pro M compact ®Miniature circuit-breakers S 200/S 200 M
Residual-current-operated
circuit-breakers F 200
Cross wiring/accessories
System pro M compact
Technical data
Navigate Document
2
System
pro M compact ®
Standard Terms for Delivery and Sale
For domestic business, the Standard Terms for Delivery of Products and Services of the
Electrical Industry (ABB Form 2292) shall apply in connection with the Standard Sales Terms
(ABB Form 2327) in their then applicable version. For foreign business, the Standard Terms
for Delivery of Products and Services of the Electrical Industry (ABB Form 2293 German-
English, or ABB Form 2294 German- French) shall apply in connection with the Standard
Sales Terms (ABB-Form 2381 English) in their then applicable version.
Warranty
We assume warranty in accordance with the standard sales and delivery terms.
Complaints shall be made in writing within eight days following receipt of the goods.
Technical information and illustrations are not binding and subject to change without
notice.
Miniature circuit-breaker
S 201
3
System
pro M compact ®
Contents page
The technology of S 200
Notes for use, special features ............................................................................ 4
The offer at a glance............................................................................................. 6
Overview of technical data ................................................................................... 7
Internal resistance and power loss ...................................................................... 8
Max. permissible impedances of fault loops ....................................................... 8
Tripping charakteristics ........................................................................................ 9
Short circuit capacity ........................................................................................... 9
Short circuit selectivity ....................................................................................... 10
Tripping diagrams ................................................................................................ 11
Let-through value diagrams ................................................................................. 13
Current-carrying capacity, thermal influence ...................................................... 14
Applications S 200 ............................................................................................... 15
Installation and operation instructions S 200 ...................................................... 16
Supplementary devices ........................................................................................ 17
Dimensions ........................................................................................................... 25
Dimension drawings accessories ........................................................................ 26
The technology of F 200
Supplementary devices ........................................................................................ 17
Description, Application examples ...................................................................... 20
Technical data ...................................................................................................... 21
Installation and operation instructions F 200 ...................................................... 22
Use in different types of circuit ............................................................................ 23
Dimension drawings ............................................................................................. 26
Dimension drawings accessories ........................................................................ 27
The technology of busbars
Description ........................................................................................................... 24
Technical data ...................................................................................................... 24
Dimensions ........................................................................................................... 27
The program
Selection table S 200-B ....................................................................................... 29
Selection table S 200-C ....................................................................................... 31
Selection table S 200-D ....................................................................................... 33
Selection table S 200-K ....................................................................................... 35
Selection table S 200-Z ....................................................................................... 37
Selection table S 200-K H .................................................................................... 39
Selection table S 200 M-B ................................................................................... 41
Selection table S 200 M-C ................................................................................... 43
Supplementary devices .......................................................................................... 44
Selection table F 200 ........................................................................................... 45
Selection table busbars, rail connectors ............................................................. 47
Selection table accessories ................................................................................. 49
Miniature circuit-breakers
Residual-current-operated circuit breaker
Busbars
Prior to connection of
aluminium conductors
( 4 mm2)
ensure that their
contact points are
cleaned, brushed and
coated with grease.
4
System
pro M compact ®
Outstanding features
Applications
SK 0049 B 99
All round protection against contact with live parts in acordance with
DIN VDE 106 part 100.
Due to new design: Upper and lower shoulders reduced.
More working space between component rows.
Outgoing and incoming connection points easily accessible.
New, failsafe, bi-directional cylinder lift terminal, ensuring a faster, totally
error-free connection.
As you tighten the screw, the terminal draws together to simultaneously
close the front and rear wiring inputs.
This creates a strong, contactassured connection between the wires and
the device, in a single operation.
Busbar is installed at the back terminals (A). Connection of conductors
on the front terminals (B).
Result: a clear view on all connection points.
Never fumble for the right connection point again.
Substantially improved cross-wiring safety.
Tangible time-savings.
Connection possible for single, multi and finely stranded conductors
of 0.75 to 25 mm2.
It is also possible to connect conductors with different cross section at
the same time.
New cross wiring busbars.
Standard length sizes or meter length cutable.
SK 0048 B 99
B
A
SK 0053 B 99
SK 0051 B 99
SK 0052 B 99
5
System
pro M compact ®
Outstanding features
Applications
New quick-fastening technique for easy disconnection of the device
from the assembly.
No time-consuming extra work:
Cross-wiring remains with the assembly.
To remove the device, just loosen the screw, lift the device and pull it
out.
If neccessary, all devices of the series connected to the new
pro M compact cross-wiring rails may be exchanged easily and quickly,
e.g. to implement the adaptation to the VDE standard
0100 part 410.
Easy to add on MCB for extensions.
New, integrated auxiliary contact, factory fitted, reduces space by 50 %.
Cross wiring to customary compact busbar possible.
Self-adhesive identification labels are provided for all devices, ensuring
clear and accurate identification.
Every detail of System pro M compact has now been optimised to meet the
user’s requirements.
Fuirthermore, System pro M compact offers you many different ways to
label the switchgear cabinet and built-in consumer unit in a professional
manner.
Individual, effecient labeling of devices.
Pad lock prevents unauthorized switching to ON or OFF.
Complete range of tripping characteristics in B, C, D, K, Z.
High rated switching capacity of 6 000 A (S 200) or 10 000 A (S 200 M).
Current limitation is below the values prescribed by the VDE, therefore
higher selectivity rating than energy limitation class 3.
Disconnector abilities according to DIN VDE 0660 part 107, surge with-
stand capability 6 kV (1.2/50).
SK 0047 B 99SK 0045 B 99
SK 0050 B 99
SK 010 B 01
6
System
pro M compact ®
Miniature circuit-breakers
The offer at a glance
Description
The MCBs of the S 200/S 200 M series have a cur-
rent-limiting effect. They have two different trip releases
acting on the contact mechanism
1. the delayed thermal release providing overload
protection
2. the electromagnetic instantaneous release with
“hammer trip” solenoid providing fault current
protection.
They offer: high short-circuit capacity
high selectivity for back-up fuse
In case of short-circuit, low stress
on the cable in the point of fault due
to the high limitation of the let-through
ƒi2dt (current heating value).
Task
To protect against excessive temperature rises of
electric items in the case of overcurrents caused by
overload, short circuit of earth-fault current if assi-
gned according to DIN VDE 0100 Part 430. Protec-
tion against electric shock in the case of excessive
touch voltage caused by insulation fault if assigned
according to DIN VDE 0100 Part 410.
Trip charcteristics
SK 0126 Z 00
B
SK 0128 Z 00
C
SK 0130 Z 98
IK · 2 = peak value of prospective short circuit current
iD= max. let-through current of device S 200/S 200 M
Un= system voltage
UB= arc voltage of MCB
tK= breaking time of MCB
Oscillogram of rupturing process
Trip charcteristics and rated current
Independent of the type of characteristic, national codes of practice provide what highest rated current
and/or performance characteristic can be assigned to the conductor cross section to be protected (e.g.
DIN VDE 0100 Part 430).
The following assignment rules apply: Ib In Iz; I2 1,45 · Iz
Ib= operating current of the circuit to be expected
In= rated current of the MCB of characteristics type B, C, D, K and Z
Iz= permissible current loading of lines
I2= conventional tripping current
B-, C- and D-type trip characteristics for line protection
Tripping behaviour according to DIN VDE 0641 Part 11.
Rated current 6 ... 63 A, (C 0,5 ... 63 A). The introduction of these trip characteristics enables direct
assignments of MCBs to the permissible load of lines I z according to DIN VDE 0298 Part 4/11.98, as the
second condition is already fulfilled (I2 = 1.45 · In).
K-type trip characteristics
Tripping behaviour according to DIN VDE 0660 Part 101 and IEC 947-2, rated current 0.5 ... 63 A,
for circuits where current-consuming appartus cause functional current peaks and for the overcurrent
protection of lines.
Z-type trip characteristics
Tripping behaviour according to DIN VDE 0660 Part 101 and IEC 947-2
Rated current 0.5 ... 63 A in 17 grades. For the protection of semiconductors and measuring circuits with
transformers.
