22.32.0.xxx.1xx0 22.32.0.xxx.4xx0
1
2 NO, 3 mm * (or 1 NO + 1 NC or 2 NC)
25 / 80 25 / 120
250 / 440 250 / 440
6,250 6,250
10 10
1,800 1,800
1 1
15 15
10
800 2,000
300 800
200 500
100 200
100 200
100 200
300 800
25/5/1 25/5/1
1,000 (10/10) 1,000 (10/10)
AgNi AgSnO2
12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
2 /2.2 2 / 2.2
(0.8…1.1) UN (0.8…1.1) UN
0.4 UN 0.4 UN
0.1 UN 0.1 UN
2 · 106 2 · 106
70 · 103 30 · 103
30 / 20 30 / 20
6 6
–20…+50 –20…+50
IP20 IP20
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage V AC
Rated load AC1 / AC-7a (per pole @ 250 V) VA
Rated current AC3 / AC-7b A
Rated load AC15 (per pole @ 230 V) VA
Single-phase motor rating (230 V AC) kW
Rated load AC5a (per pole @ 250 V) A
Rated current AC-7c A
Nominal lamp rating:
230V incandescent/halogen W
fluorescent tubes with electronic ballast W
fluorescent tubes with electromechanical ballast
W
CFL W
230V LED W
LV halogen or LED with electronic ballast W
LV halogen or LED with electromechanical ballast W
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Contact material
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz)
Rated power AC/DC VA (50 Hz)/W
Operating range DC/AC (50/60 Hz)
Holding voltage DC/AC (50/60 Hz)
Must drop-out voltage DC/AC (50/60 Hz)
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC-7a cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Ambient temperature range °C
Protection category
Approvals (according to type)
AgNi contacts, specifically
intended for resistive and
slightly inductive loads as
well as for motor loads
AgSnO2contacts, specifically
intended for lamp loads and
for high inrush current loads
Features
25 A modular contactor - 2 pole
17.5 mm wide
NO contact gap ≥ 3 mm, double break
Continuous duty for the coil and contacts
AC/DC silent coil (with varistor protection)
Protective separation (reinforced insulation)
between coil and contacts
Mechanical and LED indicators as standard
Auto-On-Off selector version available
AgNi and AgSnO2contact versions available
Compliant with EN 61095: 2009
Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions)
35 mm rail (EN 60715) mount
22.32...1xx0 / 22.32...4xx0
Screw terminal
For outline drawings see page 8
* Contact gap ≥ 3 mm for
NO contacts only;
NC contacts ≥ 1.5 mm
2 NO 1 NO + 1 NC 2 NC
(x3x0) (x5x0) (x4x0)
IV-2015, www.findernet.com
22 Series - Modular contactors 25 - 40 - 63 A 22
SERIES
L
2
22.34.0.xxx.1xx0 22.34.0.xxx.4xx0
4 NO, 3 mm * (or 3NO + 1NC or 2NO + 2NC)
25 / 80 25 / 120
250 / 440 250 / 440
6,250 6,250
10 10
1,800 1,800
4 4
15 15
10
800 2,000
300 800
200 500
100 200
100 200
100 200
300 800
25/5/1 25/5/1
1,000 (10/10) 1,000 (10/10)
AgNi AgSnO2
12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
2 / 2.2 2 / 2.2
(0.8…1.1) UN (0.8…1.1) UN
0.4 UN 0.4 UN
0.1 UN 0.1 UN
2 · 106 2 · 106
150 · 103 30 · 103
18 / 40 18 / 40
6 6
–20…+50 –20…+50
IP20 IP20
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage V AC
Rated load AC1 / AC-7a (per pole @ 250 V) VA
Rated current AC3 / AC-7b A
Rated load AC15 (per pole @ 230 V) VA
Three-phase motor rating (400 - 440 V AC) kW
Rated load AC5a (per pole @ 250 V) A
Rated current AC-7c A
Nominal lamp rating:
230V incandescent/halogen W
fluorescent tubes with electronic ballast W
fluorescent tubes with electromechanical ballast
W
CFL W
230V LED W
LV halogen or LED with electronic ballast W
LV halogen or LED with electromechanical ballast W
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Contact material
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz)
Rated power AC/DC VA (50 Hz)/W
Operating range DC/AC (50/60 Hz)
Holding voltage DC/AC (50/60 Hz)
Must drop-out voltage DC/AC (50/60 Hz)
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC-7a cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Ambient temperature range °C
Protection category
Approvals (according to type)
AgNi contacts, specifically
intended for resistive and
slightly inductive loads as well
as for motor loads
AgSnO2contacts, specifically
intended for lamp loads and
for high inrush current loads
Features
25 A modular contactor - 4 pole
