode Output(OUT1, OUT2) operates according to program when power turns on again after power failure. Normal [NOR] power restore mode When power turns on again after power failure, output is kept OFF and RET.IN flashes on the panel. When power restore input is detected, RET.IN turns off and output operates according to program. * Power restore input Input contact signal in external "Return input terminals ( key for 3sec. in to )" by switch or relay, or press RUN mode. Please use reliable contacts enough to flow 0.1mA of current at 5VDC when use switch or relay. Season switching mode This feature uses for setting seasonal weekly operation mode. To operate this mode, save starting month and date, ending month and date of each season which displays S1, S2, S3, S4 then set day and time of each season in weekly program setting. It is also able to operate only in summer and winter season. (S1: set summer season, S2: set winter season, S3/S4: do not set) At the season switching selection LEVEL 2 status in setting 2 group (SEN turns ON, OFF flashes), select ON [ON] by or key and press key to complete the pressing season switching. Be sure that if changing season switching from OFF to ON or, ON to OFF, the weekly program 1(P1) and the weekly program 2 (P2) which are set before are deleted. ON [ON] mode Weekly program is switched automatically by season switching. * Period setting per season At the season switching selection LEVEL 2 status in setting 2 group (SEN flashes, the set season turns ON, key. START and STOP turn ON), press Advance to the flashing position of season selection or key and press among S1, S2, S3, S4 by key. After set START month, date per season and press key. key is pressed after set STOP month, date per season, it is advanced to LEVEL1 of period setting per season. key. Add or adjust the period setting by It is disable to use when it is OFF [OFF]. If season terms are overlapped, these are prioritized in S4>S3>S2>S1 order. K-79 (A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other LE7M-2 Daylight saving time To utilize daylight during the summer season, daylight saving time is adjusted forward one hour from standard time. In setting group 2-LEVEL 2(DST turns ON, AT or NOR or key flashes.), select Auto [AT] or Normal [NOR] by key to set. and press Auto[AT] Daylight Saving Time mode Current time will be faster as an hour when it is started and slower as an hour when it is finished. * Automatic Daylight Saving Time period setting Automatic Daylight Saving Time period setting LEVEL 1 of setting group 2. (DST flashes and START and STOP turn ON.) Set START date(Month, date) of automatic Daylight key. Saving Time mode and press Set START time(AM/PM, Hour) of automatic Daylight key. Saving Time mode and press But, the minute will be fixed as 00. Set STOP date(Month, date) of automatic Daylight key. Saving Time mode and press Set STOP time(AM/PM, Hour) of automatic Daylight key. But, the minute Saving Time mode and press will be fixed as 00. Normal [NOR] daylight saving time mode key over 3sec. in RUN mode, +1h turns ON Press and current time is faster as an hour and +1h turns ON out key over 3sec. again. or vice versa, when press Current time setting (Ex) Set the current time as 10, Mar, 2008, 5:10 PM. Advance to the current time setting mode SUN MON TUE WED THU FRI SAT + keys are pressed over 3sec. in RUN mode, it is advanced to current time setting of setting group 2 and clock will be flashed and tAJ will be lighted in second display key. part, press Year, month, date setting SUN MON TUE WED THU FRI SAT Press or key to set 08 (year 2008) and move the flashing digit to position month by key. key after press Press or key to set date 10. Current time(AM, PM) setting SUN MON TUE WED THU FRI SAT Press or key to select PM and move the flashing digit to position hour by key. Current time(Hour, Min.) setting SUN MON TUE WED THU FRI SAT Press or key to set 5 PM and move the flashing digit to position min. by key. Press or