SK 0142 Z 00
K
Z
SK 0146 Z 00
7
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
Technical data
Specifications: DIN VDE 0641 Part 11, IEC 60898, EN 60898, IEC 60947-2, UL 1077
No. of poles: 1, 2, 3, 4, 1 + NA, 3 + NA
tripping charcteristics: B, C, D, K, Z
rated current In: B 6 ... 63 A , C, D, K and Z 0,5 ... 63 A
rated voltage Un: 1-pole 230 V
multipole 400 V
max. operating voltage UBmax:ACU
n + 10 %
DC 1-pole 60 V ...
2-pole 125 V ...
min. operating voltage UBmin : 12 V~, 12 V-
energy limitation class: S 3
short circuit rupturing capacity: see page 9
frequency: 50 ...60 Hz
insulation coordination: according to DIN VDE 0110 Part 1 and 2
- overvoltage category: III
- pollution degree: 2
- surge voltage: 5 kV (1.2/50 µs)
- impulse alternating voltage: 3 kV (50/60 Hz)
housing: Insulating material rating I (CTI 600) according to DIN IEC 112/VDE 0303 Part 1, RAL
7035
operating lever: Insulating material rating II (400 CTI 600) black, sealable
degree of protection acc. to DIN VDE 0100: IP 20, in the consumer unit IP 40
dimensions: according to DIN 43880, size code 1
depth of device: 68 mm
overall dimensions: see page 25
mounting position: optional
fixing: snap-on to DIN rails EN 60 715, 35 mm or
screw fixing by means of mounting plate (see accessories)
connection: failsave bi-directional cylinder-lift terminal at top and bottom, shock-protected according
to
DIN VDE 0106 Part 100. Suitable for connection of single, multi or finely stranded
conductors up to 25 mm2 (if also connected to rails)
tightening torque: 2.8 Nm
mechanical service life: 20,000 operations
service life at rated load
In 32 A: 20,000 operations
In 32 A: 10,000 operations
climatic resistance acc. to DIN IEC 68 Part 2-30: constant climate 23/83, 40/93, 55/20 [°C/RH]
alternating climate 25/95 - 40/93 [°C/RH]
storage temperature: T max +70 °C/158 °F, Tmin -40 °C/-13 °F
ambient temperature: T max +55 °C/158 °F, Tmin -25 °C/-13 °F
shock resistance: 30 g, at least 2 impacts shock duration 13 ms
resistance to vibration acc. to DIN IEC 68-2-6: 5 g, 20 frequency cycles 5 ... 150 ... 5 Hz at 0.8 In
weight: see selection tables
Technical data of the integrated auxiliary contact
contact: 1NO (1 make contact)
1NC (1 normally closed contact)
contact load: AC 14 230 V 2 A
DC 12 identical DC 13
DC 13 50 V 1 A
min. operating voltage: 12 VAC/DC at 0.1 VA
short-circuit withstand capacity: 230 V 1,000 A
electrical service life: 4,000 operations
safe disconnection of auxiliary circuit and main circuit according to VDE 0106 Part 101
connection capacity: 0.75 to 2.5 mm2 (finely-stranded conductors to be fitted with a connector sleeve)
8
System
pro M compact ®
Maximum permissible fault loop impedance ZS at U0 = 230 V
to ensure compliance with the rupturing conditions prescribed in DIN VDE 0100 Part 410.
The internal resistance of MCB is included.
Note: Attention should be paid to the maximum voltage drop
Miniature circuit-breakers
S 200/S 200 M series
Internal resistance and power loss of the miniature circuit-breakers
Internal resistance per pole in m, power loss per pole in W
type rated device series
current B, C, D
KZ
In AmWmWmW
S 200 and 0.5 5500 1.4 6340 1.6 10100 2.5
1 1440 1.4 1550 1.6 2270 2.3
S 200 M 1.6 630 1.6 695 1.8 1100 2.8
2 460 1.8 460 1.9 619 2.5
3 150 1.3 165 1.5 202 1.8
4 110 1.8 120 2.0 149 2.4
6 55 2.0 52 1.9 104 3.7
8 15 1.0 38 2.5 53.9 3.45
10 13.3 1.3 12.6 1.26 17.5 1.7
13 13.3 2.3 12.6 1. 26
16 7.0 1.8 7.7 2.0 10.9 2.8
20 6.25 2.5 6.7 2.7 6.0 2.4
25 5.0 3.2 4.6 2.9 4.1 2.6
32 3.6 3.7 3.5 3.6 2.8 2.9
40 3.0 4.8 2.8 4.5 2.5 4.1
50 1.3 3.25 1.25 2.9 1.8 4.4
63 1.2 4.8 0.7 5.2 1.3 5.2
Current intensities 0.5 – 4 apply exclusively to C-type trip characteristics.
U0 = rated voltage against earthed conductor; for U0 = 240 V : ZS · 1.04; for U0 = 127 V ZS · 0.55
The max. permissible lenght of cable at different voltage and cross sections on request.
S 200 and S 200 M
Bemessungs- BC D K Z
strom In A max. ZSmax. ZSmax. ZSmax. ZSmax. ZS

0,5 46.0 33.0 38.3 153.3
1 23.0 16.5 19.2 76.7
1.6 14.4 10.3 12.0 47.9
2 11.5 8.2 9.6 38.3
3 7.7 5.5 6.4 25.6
4 5.8 4.1 4.8 19.2
6 7.7 3.8 2.7 3.2 12.8
8 2.8 2.1 2.4 9.5
10 4.6 2.3 1.6 1.9 7.7
13 3.5 1.7 1.2
16 2.9 1.4 1.0 1.2 4.8
20 2.3 1.2 0.8 1.0 3.8
25 1.8 0.9 0.7 0.8 3.1
32 1.4 0.7 0.5 0.6 2.4
40 1.2 0.6 0.4 0.5 1.9
50 0.9 0.5 0.3 0.4 1.5
63 0.7 0.4 0.3 0.3 1.2
9
System
pro M compact ®
Tripping characteristics
thermal release electromagnetic release
acc. to tripping characteristic current: tripping time currents: tripping time
and rated current conventional conventional hold trip
non-triping c. tripping c. current surges at least at
DIN VDE B6 to 63 A 1.13 · In> 1 h 3 · In> 0.1 s
0641/T 11 1.45 · In< 1 h 5 · In< 0.1 s
C0.5 to 63 A 1.13 · In> 1 h 5 · In> 0.1 s
1.45 · In< 1 h 10 · In< 0.1 s
D0.5 to 63 A 1.13 · In> 1 h 10 · In> 0.1 s
1.45 · In< 1 h 20 · In< 0.1 s
DIN VDE 0660/9.82 K0.5 to 63 A 1.05 · In> 1 h
1.2 · In< 1 h not applicable
DIN VDE 0660 1.05 · In> 2 h 8 · In> 0.2 s
8/69 1.2 · In< 2 h 12 · In< 0.2 s
Part 11.5 · In< 2 min.
6.0 · In> 2 s (T1)
DIN VDE 0660/9.82 Z0.5 to 63 A 1.05 · In> 1 h
1.2 · In< 1 h not applicable
DIN VDE 0660 1.05 · In> 2 h 2 · In> 0.2 s
8/69 1.2 · In< 2 h 3 · In< 0.2 s
Part 11.5 · In< 2 min.
6.0 · In> 2 s (T1)
The thermal releases are calibrated to a nominal reference ambient temperature; for Z
and K, the value is 20 °C, for B and C = 30 °C. In the case of higher ambient
temperatures, the current values fall by ca. 6% for each 10 K temperature rise.
as from operating temperature (after I1 > 1 h or, as applicable, 2 h).
The standard DIN VDE 0660/9.69 has expired in 1986, but is still referred to due to its
complete statement of the tripping characteristics.