35 mm wide
NO contact gap ≥ 3 mm, double break
Continuous duty for the coil and contacts
AC/DC silent coil (with varistor protection)
Protective separation (reinforced insulation)
between coil and contacts
Mechanical and LED indicators as standard
Auto-On-Off selector version available
AgNi and AgSnO2contact versions available
Compliant with EN 61095: 2009
Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions)
35 mm rail (EN 60715) mount
22.34...1xx0 / 22.34...4xx0
Screw terminal
For outline drawings see page 8
4 NO 3 NO + 1 NC 2 NO + 2 NC
(x3x0) (x7x0) (x6x0)
IV-2015, www.findernet.com
22
SERIE S 22 Series - Modular contactors 25 - 40 - 63 A
L
* Contact gap ≥ 3 mm for
NO contacts only;
NC contacts ≥ 1.5 mm
4 NO 3 NO + 1 NC 2 NO + 2 NC
(4310) (4710) (4610)
3
IV-2015, www.findernet.com
22.44.0.xxx.4xx0 22.64.0.xxx.4xx0
For high inrush current loads
176 A
Contact material AgSnO2
Specifically intended:
for high inrush current loads
240 A
Contact material AgSnO2
40 - 63 A modular contactor - 4 pole
NO and NC contact gap ≥ 3 mm, double break
Continuous duty for the coil and contacts
AC/DC silent coil (with varistor protection)
Protective separation (reinforced insulation)
between coil and contacts
Mechanical indicator as standard
AgSnO2contacts
Compliant with EN 61095: 2009 and with
EN 60947-4-1: 2009
35 mm rail (EN 60715) mount
22.44.../22.64...
Screw terminal
For outline drawings see page 8
Features
4 NO, (or 3NO + 1NC or 2NO + 2NC) ≥ 3 mm
40 / 176 63 / 240
400 / 440 400 / 440
16,000 24,000
22 30
11 15
20 32
4,000 5,000
1,500 2,000
1,500 2,000
1,000 1,500
1,000 1,500
1,000 1,500
1,500 2,000
40/4/1.2 63/4/1.2
1,000 (17/50) 1,000 (17/50)
AgSnO2 AgSnO2
12 - 24 - 110...120 (110 V DC) - 230...240 (220 V DC)
5 5
(0.85…1.1) UN (0.85…1.1) UN
0.85 UN 0.85 UN
0.2 UN 0.2 UN
3 · 106 3 · 106
100 · 103 100 · 103
20 / 45 20 / 45
6 6
–5…+55 –5…+55
IP20 IP20
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage V AC
Rated load AC1 / AC-7a (per pole @ 400 V) VA
Rated current AC3 / AC-7b (400 V) A
Rated load AC15 (per pole @ 230 V) VA
Three-phase motor rating (400 - 440 V AC) kW
Rated load AC5a (per pole @ 250 V) A
Rated current AC-7c A
Nominal lamp rating:
230V incandescent/halogen W
fluorescent tubes with electronic ballast W
fluorescent tubes with electromechanical ballast
W
CFL W
230V LED W
LV halogen or LED with electronic ballast W
LV halogen or LED with electromechanical ballast W
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Contact material
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz)
Rated power AC/DC VA (50 Hz)/W
Operating range DC/AC (50/60 Hz)
Holding voltage DC/AC (50/60 Hz)
Must drop-out voltage DC/AC (50/60 Hz)
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC-7a cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Ambient temperature range °C
Protection category
Approvals (according to type)
22 Series - Modular contactors 25 - 40 - 63 A 22
SERIES
L
Ordering information
Exemple: 22 series, modular contactor 25 A, 4 NO contacts, coil 230 V AC/DC, AgSnO2contacts, Auto-On-Off selector + mechanical indicator + LED.
D: Special versions
0 = Standard
C: Options
1 = Mechanical indicator
2 = Mechanical indicator + LED
4 = Auto-On-Off selector +
mechanical indicator + LED
B: Contact circuit
3 = All NO contacts
4 = All NC contacts (22.32 only)
5 = 1 NO + 1 NC
6 = 2 NO + 2 NC
7 = 3 NO + 1 NC
A: Contact material
1 = AgNi
4 = AgSnO2
Series
Type
3 = 25 A modular contactor range
4 = 40 A modular contactor range
6 = 63 A modular contactor range
Number of contacts
2 = 2 pole
4 = 4 pole
Coil version
0 = AC (50/60 Hz)/DC
Coil rated voltage
See coil specifications
3 4 3 0 4 0
... .
2 3 0 2 2 4
Options
Auto-On-Off selector + mechanical indicator + LED (xx40 option)
Selector
The three-position manual selector has the following functions:
ON position - the contacts are latched in the operated state
(NO contacts - closed and NC contacts - open), the mechanical
indicator is visible in its window, the LED is not illuminated.
AUTO position - the state of contacts, mechanical indicator
and LED follow the coil supply voltage.