key to set 10min. and press key and it is returned to RUN mode when press key over 3sec. It advances to "Current time setting mode" in ON status and set current time as shown above to by key. Current time is set up to 31, Dec., 2099. Check current year/month/date in RUN mode When key is pressed over 3sec. in RUN mode, it advances to current year/month/date display. After display current year/month/ date for 3sec., it returns to RUN mode displaying current display. K-80 Weekly/Yearly Timer Program setting Setting group 1 Setting group 2 RUN mode RUN mode Press MODE key for 3sec. Press MODE key for 3sec. (Setting group 1) Program1 weekly programsetting mode (PROG P1 flashes) MODE MODE MODE MODE MODE SET SET MODE LEVEL2 SET All Program1 yearly program delete (Setting group 2) LEVEL2 Current time setting Power failure return selection LEVEL2 SET Standard day, change day setting LEVEL2 SET Yearly holiday operation mode setting MODE (E) Pressure sensor LEVEL2 SET (G) Connector/ Socket Season switching selection (H) Temp. controller MODE LEVEL1 Period setting for season mode (SEN flashes, period-set season turns ON and START or STOP turns ON) LEVEL2 SET Period setting per season (I) SSR/ Power controller (J) Counter MODE LEVEL1 Daylight saving time mode (DST flashes, AT or NOR turns ON) 2 LEVEL2 SET Daylight saving time selection MODE Automatic[AT] daylight saving time period setting mode [DST] flashes, START or STOP turns ON) LEVEL2 SET (K) Timer (L) Panel meter Automatic daylight saving time period setting (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller MODE All Program2 yearly program delete (C) Door/Area sensor (F) Rotary encoder LEVEL2 SET (B) Fiber optic sensor (D) Proximity sensor LEVEL2 SET LEVEL1 Season switching selection mode (SEN flashes, ON or OFF turns ON) 1 SET LEVEL1 Power failure return selection mode (RET flashes, AT or NOR turns ON) All Program1 weekly program delete All Program2 weekly program delete LEVEL1 LEVEL1 LEVEL1 Yearly holiday operation mode (hDY, YEAR flash) MODE LEVEL2 LEVEL1 Weekly day change mode (cDY flashes) Program2 yearly program setting LEVEL2 LEVEL1 Program2 yearly program delete mode (PROG P2, YEAR, CLR flash) MODE SET LEVEL1 Program1 yearly program delete mode (PROG P1, YEAR, CLR flash) Program1 yearly program setting LEVEL2 LEVEL1 Program1 weekly program delete mode (PROG P2, CLR flash) Program2 weekly program setting Press MODE + SET key for 3sec. Current time setting mode (Clock icon flashes) Program1 weekly program setting LEVEL2 SET LEVEL1 Program1 weekly program delete mode (PROG P1, CLR flash) MODE SET LEVEL1 Program2 yearly program setting mode (PROG P2, YEAR flash) LEVEL2 LEVEL2 LEVEL1 Program1 Yearly programsetting mode (PROG P1, YEAR flash) MODE SET LEVEL1 Program2 weekly programsetting mode (PROG P2 flashes) Press MODE key for 3sec. MODE LEVEL1 MODE (A) Photo electric sensor 1: Season switching selection is OFF. 2: Automatic switching selection of Daylight Saving Time is Normal [NOR]. When it advances to setting group 2 in RUN mode, output (OUT1, OUT2) will be OFF. When power of time switch is ON again in setting group 2, it returns to previous setting group 1. Front MODE key is pressed in LEVEL2 of setting group 2, it returns to previous LEVEL1. When season switching selection is changed from OFF to ON or ON to OFF, previous set weekly program will be deleted. (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other When it advances to setting group 1 in RUN mode, output (OUT1, OUT2) will be OFF. It returns to previous setting group 1 when power of time switch is ON again in setting group 1. When MODE key is pressed in LEVEL2 of setting group 1, current setting will be canceled and it returns to previous LEVEL1. K-81 LE7M-2 OFF time setting(AM, PM) Weekly program setting Weekly ON/OFF mode (Ex) Output1(OUT1) is ON from Monday to Friday at 8:00 AM and OFF at 6:10 PM. SUN MON TUE WED THU FRI SAT 8:00 6:10 8:00 6:10 8:00 6:10 8:00 6:10 8:00 6:10 AM PM AM PM AM PM AM PM