The indicated tripping values of electromagnetic tripping devices apply to a frequency
range of 16 2/3 ... 60 Hz. In the case of diverging frequencies or direct current, the values
change by the factor indicated below
Miniature circuit-breakers
S 200/S 200 M series
alternating current direct current
100 Hz 200 Hz 400 Hz
factor ca. 1.1 1.2 1.5 1.5
The thermal release operates independently of voltagest.
operating sequence: B and C according to DIN VDE 0641, DIN VDE 0660 Part 101 ICS
K and Z according to IEC 947
Short circuit rupturing capacity and back-up
series alternating current direct current Max. back-up
trip characteristic 1phase 2/3phase 1pole
rated current 133 V 230 V 230 V 400 V 60 V ... main
133/230 V 230/400 V fuse circuit-br.
A kA/cos ϕkA/cos ϕkA/cos ϕkA/cos ϕkA/T ms gL S 700
S 200-B 6 63 A 100 A
S 200 M-B 10 ... 20 10/0.5 6/0.7 10/0.5 6/0.7 10/4.0 100 A 100 A
25 ... 32 100 A 100 A
40 10/0.5 10/0.5 125 A 100 A
50 ... 63 (S 200 M-B) (S 200 M-B) 160 A 100 A
S 200-C 0.5 ... 2 unlimited not required
S 200 M-C 3 ... 4 20 A
S 200-D 6 40 A 100 A
810/0.5 6/0.7 10/0.5 6/0.7 10/4.0 63 A 100 A
10 ... 20 100 A 100 A
25 ... 32 10/0.5 10/0.5 100 A 100 A
40 ( S 200 M-C) (S 200 M-C) 125 A 100 A
50 ... 63 160 A 100 A
S 200-K 0.5 ... 2 unlimited not required
320 A
425 A
6 ... 10 63 A 100 A
16 ... 20 10/0.5 6/0.7 10/0.5 6/0.7 10/4.0 80 A 100 A
25 ... 32 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
S 200-Z 0.5 ... 2 unlimited not required
3 ... 4 20 A
635 A 100 A
840 A 100 A
10 ... 16 10/0.5 6/0.7 10/0.5 6/0.7 10/4.0 63 A 100 A
20 ... 25 80 A 100 A
32 ... 40 100 A 100 A
50 ... 63 125 A 100 A
In symmetrically earthed direct current circuits, 2-pole devices (two poles connected in series) can be used up to 110 VDC. Any connection is possible,
polarity does not need to be taken into account.
Back-up protection is necessary only if the solid short-circuit current to be expected at the place of installation may exceed the switching capacity indicated.
10
System
pro M compact ®
SK 0112 Z 99 SK 0113 Z 99
Miniature circuit-breakers
S 200/S 200 M series
2 15 15 15 15 15 15 15 15 15 1 1.2 4 15 15 15 15 15 15 15
3 15 15 15 15 15 15 15 10 10 0.3 0.7 1.2 4.6 6 6 6 6 6 6
4 15 15 15 15 15 15 15 10 10 0.3 0.6 0.9 2.8 6 6 6 6 6 6
6 15 15 15 15 15 15 15 10 10 0.2 0.5 0.8 2 3.3 5.5 6 6 6 6
8 15 15 15 15 15 15 15 10 10 0.2 0.4 0.7 1.7 2.8 4.5 6 6 6 6
10 15 15 15 15 15 15 15 10 10 0.2 0.4 0.7 1.5 2.5 3.5 5 6 6 6
13 15 15 15 15 15 15 15 10 10 0.7 1.5 2.5 3.5 5 6 6 6
16 15 15 15 15 15 15 15 10 10 1.3 2 2.9 4.1 6 6 6
20 15 15 15 15 15 15 10 10 1.8 2.6 3.5 5 6 6
25 15 15 15 15 15 10 10 1.8 2.6 3.5 5 6 6
32 15 15 15 15 10 10 2.2 3 4 6 6
40 ** 15 15 15 10 10 2.5 4 6 6
50/63 15 15 10 10 3.5 5 6
2 15 15 15 15 15 15 15 15 15 0.3 1.2 4 15 15 15 15 15 15 15
3 10 10 10 10 10 10 10 10 10 0.3 0.7 1.2 4.6 6 6 6 6 6 6
4 10 10 10 10 10 10 10 10 10 0.3 0.6 0.9 2.8 6 6 6 6 6 6
610 1010101010101010 0.71.7 35.96 6 6 6
810 1010101010101010 1.32.23.6 6 6 6 6
10 10 10 10 10 10 10 10 10 10 1.7 2.5 4 6 6 6
16 10 10 10 10 10 10 10 10 10 2.2 3.1 4.6 6 6
20 10 10 10 10 10 10 10 10 3.1 4.6 6 6
25 10 10 10 15 10 10 10 2.6 3.5 6 6
32 10 10 10 10 10 10 3.5 6 6
40 ** 10 10 10 10 10 5.5 6
50/63 10 10 10 10 6
2 15 15 15 15 15 15 15 15 15 0.5 2 15 15 15 15 15 15 15 15
310 10101010101010100.30.71.2 6 6 6 6 6 6 6
410 10101010101010100.30.61.3 7 6 6 6 6 6 6
6 10 10 10 10 10 10 10 10 10 0.2 0.5 0.9 2.7 6 6 6 6 6 6
8 10 10 10 10 10 10 10 10 10 0.2 0.5 0.6 1.7 3.8 6 6 6 6 6
10 10 10 10 10 10 10 10 10 10 0.4 0.6 1.3 2.4 4 6 6 6 6
16 10 10 10 10 10 10 10 10 10 0.5 1.1 1.7 3 4.5 6 6 6
20 10 10 10 10 10 10 10 10 0.9 1.5 2.3 3.5 5.2 6 6
25 10 10 10 15 10 10 10 1.4 2 3 4 6 6
32 10 10 10 10 10 10 1.4 2 3 4 6 6
40 ** 10 10 10 10 10 2 3 4 6 6
50/63 10 10 10 10 2.2 3.5 5.8 6
S 200 M-B, C
Current values smaller
than 6 A and 8 A,
apply only to
C characteristics.
Short circuit selectivity: In the case of a short circuit, selectivity exists up to the values indicated.
In16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 125 160
A
2 15 15 15 15 15 15 15 15 15 1 1.2 4 15 15 15 15 15 15 15
3 10 10 10 10 10 10 10 8 8 0.3 0.7 1.2 4.6 6 6 6 6 6 6
4 10 10 10 10 10 10 10 8 8 0.3 0.6 0.9 2.8 6 6 6 6 6 6
6 10 10 10 10 10 10 10 8 8 0.2 0.5 0.8 2 3.3 5.5 6 6 6 6
8 10 10 10 10 10 10 10 8 8 0.2 0.4 0.7 1.7 2.8 4.5 6 6 6 6
10 10 10 10 10 10 10 10 8 8 0.2 0.4 0.7 1.5 2.5 3.5 5 6 6 6
13 10 10 10 10 10 10 10 8 8 0.7 1.5 2.5 3.5 5 6 6 6
16 10 10 10 10 10 10 10 8 8 1.3 2 2.9 4.1 6 6 6
20 10 10 10 10 10 10 8 8 1.8 2.6 3.5 5 6 6
25 10 10 10 10 10 8 8 1.8 2.6 3.5 5 6 6
32 10 10 10 10 8 8 2.2 3 4 6 6
40 ** 10 10 10 8 8 2.5 4 6 6 6
50/63 10 10 8 8 3,5 5 6
series
S 200-B, C, D
Current values smaller
than 6 A and 8 A,
apply only to C and D
characteristics.
MCBs short circuit discrimination in kA
to main circuit breaker S 700
S 200-K
Selectivity values apply to
Icu according to IEC 947-2.
to fuse gL/gG
(DIN VDE 0636; IEC 269/3)
** Limited or no selectivity at all possible in the overload range (thermal tripping)
S 200 Z
Selectivity values apply to
Icu according to IEC 947-2.
The above values require that, in the case of multi-phase installations, that the last cb be feed from above.
11
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
Tripping diagrams
Reading example for tripping characte-
ristic of the B-type trip characteristics
(in connection with the table
tripping characteristics on page 9, line B)
aThermal tripping characteristic:
Conventional non-tripping current
I1 = selected non-tripping current
The MCB maintains the 1.13 times
of the rated current for at least
60 minutes.