OFF position - even if terminals A1 - A2 are supplied with
rated voltage, the coil is not energized, and so the contacts
remain in the non-operated state, the mechanical indicator is
not visible and the LED is not illuminated.
LED
Mechanical indicator
1
2
3
Type Coil version A B C D
22.32 AC/DC 1 - 4 3- 4 - 5 2 - 4 0
22.34 AC/DC 1 - 4 3- 6 - 7 2 - 4 0
22.44 AC/DC 4 3 - 6 - 7 1 0
22.64 AC/DC 4 3 - 6 - 7 1 0
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
1
2
3
A B C D
4
IV-2015, www.findernet.com
Type 22.32 / 22.34 Options
Type 22.44 / 22.64 Options
Mechanical indicator
1
1
22
SERIE S 22 Series - Modular contactors 25 - 40 - 63 A
L
Technical data
Insulation 22.32 / 22.34 22.44 / 22.64
Rated insulation voltage V AC 250 440 440
Pollution degree 3 * 2 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 4
Dielectric strength V AC 4,000 2,000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 4
Dielectric strength V AC 2,500 2,000
Insulation between open contacts NO contact NC contact NO/NC contacts
Contact gap mm 3 1.5 3
Overvoltage category III II III
Rated impulse voltage kV (1.2/50 µs) 4 2.5 4
Dielectric strength V AC/kV (1.2/50 µs) 2,500/4 2,000/3 2,000/3
* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.
Conducted disturbance immunity Reference standard
Fast transients (burst 5/50 ns, 5 kHz) at coil terminals EN 61000-4-4 Level 4 (4 kV) Level 2 (2 kV)
Voltage pulses (surge 1.2/50 s) at supply terminals (differential mode) EN 61000-4-5 Level 4 (4 kV) Level 2 (2 kV)
Short circuit protection 22.32 / 22.34 22.44 22.64
Rated conditional short circuit current kA 3 3 3
Back-up fuse A 32 (gL/gG type) 63 80
Terminals Solid and stranded cable
22.32 / 22.34 22.44 / 22.64
Max. wire size – contact terminals mm2 1 x 6 / 2 x 4 1x25 (solid) - 1x16 (stranded)
AWG 1 x 10 / 2 x 12 1x4 (solid) - 1x6 (stranded)
Max. wire size – coil terminals mm2 1 x 4 / 2 x 2.5 1x2.5
AWG 1 x 12 / 2 x 14 1x14
Min. wire size – contact and coil terminals mm2 1 x 0.2 1x1 (coil) - 1x1.5 (contacts)
AWG 1 x 24 1x18 (coil) - 1x16 (contacts)
Screw torque Nm 0.8 1.2 (coil terminals) - 3.5 (contact terminals)
Wire strip length mm 9 10
Other data 22.32 22.34 22.44 22.64
Vibration resistance (10...150)Hz g 4 4 3 3
Shock resistance g 10 10 15 15
Power lost to the environment without contact current W 2 2 5 5
with rated current W 4.8 6.3 17 37
NOTE
22.32/22.34: It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient
temperature > 40 °C, coil operated for a prolonged period of time, all contacts loaded with current > 20 A).
22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is + 40 °C; when more than 3 contactors are installed, it is necessary
an air gap of 9 mm.
With 2 adjacent contactors the maximum ambient temperature is + 55 °C; when more than 2 contactors are installed, it is necessary
an air gap of 9 mm.
5
IV-2015, www.findernet.com
22 Series - Modular contactors 25 - 40 - 63 A 22
SERIES
L
L
6
Contact specification
H 22 - Maximum DC1 breaking capacity - Type 22.32 / 22.34
R 22 - Coil operating range v ambient temperature
Coil specifications
Nominal Coil Operating range Rated coil
voltage code
consumption
UN Umin Umax
INat UN (AC)
V V V mA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120 0.120 88 138 16.5
(110...125)
230 184 (AC) 264 (AC)
(230...240 AC)
0.230
176 (DC) 242 (DC)
8.7
(220 DC)
AC/DC version data (type 22.34)
Nominal Coil Operating range Rated coil
voltage code
consumption
UN Umin Umax
INat UN (AC)
V V V mA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120 0.120 88 138 16.5
(110...125)
230 184 (AC) 264 (AC)
(230...240 AC)
0.230
176 (DC) 242 (DC)
8.7
(220 DC)
AC/DC version data (type 22.32)
1- Max. permitted coil voltage.
2- Min. pick-up voltage with coil at ambient temperature.
When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of 100·103can be expected.