AM PM Advance to program1(P1) weekly program setting mode SUN MON TUE WED THU FRI SAT SUN MON TUE WED THU FRI SAT Select PM by or key and move the flashing to hour position by key. OFF time setting(Hour, Min.) SUN MON TUE WED THU FRI SAT Move the flashing to minute position after set 6:00 by or key and set the minute as 10 and press SET key. key is pressed over 3sec. in RUN mode, PROG P1 flashes and press SET key. MODE Complete to set SUN MON TUE WED THU FRI SAT Mode type setting SUN MON TUE WED THU FRI SAT Press mode. SET ON day setting SUN MON TUE WED THU FRI SAT Press key to move the indicator to monday, it will be lighted when or key are pressed and move it to tuesday by key. Press SET key after tuesday, wednesday, thursday, friday turn ON. ON time setting(AM, PM) SUN MON TUE WED THU FRI SAT key is pressed, move the flashing to hour position and select PM by or key when ON time is afternoon. ON time setting(Hour, Min.) SUN MON TUE WED THU FRI SAT or key Set 8:00 by and press SET key. OFF day setting SUN MON TUE WED THU FRI SAT K-82 Press SET key to set additional program. key in ON/OFF Weekly pulse mode Output2(OUT2) is ON for 10sec. at 8:00AM from monday to friday during S2 season in case, period of S1, S2, S3, S4 is set. SUN MON 8:00 AM TUE 8:00 AM WED 8:00 AM THU 8:00 AM FRI 8:00 AM 8:00 AM ON for 10sec. Program2(P2) advance to weekly program setting mode SUN MON TUE WED THU FRI SAT SAT 8:00 AM MODE key is pressed for 3sec.in RUN mode, PROG P1 is flashed and press MODE key again, PROG P2 flashes and press SET key. Mode type setting SUN MON TUE WED THU FRI SAT or key when Press ON /OFF flashes, Pulse flashes and press SET key. Season selection Press SET key to check ON/OFF day. SUN MON TUE WED THU FRI SAT or key to select Press season S2 and press SET key. Weekly/Yearly Timer ON day setting SUN MON TUE WED THU FRI SAT Press key to move the indicator to Monday, it will be lighted when or key is pressed and move it to Tuesday by key. Press SET key after light Tuesday, Wednesday, Thursday and Friday. ON time setting(AM, PM) SUN MON TUE WED THU FRI SAT Press key, move the flashing to hour position and select PM by or Weekly cycle mode (Ex) Output1(OUT1) is ON for 10min and OFF for 5min from monday 6:00AM to saturday 5:30PM. SAT SUN MON TUE 6:00 AM Start Cycle mode WED THU (B) Fiber optic sensor FRI 5:30 PM (C) Door/Area sensor ON for 10min. OFF for 5min. Advance to program1(P1) weekly program setting mode SUN MON TUE WED THU FRI SAT Set 8:00 by or key and press SET key. In RUN mode, press MODE key for 3 sec. and PROG P1 flashes. Press SET key. (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller Mode type setting SUN MON TUE WED THU FRI SAT Press or key when ON/OFF flashes, CYCLE flashes and press SET key. (I) SSR/ Power controller (J) Counter Pulse width setting SUN MON TUE WED THU FRI SAT Press or key to select pulse duration as 10s and press SET key. to Refer to to of "Weekly ON/OFF mode" to set ON day, ON time, OFF day and OFF time. ON time width setting SUN MON TUE WED THU FRI SAT Complete to set SUN MON TUE WED THU FRI SAT (D) Proximity sensor (E) Pressure sensor ON time setting(Hour, Min.) SUN MON TUE WED THU FRI SAT (A) Photo electric sensor Press SET key to set additional program. (N) Display unit (O) Sensor controller (P) Switching mode power supply Press key to move the flashing to minute position and set as 5min. by or key and press SET key. (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel Complete to set SUN MON TUE WED THU FRI SAT (L) Panel meter (M) Tacho/ Speed/ Pulse meter Press key to move the flashing to minute position and set as 10min. by or key and press SET key OFF time width setting SUN MON TUE WED THU FRI SAT (K) Timer (S) Field network device Press SET key to set additional program. (T) Software (U) Other K-83 LE7M-2 Weekly day change It operates when the specified day mode is required to install in other day from the set day and it returns to previous program setting automatically