Conventional tripping current
I2 = selected tripping current.
The MCB switches off within
60 minutes when the 1.45 times
of the rated current is reached.
bElectromagnetic trip characteristic
AC:
The MCB maintains current rushes of
the 3-fold of the rated current for
more than 0.1 sec. (in this example
up to ca. 4 sec.).
The MCB switches off within less than
0.1 sec when the 5-times of the rated
current is reached.
SK 0038 Z 01
trip characteristic: C
In = 0.5 ... 63 A
S 200/S 200 M MCBs
SK 0128 Z 00
trip characteristic: D
In = 0.5 ... 63 A
S 200 MCBs
2CDC 022 377 F0203
SK 0142 Z 00
trip characteristic: K
In = 0.5 ... 63 A
S 200 MCBs
Note: Deviating ambient temperature values and interdependencies need
to be taken into account
SK 0146 Z 00
trip characteristic: Z
In = 0.5 ... 63 A
S 200 MCBs
trip characteristic: B
In = 6 ... 63 A
S 200/S 200 M MCBs
12
System
pro M compact ®
Pulse tripping of the MCBs S 200/S 200 M made by ABB-STOTZ-KONTAKT
Miniature circuit-breakers
S 200/S 200 M series
Example: non-tripping current (electromagnetic release)
S 201-B16 Ihold = K x non-tripping current B-type characteristic = 3 x In
Ihold = 4.2 x 3 x 16 C-type characteristic = 5 x In
Ihold = 201.6 A D-type characteristic = 10 x In
K-type characteristic = 10 x In
Z-type characteristic = 2 x In
In the case of an impulse of 600 , S 201-B16 maintains up to a current of 201.6 A.
2CDC 022 131 F0203
13
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
Diagrams of let-through values I2 t at 230/400 VAC
Miniature circuit-breakers S 200 B/C, D on request Miniature circuit-breakers S 200 K
Miniature circuit-breakers S 200 Z Miniature circuit-breakers S 200 M B/C
min. pre-arcing I2t, e.g. In = 80 A gL
max. let-through I2t MCB e.g. B20 A
Fuse-MCB, selectivity with respect to the upstream fuse to the point of intersection of both curves and .
e.g. S 200-B20 to fuse 80 A: selectivity up to 3.5 kA min.
Let-through value I2t reduced:
127 V by factor 2.5
110 V by factor 3
2CDC 022 157 F0203
2CDC 022 132 F0203
2CDC 022 152 F0203
2CDC 022 159 F0203
14
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
The influence of ambient temperature and interdependencies in the case of even loads on the load
capability of MCBs
Practical Note: This practical deduction, that is applicable for all types of characteristics, can be recommended for standard
environments. Selection criteria for rated current of circuit-breakers according to EN 60898 and EN 60947-2.
Choose the circuit-breaker that is appropriate for the lower of the rated value of the device or the permissible current loading.
Now, the major factors having an influence on the circuit-breaker, must be taken into account:
1. ambient temperature with IB 0.9 x In at 40 °C ambient temperature
2. mutual influence with IB 0.75 x In in the case of more than one circuit-breaker being loaded evenly in parallel.
The ensuing rated current of the circuit breaker is thus: In = 1.5 x rated current
Example: operating currect 4 A, then the rated current of the circuit-breaker is: In = 1.5 x 4 A = 6 A
The above takes into account all relevant factors and the circuit is protected at the lowest possible level.
This practical note is based on the following:
1. Deviating ambient temperature: The thermal releases are adapted to a given reference ambient temperature. For the K- and Z-type
characteristics, it is 20 °C, for B-, C- and D-type, it is 30 °C.
For all other ambient temperatures, the current values indicated vary by ca. 6 % per 10 K temperature de/increase.
For more precise calculations and very high/low ambient temperatures, the following tables apply:
Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type B, C and D
B, C and D Ambient temperature T (°C)
In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70
0.5 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.0 1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
1,6 2.13 2.07 2.00 1.92 1,85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2,0 2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
3,0 4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
4,0 5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
6,0 8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
8,0 10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
10,0 13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
13,0 17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
16,0 21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
20,0 26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
25,0 33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
32,0 42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
40,0 53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
50,0 66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
63,0 84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type K and Z
K and Z Ambient temperature T (°C)
In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70
0.5 0.66 0.64 0.61 0.59 0.56 0.53 0.50 0.47 0.43 0.40 0.35 0.31
1.0 1.32 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61
1.6 2.12 2.04 1.96 1.88 1.79 1.70 1.60 1.50 1.39 1.26 1.13 0.98
2.0 2.65 2.55 2.45 2.35 2.24 2.12 2.00 1.87 1.73 1.58 1.41 1.22
3.0 4.0 3.8 3.7 3.5 3.4 3.2 3.0 2.8 2.6 2.4 2.1 1.8
4.0 5.3 5.1 4.9 4.7 4.5 4.2 4.0 3.7 3.5 3.2 2.8 2.4
6.0 7.9 7.6 7.3 7.0 6.7 6.4 6.0 5.6 5.2 4.7 4.2 3.7
8.0 10.8 10.2 9.8 9.4 8.9 8.5 8.0 7.5 6.9 6.3 5.7 4.9
10.0 13.2 12.7 12.2 11.7 11.2 10.6 10.0 9.4 8.7 7.9 7.1 6.1
13.0 17.2 16.6 15.9 15.2 14.5 13.8 13.0 12.2 11.3 10.3 9.2 8.0
16.0 21.2 20.4 19.6 18.8 17.9 17.0 16.0 15.0 13.9 12.6 11.3 9.8
20.0 26.5 25.5 24.5 23.5 22.4 21.2 20.0 18.7 17.3 15.8 14.1 12.2
25.0 33.1 31.9 30.6 29.3 28.0 26.5 25.0 23.4 21.7 19.8 17.7 15.3
32.0 42.3 40.8 39.2 37.5 35.8 33.9 32.0 29.9 27.7 25.3 22.6 19.6
40.0 52.9 51.0 49.0 46.9 44.7 42.4 40.0 37.4 34.6 31.6 28.3 24.5
50.0 66.1 63.7 61.2 58.6 55.9 53.0 50.0 46.8 43.3 39.5 35.4 30.6
63.0 83.3 80.3 77.2 73.9 70.4 66.8 63.0 58.9 54.6 49.8 44.5 38.6
2. Interdependencies in
the case of even loads
A correction factor must be
taken into account in the
case butt-mounted devices
and an evenly applied, high
load:
2 and 3 circuit-breakers
with factor 0.9
4 and 5 circuit-breakers
with factor 0.8
6 and more circuit-breakers
with factor 0.75
The interdependency
becomes irrelevant if
FST … spacers or
packing blocks (9mm
width) are used.
The influence of ambient temperature and interdependencies in the case of even loads on the load
capability of MCBs
Practical Note: This practical deduction, that is applicable for all types of characteristics, can be recommended for standard
environments. Selection criteria for rated current of circuit-breakers according to EN 60898 and EN 60947-2.
Choose the circuit-breaker that is appropriate for the lower of the rated value of the device or the permissible current loading.
Now, the major factors having an influence on the circuit-breaker, must be taken into account:
1. ambient temperature with IB 0.9 x In at 40 °C ambient temperature
2. mutual influence with IB 0.75 x In in the case of more than one circuit-breaker being loaded evenly in parallel.
The ensuing rated current of the circuit breaker is thus: In = 1.5 x rated current
Example: operating currect 4 A, then the rated current of the circuit-breaker is: In = 1.5 x 4 A = 6 A
The above takes into account all relevant factors and the circuit is protected at the lowest possible level.
This practical note is based on the following:
1. Deviating ambient temperature: The thermal releases are adapted to a given reference ambient temperature. For the K- and Z-type
characteristics, it is 20 °C, for B-, C- and D-type, it is 30 °C.
For all other ambient temperatures, the current values indicated vary by ca. 6 % per 10 K temperature de/increase.