In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC breaking current (A)
DC voltage (V)
Ratings and utilization categories according to EN 61095: 2009
Type Utilization category
AC-7a AC-7b AC-7c
Rated current Rated electrical Rated current Rated electrical Rated current Rated electrical
(A) life (Cycles) (A) life (Cycles) (A) life (Cycles)
22.32….1xx0 (AgNi contacts) 25 70·103(NO) 10 30·103——
30·103(NC)
22.32….4xx0 (AgSnO2contacts) 25 30·10310 30·10310 30·103
22.34….1xx0 (AgNi contacts) 25 150·103(NO) 10 30·103——
100·103(NC)
22.34….4xx0 (AgSnO2contacts) 25 30·10310 30·10310 30·103
22.44….4xx0 40 100·10322 150·103——
22.64….4xx0 63 100·10330 150·103——
IV-2015, www.findernet.com
H 22 - Maximum DC1 breaking capacity - Type 22.44 / 22.64
DC breaking current (A)
DC voltage (V)
Nominal Coil Operating range Rated coil
voltage code
consumption
UN Umin Umax
INat UN (AC)
V V V mA
12 0.012 10.2 13.2 417
24 0.024 20.4 26.4 208
120 0.120 102 138 41
(110...125)
230 264 (AC)
(230...240 AC)
0.230 196
242 (DC)
21
(220 DC)
AC/DC version data (type 22.44 / 22.64)
Utilization category: AC-7a = Slightly inductive loads (cosϕ=0.8)
AC-7b = Motor loads; (cosϕ=0.45, Imaking= 6xIbreaking)
AC-7c = Compensated electric discharge lamps (cosϕ=0.9, C= 10 mF/A)
type 22.64
type 22.44
22
SERIE S 22 Series - Modular contactors 25 - 40 - 63 A
7
IV-2015, www.findernet.com
Wiring diagrams
Type 22.32 Type 22.34
Line and neutral switched
Type 22.34
Line only switched
Type 22.44 / 22.64 Type 22.44 / 22.64
Line and neutral switched Line only switched
22 Series - Modular contactors 25 - 40 - 63 A 22
SERIES
L
8
Outline drawings
Type 22.32
Screw terminal
Type 22.34
Screw terminal
Type 22.44 / 22.64
Screw terminal
Type 22.32 + 022.33 / 022.35
Screw terminal
Type 22.34 + 022.33 / 022.35
Screw terminal
IV-2015, www.findernet.com
Type 022.33 / 022.35
Screw terminal
Type 022.63 / 022.65
Screw terminal
Type 22.44 / 22.64 + 022.63 / 022.65
Screw terminal
22
SERIE S 22 Series - Modular contactors 25 - 40 - 63 A
L
9
IV-2015, www.findernet.com
Auxiliary modules
Mechanically linked contacts
according to Annex L of EN 60947-5-1
Contact specification
Contact configuration 2 NO 1 NO + 1 NC 2 NO 1 NO + 1 NC
Conventional free air thermal current Ith A 6 6
Rated power AC15 (230 V) VA 700 700
Electrical life at rated load cycles 30 x 103 30 x 103
Minimum switching load mW (V/mA) 1,000 (10/10) 1,000 (10/10)
Contact material AgNi AgNi
Short circuit protection
Rated conditional short circuit current kA 1 1
Back-up fuse A 6 (gL/gG type) 6 (gL/gG type)
Terminals Solid and stranded cable Solid and stranded cable
Max. wire size mm2 1 x 4 / 2 x 2.5 1 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14
Min. wire size mm2 1 x 0.2 1 x 1
AWG 1 x 24 1 x 18
Screw torque Nm 0.8 0.6
Wire strip length mm 9 9
Power lost to the environment
without contact current W
with rated current W 0.5 0.5
Approvals (according to type)
Type of contactor Type 22.32 Type 22.44
Type 22.34 Type 22.64
22.32 + 022.33/022.35
22.34 + 022.33/022.35
22.44 + 022.63/022.65
22.64 + 022.63/022.65
022.33 022.35 022.63 022.65
NOTE: it is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0 (2 NC versions).
22 Series - Modular contactors 25 - 40 - 63 A 22
SERIES
L
10
Accessories
Adaptor for panel mounting (for 22.34 type), plastic, 35 mm wide 011.01
011.01
Adaptor for panel mounting (for 22.32 type), plastic, 17.5 mm wide 020.01
020.01
Sheet of marker tags, plastic, 72 tags, 6x12 mm 060.72
060.72
Separator for rail mounting, plastic, 9 mm wide 022.09
022.09
Identification tag, plastic, 1 tag, 17x25.5 mm 019.01
019.01
022.18
8-way jumper link for type 22.32, 17.5 mm wide 022.18 (blue)
Rated values 10 A - 250 V
022.26
6-way jumper link for type 22.34, 35 mm wide 022.26 (blue)
Rated values 10 A - 250 V
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT
IV-2015, www.findernet.com
22
SERIE S 22 Series - Modular contactors 25 - 40 - 63 A
L