when it is finished. It is applied to program1(P1) and program2(P2). Weekly day change cancellation Change current year, month, date in current time setting mode Change standard day Delete all program in program1(P1) and program2 (P2) Season switching Setting example Output1(OUT1) is ON in Saturday at 9:00AM and OFF at 12:00PM and it is ON 8:30AM and OFF at 6:00PM from Monday to Friday and the mode of Monday and Tuesday is operated temporarily as Saturday(standard) program. Yearly holiday mode It operates to off the output without program adjustment during previously set yearly holiday period available from present year to 31, Dec. of the next year. Designate the start date of yearly holiday and year of end date as every year [--] to repeat the holiday mode for specified in every year. Setting example Set every year 5, May to off the output(OUT1, OUT2). Advance to yearly holiday mode SUN MON TUE WED THU FRI SAT Advance to weekly day change mode SUN MON TUE WED THU FRI SAT Press MODE key over 3sec. to move to the setting group1 in RUN mode and press it repeatedly until cDY is flashed in second display part and press SET key. Press MODE key over 3sec. to move to the setting group1 in RUN mode and press it repeatedly until hDY flashes in second display part and press SET key. Yearly holiday No. display SUN MON TUE WED THU FRI SAT Press SET key after check yearly holiday No. Standard day selection SUN MON TUE WED THU FRI SAT Press key to move the indicator to saturday and press SET key. after select saturday as standard day (Sat turns ON) by or key. Start date of yearly holiday setting SUN MON TUE WED THU FRI SAT Change day selection SUN MON TUE WED THU FRI SAT Press key to move the indicator to monday and select monday to change (Mon turns ON) by or key and repeat the procedure to select tuesday to change (Tue turns ON) and press SET key to complete. Press key until month position flashes and set May by or key and press key until date position flashes. Press SET key after set 5th by key. End date of yearly holiday setting SUN MON TUE WED THU FRI SAT The flashing is moved to month position directly and press or key to set May and press key until date position flashes. Press SET key after set 5th by or key. Complete to yearly holiday SUN MON TUE WED THU FRI SAT K-84 Press MODE key to finish the additional yearly holiday setting and press SET key to set . It is able to set yearly holiday up to 12 times. Weekly/Yearly Timer Yearly program setting Yearly ON/OFF mode (Ex) Output1(OUT1) is ON from every 5, Apr to 7, Apr at 9:00AM and OFF 5:10PM. OFF time setting(Hour, Minute) SUN MON TUE WED THU FRI SAT Advance to program1(P1) yearly program setting mode SUN MON TUE WED THU FRI SAT Press MODE key for 3sec. in RUN mode, PROG P1 is flashed and press MODE key 3 times more until PROG P2 YEAR flashes and press SET key. (A) Photo electric sensor Move the flashing to minute position after set 5:00 by or key and set the minute as 10 and press SET key. (B) Fiber optic sensor (C) Door/Area sensor Complete to set SUN MON TUE WED THU FRI SAT (D) Proximity sensor Press SET key to set additional program. (E) Pressure sensor Mode type setting SUN MON TUE WED THU FRI SAT Press SET key when ON/ OFF flashes. (F) Rotary encoder Yearly pulse mode (Ex)Output2(OUT2) is ON from 2, Oct, 2008 to 4, Oct, 2008 at 10:00AM and OFF after 5sec. (Present is 2007.) 2, Oct Start date setting SUN MON TUE WED THU FRI SAT Press key until month position flashes and set April by or key and press key until date position flashes. Press SET key after set 5th by or key. 8:00 AM 3, Oct 8:00 AM The flashing is moved to month position directly and press or key to set April and press or key until date position flashes. Press key after set 7th by SET key. SUN MON TUE WED THU FRI SAT key is pressed, move the flashing to hour position and select PM by or key when ON time is afternoon. SUN MON TUE WED THU FRI SAT Press or key to set 9 and press SET key after check 00min. SUN MON TUE WED