For more precise calculations and very high/low ambient temperatures, the following tables apply:
Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type B, C and D
B, C and D Ambient temperature T (°C)
In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70
0.5 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.0 1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
1,6 2.13 2.07 2.00 1.92 1,85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2,0 2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
3,0 4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
4,0 5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
6,0 8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
8,0 10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
10,0 13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
13,0 17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
16,0 21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
20,0 26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
25,0 33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
32,0 42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
40,0 53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
50,0 66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
63,0 84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type K and Z
K and Z Ambient temperature T (°C)
In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70
0.5 0.66 0.64 0.61 0.59 0.56 0.53 0.50 0.47 0.43 0.40 0.35 0.31
1.0 1.32 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61
1.6 2.12 2.04 1.96 1.88 1.79 1.70 1.60 1.50 1.39 1.26 1.13 0.98
2.0 2.65 2.55 2.45 2.35 2.24 2.12 2.00 1.87 1.73 1.58 1.41 1.22
3.0 4.0 3.8 3.7 3.5 3.4 3.2 3.0 2.8 2.6 2.4 2.1 1.8
4.0 5.3 5.1 4.9 4.7 4.5 4.2 4.0 3.7 3.5 3.2 2.8 2.4
6.0 7.9 7.6 7.3 7.0 6.7 6.4 6.0 5.6 5.2 4.7 4.2 3.7
8.0 10.8 10.2 9.8 9.4 8.9 8.5 8.0 7.5 6.9 6.3 5.7 4.9
10.0 13.2 12.7 12.2 11.7 11.2 10.6 10.0 9.4 8.7 7.9 7.1 6.1
13.0 17.2 16.6 15.9 15.2 14.5 13.8 13.0 12.2 11.3 10.3 9.2 8.0
16.0 21.2 20.4 19.6 18.8 17.9 17.0 16.0 15.0 13.9 12.6 11.3 9.8
20.0 26.5 25.5 24.5 23.5 22.4 21.2 20.0 18.7 17.3 15.8 14.1 12.2
25.0 33.1 31.9 30.6 29.3 28.0 26.5 25.0 23.4 21.7 19.8 17.7 15.3
32.0 42.3 40.8 39.2 37.5 35.8 33.9 32.0 29.9 27.7 25.3 22.6 19.6
40.0 52.9 51.0 49.0 46.9 44.7 42.4 40.0 37.4 34.6 31.6 28.3 24.5
50.0 66.1 63.7 61.2 58.6 55.9 53.0 50.0 46.8 43.3 39.5 35.4 30.6
63.0 83.3 80.3 77.2 73.9 70.4 66.8 63.0 58.9 54.6 49.8 44.5 38.6
15
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
Use of S 200/S 200 M miniature circuit-breakers in direct current circuits 60 VDC/125 VDC
In DC systems up to 60 VDC or, as the case may be, series connection up to 125 VDC, customary S 200/S 200 M series MCBs can be used.
Polarity does not need to be taken into consideration, the outgoing circuit may be implemented from above or below the device.
For higher direct voltage up to 440 VDC devices of the S 280 UC series must be used.
Example for max. permissible voltages between conductors depending on the number of poles and type of connection.
Fusing of lighting currents
1. Filament lamps and fluorescent lamps
The following table indicates the maximum number of fluorescent lamps that can be protected with a single-pole miniature circuit-breaker.
In the case of multipole MCBs, the value is reduced by 20 %. Tripping charcteristic type C allows for light currents up to the rated current
of the MCB,
for fusing of: filament lamps
fluorescent lamps a) non-compensated
b) shunt compensated (cos ϕ = 0.95)
c) electronic load
2. High-pressure discharge lamps
Starting current: ca. 1.7 x lamp current
Recovery time: ca. 3 ... 5 min.
According to the type of lamp, line impedance and start-stop torque, the so-called rectifier effect may occur which superimposes the
starting current of the lamp for some half-waves.
In the most unfavorable circumstances, inrush currents of 15 times of the lamp nominal current may ensue.
To avoid nuisance tripping, MCBs with K-type characteristic should not carry loads higher than 0.6-fold of the lamp current. The load factor
indicated refers to the least favorable case (proximity to transformer, low line impedances).
Examples for different voltages between a conductor and earth where voltages between conductors are identical:
electronic ballast: twin-lamp style, jointly switched number of lamps
Characteristic/ non-compensated shunt compensated electronic ballast
rated current conventional ballast conventional ballast
18/20 W 36/40 W 58/65 W 18/20 W 36/40 W 58/65 W 18/20 W 36/40 W 58/65 W
10 27 23 15 32 32 20 18 18 8
16 43 37 24 51 51 33 26 26 12
20 53 46 30 64 64 41 33 33 15
25 66 58 37 82 82 53 42 42 19
SK 0173 Z 99
SK 0174 Z 99
16
System
pro M compact ®
Miniature circuit-breakers
S 200/S 200 M series
Installation and operation instructions
Installation
Can be installed in any mounting position due to snap-on fixing to DIN rails EN 60 715, 35 mm width.
AIf MCB S 200/S 200 M is installed without cross wiring, hinge the upper part into the DIN rail and push to let the lower part of the device snap
into place (1). The device is released in the reverse order, after the quick fastener has been removed with a screw driver (2).
BTo release S 200 /S 200 M that are cross-wired with System pro M compact busbars, first remove the clamping screws Then, pull the lower
part of the S 200/S 200 M forwards (1) and lift it straight up (1a) , then, the quick fastener (1b) will recede.
CThe busbar is deallocated and the S 200/S 200 M can be pulled out by lifting the device forwards (2).
DThe cross-wiring is re-inserted in the reverse order. First, open the clamping screws and pull out the quick fastener until it locks into place
for the first time (3) . Then, take the S 200 /S 200 M and insert it with rear terminal side onto the pins of the System pro M compact busbar
(4) , turn it into the direction of the DIN rail (4a) and shift it vertically downwards (4b) ,this way, the quick fasterner snaps back into place
(4c).
Attention: Do not forget to re-tighten the clamping screws.
2CDC 022 153 F0003
Operation
MCBs are switched on by switching the operating lever into the upper position (with resepct to the text block of the nameplate). If an MCB,
after it has triggered, cannot be switched on again off-handedly, the triggering is probably caused by overload.
If the MCB trips again immediately when trying to reclose (let a short period of time elapse), a complete short-circuit, or as the case may
be, earth connection can be assumed.
Do not try and continuously re-close an existing short circuit or earth fault. The MCB even trips under overload, or short-circuit or earth
fault conditions, even if the operating lever is maintained in the ON position by force (trip-free mechanism).
Cleaning the device
MCBs soiled by installation work should be cleaned with a dry, or, if necessary, a damp and soapy cloth. Never use caustic agents or
dissolvents.
Maintenance
STOTZ MCBs are maintenance-free.
Opening the device will lead to a loss of warranty.
Connection:
For connection cross sections, see page 7.
Feeder optional, top or bottom, terminal designation according to EN 50 005.
For wiring diagrams, see picture to the right.
CRemoval when
pro M compact
cross wiring
remains in place
SK 0267 Z 98
SK 0266 Z 98
SK 0268 Z 98
SK 0269 Z 98
pro M compact
busbar
pro M compact
busbar
quick
fastener
DInsertion when
pro M compact
cross wiring
remains in place
AAssembly,
disassembly
without
pro M compact
cross wiring
BDetaching when
pro M compact
cross wiring
remains in place
snap on release
pro M compact
busbar
pin
SK 0167 Z 99
pin
17
System
pro M compact ®
Additional devices
Mounting additional devices
Additional devices are always fitted from the right hand side:
– signal contact/auxiliary switch S2C-S/H6R for MCBs and RCCBS
– auxiliary switch S2C-H6R for MCBs
– shunt release S2C-A for MCB
Supplementary devices
2CDC 092 154 F0003
S function signal contact
H function auxiliary switch
1. Signal contact and auxiliary switches
Retrofittable to the right side of circuit-breakers or shunt releases without extra installation devices.
