Product Data Sheet
Insulator Strip Required for Voltage Rating
Copper Wire Only
Wire Range with Wire Binding Screw: #10 - #16 AWG
Wire Range with Listed Ring or Fork Lug: #6 – 16 AWG
11/16” Centers
Application torque: 20 in. lbs
Electrical Ratings:
• 50A (Based on NEC standards of 75°C ampacity)
• Wires larger than #10 AWG require listed ring or fork lug
• 600 Volts AC/DC (UL 1059 Class B and C, User Group – Commercial Appliance and
General Industrial)
• Short Circuit Current Rating: 10,000A (Default)
• Approved for Factory and Field Wiring.
Mechanical Ratings:
• Storage and transportation temperature range: -35°C to 110°C (-31°F to 230°F)*
• Maximum insulator base temperature: 130°C (266°F)* UL RTI
• Flammability rating of insulator base: UL 94V-0
* Use outside these ratings needs to be judged in the end-use application.
Materials:
• Connector: Brass, tin plated.
• Insulator base: JJ (GDI-30F). Glass-fiber filled, diallyl ortho-phthalate.
• Screw, #10-32 Machine Screw: Stainless steel
• Rivet: Brass, tin plated.
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E47811
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant, IEC 60947-7-1
603 JJ XX Cres
Replace “XX” with 01 through 12 for number of poles
Terminal Block– Open Back
50 Amps, 600 Volts
(AC/DC)