THU FRI SAT SUN MON TUE WED THU FRI SAT Select PM by or key and move the flashing to hour position by key. (I) SSR/ Power controller (J) Counter MODE key is pressed for 3sec.in RUN mode, PROG P1 is flashed and press MODE key again, PROG P2 YEAR is flashed and press SET key. (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter or key is pressed when ON/OFF flashes to set pulse mode and press SET key. (N) Display unit (O) Sensor controller (P) Switching mode power supply Press or key twice to set 08(year 2008) and move to month position by key. Set Oct. by or key and move to date position by key and press SET key after set 2nd by or key. (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device End date setting SUN MON TUE WED THU FRI SAT OFF time setting(AM, PM) 10:00AM Start date setting ON time setting(Hour, Minute) SUN MON TUE WED THU FRI SAT 8:00 AM Mode type setting ON time setting(AM, PM) SUN MON TUE WED THU FRI SAT (H) Temp. controller ON for 5sec. Advance to program2(P2) yearly program setting mode End date setting SUN MON TUE WED THU FRI SAT 4, Oct (G) Connector/ Socket The flashing is moved to month position directly by key and set 4th by or key after move it to date position by key, then press SET key. (T) Software (U) Other K-85 LE7M-2 ON time setting(AM, PM) SUN MON TUE WED THU FRI SAT key is pressed, move the flashing to hour position and select PM by or key when ON time is afternoon. ON time setting(Hour, Minute) SUN MON TUE WED THU FRI SAT Press or key twice to set 10 and press SET key after check 00min. Yearly program check, modify and delete RUN mode Press MODE key for 3sec. Press CHECK key for 1sec. Press SET Program1 Yearly program key for 3sec. Program1 Yearly program record No.1 [r01] record No.1 [r01] setting setting check modify and delete CHECK Press SET Program1 Yearly program key for 3sec. Program1 Yearly program record No.2 [r02] setting record No.2 [r02] modify and delete setting check CHECK Pulse width setting SUN MON TUE WED THU FRI SAT Press or key 4 times to select pulse width as 5s and press SET key. Press SET Program2 Yearly program key for 3sec. Program2 Yearly program record No.1 [r01] record No.1 [r01] setting setting check modify and delete CHECK Complete to set SUN MON TUE WED THU FRI SAT Press SET key to set additional program. It is able to set year of start/end date in yearly program setting up to 2 years later from the present year. Program check, modify and delete Weekly program check, modify and delete RUN mode Press MODE key for 3sec. Press CHECK key for 1sec. Press SET Program1 weekly program key for 3sec. Program1 weekly program record No.1 [r01] setting record No.1 [r01] modify and delete setting check CHECK Press SET Program1 weekly program key for 3sec. Program1 weekly program record No.2 [r02] setting record No.2 [r02] modify and delete setting check CHECK Press SET Program2 weekly program key for 3sec. Program2 weekly program record No.1 [r01] setting record No.1 [r01] modify and delete setting check CHECK K-86 YEAR turns ON when check, modify or delete yearly program. If any key is untouched for 60sec, it is returned to RUN mode in weekly or yearly program check. In weekly or yearly program check, it controls output according to program setting and output is OFF in modify or delete mode. When MODE key is pressed in weekly or yearly programrecord modify, delete stand by or delete mode, current work is cancelled and it is returned to check mode. Weekly or yearly program record modify and delete (1) Program record modify When press SET key over 3sec. in program check, EDT flashes in second display part, press SET key. It returns to check mode when finish the modify same as the above procedure. (2) Program record delete When press SET key over 3sec. in program check, EDT flashes in second display part, press or key until CLR flashes in second display part and press SET key. Press CLR key over 3sec. when SET turns ON in second display part, it returns to program check.