1.1 Universal signal contact/ auxiliary switch type S2C-S/H6R
Description
S2 – serial code: S 2 C - S/H 6 R
R = right side-mounted
6 = change over
H = auxiliary switch
S = signal contact
C = compatible to pro M compact
S2C-S/H6R is a universal device complementing the range of pro M compact, which is supplied to offer signal contact functionality,
or the auxiliary switch can be activated, all you need is a screwdriver. The universal switch can be with MCBs and RCCBs.
Up to three S2C-H6R can be mounted (one signal contact max. fitted to MCB or RCCB). Both the switchgear and the S2C-S/H6R must
be in the ON end position to ensure that the coupling is correct.
Function of the signal contact S
Signal is transmitted only if caused by fault-tripping of the circuit-breaker, but not if the switch has been switched on or off manually.
Press the orange reset button to acknowledge the has-tripped signal.
Function of the auxiliary switch H
The switch always indicates the switching position of the MCB, irrespective of whether the switching position is attributable to manual
operation or fault tripping.
Functionality selection
To select either the signal contact function S or the auxiliary switch H, use a screwdriver and adjust to position S, or as the case may be, H at
the side of the device.
SK 0170 Z 02
to MCBs
and RCCBs only to
MCBs to shunt releases
18
System
pro M compact ®
Supplementary devices
Installation:
1. Mounting one S2C-S/H6R
RCCB or MCB must be in the ON position remove coupling cover on the right side of the MCB/RCCB signal contact/auxiliary
switch in ON position if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin plug devices together.
SK 0287 Z 02 SK 0288 Z 02
2. Mounting more than one S2C-S/H6R
Up to three S2C-H6R can be mounted.
Note: one signal contact max. fitted at first to MCB or RCCB
If fitted to an MCB, remove the bottom coupling pin (RCD), if fitted to an RCCB, remove the middle coupling pin (MCB), switch all signal
contact/ auxiliary switches to the end position ON, plug them together and carry through a function control test.
SK 0285 Z 02
Function control test:
After all signal contacts/auxiliary switches or auxiliary switches have been mounted, use the upper coupling pin to switch on the devices
(ON position). If the lower (for RCD) or, as the case may be, the middle (for MCB) coupling pin is operated, all devices must trip.
Now combination with MCB/RCCB:
RCCB or MCB must be in the ON position remove coupling cover on the right side of the MCB/RCCB signal contact/auxiliary switch
in ON position if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin plug devices together.
SK 0240 Z 02
Test functions of the signal contact
in ON and OFF position after hand operation
SK 0241 Z 02
Test functions of the auxiliary switch
in ON position
SK 0242 Z 02
in ON position after tripping
SK 0243 Z 02
in OFF position
19
System
pro M compact ®
Supplementary devices
Technical Data
Signal contact/auxiliary switch S2C-S/H6R and auxiliary switch S2C – H6R according to EN 62019
rated current Ith: 10 A
min. rated voltage UBmin: 24 V ~, 24 V ...
min. rated operational current: 5 VA
short-circuit withstand capacity: 230 V~ 1000 A with S 201 K 4
insulation coordination: according to DIN VDE 0110 Parts 1 and 2
– overvoltage category: III
– surge voltage: 4 kV (1.2/50 µs)
– pollution degree: 2
connection cross section: 0.75 ... 2.5 mm2 (up to 2 x 1.5 mm2)
tightening torque: 1.2 Nm max.
contact stability in vibration test
according to DIN IEC 68-2-6-: 5 g, 20 sweep cycles 5 ... 150 ... 5 Hz
at 24 VAC/DC, 5 mA automatic reclosing < 10 ms
mech. service life: 10 000 operations
The minimum rated operational current value applies in the case of operation and environmental conditions according to
EN 60 204-1/1998 and EN 60 439-1/2000 if installed indoors and in clean ambient air: 24 VAC/DC, 5 mA (AC-12, DC-12)
1.2 Auxiliary switch type S2C-H6R
Description
The simple auxiliary switch without test functionality is appropriate for applications where it is only necessary to indicate the contact
position of the circuit-breaker.
Up to three S2C-H6R can be butt-mounted, including combinations with the signal contact/auxiliary switch SC2-S/H6R.
Installation and technical data
the same as for signal contact/auxiliary switch SC2-S/H6R, see preceding page and above.
Installation and technical data
the same as for signal contact/auxiliary switch SC2-S/H6R, see preceding page and above.
2. Shunt trip S2C-A
Description
For distance tripping of the MCB. The shunt release has a relay coil with an integrated contact which disconnects the coil and the coil
voltage if the MCB trips, this prevents the flow of current in the case of sustained coil voltage.
Technical data
type: S2C - A1 S2C - A2
service voltage: 12 ... 60 V 110 ... 415 VAC and 110 ... 250 VDC
AC 14
DC 12
DC 13
Ue400 V 230 V
Ie1 A 2 A
Ue220 V 110 V
Ie1 A 1.5 A
Ue60 V 24 V
Ue1.5 A 4 A
STOTZ-Shunt trip with automatic disconnecting within 10 milliseconds UB = Un + 10 – 30 %
UBIBmax UBIBmax
S2C-A1 12 VDC 2.2 A S2C-A2 110 VDC 0.35 A
12 VAC 2.5 A 110 VAC 0.5 A
24 VDC 4.5 A 220 VDC 1.1 A
24 VAC 5 A 230 VAC 1.0 A
60 VDC 14 A 415 VAC 2.7 A
60 VAC 8.8 A
UB = operating voltage IBmax = operating current
20
System
pro M compact ®
Residual-current-operated circuit breaker
F 200 series
Description
Residual-current protective devices have a balance or, as the case may be, differential current transformer as measuring device that is
connected with permanent magnet trip via the secondary winding. Residual-current protective devices cover a.c. fault current and
pulsating d.c. fault current and are insensitive to current rushes up to 250 A, selective and short-time delayed tripping types up to 3,000 A).
Pulse shape 8/20 according to DIN VDE 0432 Part 2.
STOTZ residual-current protective devices are surge-proof and thus insensitive to transient leakage current to earth, as may occur e.g.
when switching fluorescent lamps, X-ray apparatus, IT systems and also thyristor control. (The value of the surge strength is indicated in
the technical data information regarding the switching variants).
Protection through RCD of types AC, A and B according to IEC 755
Selective RCCB F 200S
Is installed centrally and operates on a time-selective basis with respect to more sensitive downstream residual-current devices.
The result is a high degree of service security, as in the case of a fault, only the circuit affected will be switched off.
Due to their surge strength of up to 5,000 A/3,000 A, nuisance tripping of STOTZ main RCCBs caused by remote strike is ruled out.
They are therefore the perfect choice for the connection of freezers and agricultural applications (e.g. fans in intensive livestock husbandry)
according to DIN VDE 0100 Part 705.
Short-time delayed RCCBs F 200 R
are RCCBs with high surge strength needed where apparatus causes high leakage currents when switched on or off (e.g. lighting circuits
with ballast, long lines).
Application
To obtain a better level of security in all wiring systems, as well as in supply areas with respect to which codes of practice
recommend or require the use of residual-current protective devices.
Tasks
Protection against electric shock
Measures for the protection against electric shock as provided for in DIN VDE 0100 Part 410. These measures are:
Protection from indirect touch – as fault protection through disconnection of circuit in the case of excessive touch voltage caused by
short circuit to exposed conductive part.
Protection from direct touch – as additional protection through disconnection when conductive parts are touched. Dangerous leakage
current is switched off within the shortest possible time if the rated residual current of the circuit-breakers is In 30 mA, in the case of
people protector FS 201 In 10 mA.
Protection against fire – protection against fire ignited by electricity if the nominal residual current of the circuit-breaker is In 300 mA.
form of residual current
sinusoidal a.c.
pulsating d.c.
smooth d.c.
correct functioning of RCD
a.c.- sensitive
type AC
pulsating
current-sensitive
type A
d.c.-sensitive
type B
F 200 AC
F 200
suddenly applied slowly rising
suddenly applied with/without
superimosed smooth
d.c. of 6 mA slowly rising
21
System
pro M compact ®
Residual-current-operated circuit-breakers
F 200 series/FS 201
Technical data F 200 F 200 R F 204 S FS 201
short time delayed selective RCBO
specifications: DIN VDE 0664 Part 11, EN 61008-2-1 DIN VDE 0664 Part 21
and EN 61009/IEC 61009
No. of poles: 2-pole 2-pole 2-pole 4-pole
4-pole 4-pole 4-pole
tripping characteristics:
B and C acc. to DIN VDE 0641 and EN 60898;
K acc. to DIN VDE 0660 and EN 60947
rated current In:
16, 25, 40, 63 A 25, 40, 63 A
25, 40, 63 A 40 A, 63 A 6 to 32 (40) A
rated residual current In:
10, 30, 300 30, 100
30 mA 300 mA 10 mA, 30 mA, 300 mA
and 500 mA and 300 mA
tripping range at 0.50 ... 1.0 · In
at 0.11 ... 1.4 · In
tripping time at 1 · In:
300 ms 300 ms
120 … 300 ms 150 ... 500 ms 300 ms
at 2 · In: 50 … 150 ms 60 ... 200 ms
at 5 · In:
40 ms 40 ms
40 ... 150 ms 40 ms
at 500 A: 20 … 40 ms 40 ... 150 ms
tripping time at 1 · 1,4 In:
300 ms
300 ms 300 ms 300 ms
at 5 · 1,4 In:
40 ms
40 ms 50 ... 150 ms 40 ms
rated switching capacity: 6 kA, ϕ 0,7
surge strength (impulse waveshape 8/20): 250 A 3000 A 5000 A 250 A
short-circuit withstand capacity:
10.000 A, in connection with an upstream 10.000 A, in connection
fuse gL 100 A or the STOTZ selective with an upstream fuse
main circuit-breaker S 700-E 100 A gL 100 A or the selective
main circuit-breaker
S 700-E 100 A
rated voltage Un: 2-pole: 230 V ~ 4-pole: 230/400 V ~ 230/400 V ~ 2-pole: 230 V ~
max. operating voltage UBmax:U
n + 10 %
operative range of test equipment UT: 100 V ~ to 264 V ~ 100 V ~ to 264 V ~ 100 V ~ to 264 V ~
insulation coordination according to
DIN VDE 0110 Part 1 and 2
– overvoltage category: III, disconnector abilities
– pollution degree: 2
– surge voltage Uimp (1,2/50): 4 kV
power-frequency withstand voltage (50/60 Hz):
2.5 kV
frequency: 50/60 Hz 50/60 Hz
housing: moulding grey moulding grey
operating lever/test button: blue black/blue
degree of protection: IP 20; in the distribution board IP 40;
in moulded-plastic casing IP 55 (see accessories)
dimensions: see dimension drawings
connection cross section: 1 to 16 mm2 for finely-stranded to massive conductors 1 to 16 mm2
for In to 40 A, 1 to 25 mm2 for In 63 A
service life: > 5.000 switches
climatic resistance according to DIN IEC 68 Part 2-30:
damp heat: 28 cycl. 55/95 … 100 (°/RH)
(RH = rel. humidity) damp heat, cyclic (55 °C/28 cycles) alterning climate: 25/95 - 40/93 (°C/RH)
constant climate: 23/83, 40/93,
55/95 … 100 (°C/RH)
ambient temperature: Tmax. + 55 °C Tmin. – 25 °C
vibration resistance according to: DIN VDE 0664 Part 1/10.85 and EN 61008 DIN VDE 0664 Part 2/10.85
and EN 61009
terminals: bi-directional cylinder-lift terminal
trip-free mechanism: yes
connection: individually or collectively via a busbar
supplementary devices: type S2C-S/HR s. pagee 17 in preparation
F 200
AC
22
System
pro M compact ®
Residual-current-operated circuit-breakers
F 200 series/FS 201
Installation and operation instructions
Installation
Can be installed in any mounting position due to snap-on fixing to DIN rails EN 50 022, 35 mm width.
AIf RCD F 200/FS 201 is installed without cross-wiring , hinge the upper part into the DIN rail and push to let the lower part of the device snap
into place (1). The device is released in the reverse order, after the quick fastener has been removed with a screw driver (2).
BTo release RCD F 200/FS 201 that are cross-wired with System pro M compact busbars, first remove the clamping screws. Then, pull the
lower part of the F 200/FS 201 forwards (1) and lift it straight up (1a), then, the quick fastener will recede (1b).
CThe busbar is deallocated and the RCD F 200/FS 201 can be pulled out by lifting the device forwards (2).
DThe cross-wiring is re-inserted in the reverse order. First, open the clamping screws and pull out the quick fastener until it locks into place
for the first time (3). Then, take the RCD F 200/FS 201 and insert it with the rear terminal side onto the pins of the System pro M compact
busbar (4), turn it into the direction of the DIN rail (4a) and shift it vertically downwards (4b), to let the quick fastener snap back into place
(4c).
Attention: Do not forget to re-tighten the clamping screws.
Connection
Feeder optional, top or bottom. Ensure that conductors are con-
nected correctly and firmly.
If the 4-pole RCCB is operated as a 2-pole RCCB, use terminals
5 and 7 or, as the case may be, 6 and 8 to make sure that the
test button function of the RCCB is working. In the case of a
three-phase system with Un = 127/230 V (without neutral N),
terminals 4 and 8 must be bridged.
Operation
F 200/FS 201 is switched ON or OFF with the blue operating
lever.
SK 0012 Z 96
SK 0272 Z 98
2CDC 032 138
F0203
CRemoval when
pro M compact
cross wiring
remains in place
SK 0267 Z 98
SK 0266 Z 98
SK 0268 Z 98
SK 0269 Z 98
pro M compact
busbar
pro M compact
busbar
quick
fastener
DInsertion when
pro M compact
cross wiring
remains in place
AAssembly,
disassembly
without
pro M compact
cross wiring
BDetaching when
pro M compact
cross wiring
remains in place
snap on release
pro M compact
busbar
pin
SK 0167 Z 99
pin
Operating test
To test proper functioning, press the blue test button when the device is switched ON, the RCCB must trip immediately (the knob jumps into
the „0“ switching position).
It is necessary to test the RCD halfyearly, if no other regional or user specified additional test are required.
23
System
pro M compact ®
Residual-current-operated circuit-breakers
F 200 series/FS 201
Test of protective measure
Except for the operating test, the effectiveness of the protection provided within the installation must be tested according to the applicable codes
of practice. For RCD protection, the maximum permissible earthing resistance values are as follows:
max. max. earthing resistance
touch at nominal residual current
voltage UL10 mA 30 mA 100 mA 300 mA 500 mA
25 V 2500 833 250 83 50
50 V 5000 1666 500 166 100
Malfunctioning
The high-quality STOTZ residual-current-operated circuit-breakers are thorougly adjusted and tested in our works. Where damage occurs
(caused e.g. by transport, storage, etc.) no repair work must be undertaken.
If the device responds immediately after putting the RCCB into operation, check the downstream active circuit and any connected current-
consuming apparatus for earth fault current. Remove insulation faults or connections between the neutral conductor and the protective
conductor existing in load circuit. Where the RCCB does not trip in the first operating test after pressing the test button, check first wheth-
er the test circuit is connected correctly.
Where none of the above causes apply, or should the operating test be completed unsuccessfully, the RCCB must be replaced.
Opening the device will lead to a loss of warranty.
TN-S system (protective multiple earthing)
separate neutral and protective conductors
throughout the network
TN-C-S system
neutral and protective conductor (PEN)
combined in one part of the network.
TT system IT system
The residual-current-operated circuit-breaker trips if a double
fault occurs, as e.g. is indicated as fault 1 and fault 2 above.
Examples for the protection against electric shock
I„insulation“
C„combined“ PE and N (PEN)
S„separated“ PE and N
„…“ terms used in international IEC standard
SK 0005 Z 97SK 0017 Z 95
SK 0040 Z 94 SK 0038 Z 94
only indicated by
line isolation
monitor
Explanation of type codes
L1, L2, L3 line“ phase conductor
PE protection earth“
N„neutral“
PEN PE and N combined
T„terre“ direct bond to earth
24
System
pro M compact ®
Load capability depending on the feed point
bar cross section 10 mm2 16 mm2
max. busbar current IS/phase 63 A 80 A
max. current in branch IE/phase 100 A 130 A*
* If the device is fed via the device terminal, ensure that - irrespective of the current carrying capacity (IS) of the busbar -
the following values are not exceeded:
For devices up to and including 40 A In max. 110 A and for 50/63 A In max. 140 A.
Description
The newly developed pro M compact cross wiring busbar system includes everything that is needed for secure and economic connections
of distribution build-in devices of the series S 200 and F 200.
The optimised quick fastener of the S 200 series, F 200 , when used together with the System pro M compact cross wiring busbars, makes
removing and inserting devices a quick and easy job, and the cross wiring of other devices remains in place, at that.
Busbars are supplied ready-to-use and in standard lengths, time-consuming cutting to length or end caps are no longer required.
MCBs and RCCBs of the customary System pro M technology can also be easily cross-wired with the new System pro M compact busbars.
Technical data
specifications: VDE 0660 Part 500, DIN EN 60439-1: 1994 test surge voltage: (1,2/50) 6,2 kV
busbar material: SF-Cu F 24 short-circuit withstand capacity: 25 kA
insulating profile material: plastic, temperature resistant 90 °C climatic resistance:
constant climate L23/83; 40/92
flame-retardant, self-extinguishing 55/20 according to DIN 50 015
dioxine- and halogene-free humid heat, 28 cycles
(IEC 68 Part 2 - 30)
busbar cross section: 10 mm2insulation coordination: acc. to VDE 0110 Part 1
April 1997 (IEC 664)
max. operating voltage: 440 V - overvoltage category: III
rated surge voltage: 4 kV - pollution degree: 2
incoming supply
incoming supply
at the beginning of the within the busbar
busbar or centre-fed
If the device is centre-fed (see picture to the right), ensure that the combined outgoing currents a1 ...an per branch do not exceed the max. busbar
current IS/phase referred to above.
SK 0063 Z 91
SK 0062 Z 91
Busbars for
series S 200, S 200 M, F 200, FS 201
25
System
pro M compact ®
Miniature circuit-breakers S 200/S 200 M
Residual-current-operated circuit breakers F 200/FS 201
Dimensions
Dimensions measurements in mm
F 202, F 204, F 204 S
SK 0111 Z 99
S 201 H, S 202 H, S 203 H, S 204 H
S 201, S 202, S 203, S 204
SK 0058 Z 01 SK 0136 Z 01
1-pole 2-pole 3-pole 4-pole
1 + NA 3 + NA
1-pole 2-pole 3-pole 4-pole
2-pole 4-pole
SK 0046 Z 02
Supplementary devices
FS 201
SK 0047 Z 02
S2C-S/H 6 R S2C-A...
S2C-H 6 R S2C-UA...
26
System
pro M compact ®
Accessories
Dimensions
Terminal covers measurements in mm
Enclosure of moulded-plastic
Flush frame
type
S 500 - ME 1
S 500 - ME 2
S 500 - ME 3
dim. L
38 mm
88 mm
184 mm
max. No. of modules
(1 module = 17.5 mm)
for 2 Module
for 5 Module
for 10 Module Mounting rails
SK 0136 Z 96
name A A1
DSW 17.5 15
DSW 2 35 20
DSW 3 52.5 37.5
DSW 4 70 55
DSW 6 105 90
PCD 2 N PCD 4 N PCD 6 N SK 0137 Z 96 PCD 8 N SK 0138 Z 96
QES 4/3 N QES 6/3 N
SK 0078 Z98
SK 0079 Z98
SK 0131 Z 94
In the case of DSW 1,
the drill holes
are vertical
SK 0150 Z 93
27
System
pro M compact ®
Busbars
Dimensions
Dimensions measurements in mm
2CDC 062 145 F0203
2CDC 062 139 F0203
PS 1/2 PS 3/6
PS 1/6
PS 1/9
PS 1/12
2CDC 062 140 F0203
2CDC 062 141 F0203
2CDC 062 142 F0203
2CDC 062 146 F0203
2CDC 062 255 F0203
2CDC 062 148 F0203
PS 3/9
PS 3/12
PS 3/12 FI
PS 3/60
2CDC 062 263 F0203
2CDC 062 149 F0203
auxiliary contact
bridge HKB
28
System
pro M compact ®
Busbars
Dimensions
Dimensions measurements in mm
2CDC 062 261 F0203
PS 3/48 H
2CDC 062 260 F0203
PS 3/39 H
2CDC 062 253 F0203
PS 2/58
2CDC 062 251 F0203
PS 2/12
2CDC 062 252 F0203
PS 2/48
2CDC 062 143 F0203
PS 3/12 E 463
2CDC 062 267 F0203
PS 4/58 N
2CDC 062 269 F0203
PS 4/60
2CDC 062 265 F0203
PS 4/12
PS 3/12 FI H
2CDC 062 148 F0203
33
System
pro M compact ®
1
No. of rated order details bbn price price w'ght pack.
poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
0.5 S 201-D 0.5 2CDS 251 001 R0981 52993 8 0.125 10/40
1 S 201-D 1 2CDS 251 001 R0011 52994 5
1.6 S 201-D 1.6 2CDS 251 001 R0971 52995 2
2 S 201-D 2 2CDS 251 001 R0021 52996 9
3 S 201-D 3 2CDS 251 001 R0031 52997 6
4 S 201-D 4 2CDS 251 001 R0041 52998 3
6 S 201-D 6 2CDS 251 001 R0061 52999 0
8 S 201-D 8 2CDS 251 001 R0081 53000 2
10 S 201-D 10 2CDS 251 001 R0101 53001 9
13 S 201-D 13 2CDS 251 001 R0131 53002 6
16 S 201-D 16 2CDS 251 001 R0161 53003 3
20 S 201-D 20 2CDS 251 001 R0201 53004 0
25 S 201-D 25 2CDS 251 001 R0251 53005 7
32 S 201-D 32 2CDS 251 001 R0321 53006 4
40 S 201-D 40 2CDS 251 001 R0401 53007 1
50 S 201-D 50 2CDS 251 001 R0501 55199 1
63 S 201-D 63 2CDS 251 001 R0631 55200 4
0.5 S 202-D 0.5 2CDS 252 001 R0981 53048 4 0.250 5/20
1 S 202-D 1 2CDS 252 001 R0011 53049 1
1.6 S 202-D 1.6 2CDS 252 001 R0971 53050 7
2 S 202-D 2 2CDS 252 001 R0021 53051 4
3 S 202-D 3 2CDS 252 001 R0031 53052 1
4 S 202-D 4 2CDS 252 001 R0041 53053 8
6 S 202-D 6 2CDS 252 001 R0061 53054 5
8 S 202-D 8 2CDS 252 001 R0081 53055 2
10 S 202-D 10 2CDS 252 001 R0101 53058 3
13 S 202-D 13 2CDS 252 001 R0131 53060 6
16 S 202-D 16 2CDS 252 001 R0161 53061 3
20 S 202-D 20 2CDS 252 001 R0201 53063 7
25 S 202-D 25 2CDS 252 001 R0251 53064 4
32 S 202-D 32 2CDS 252 001 R0321 53065 1
40 S 202-D 40 2CDS 252 001 R0401 53066 8
50 S 202-D 50 2CDS 252 001 R0501 55203 5
63 S 202-D 63 2CDS 252 001 R0631 55204 2
0.5 S 203-D 0.5 2CDS 253 001 R0981 53081 1 0.375 3/12
1 S 203-D 1 2CDS 253 001 R0011 53082 8
1.6 S 203-D 1.6 2CDS 253 001 R0971 53083 5
2 S 203-D 2 2CDS 253 001 R0021 53084 2
3 S 203-D 3 2CDS 253 001 R0031 53085 9
4 S 203-D 4 2CDS 253 001 R0041 53086 6
6 S 203-D 6 2CDS 253 001 R0061 53088 0
8 S 203-D 8 2CDS 253 001 R0081 53089 7
10 S 203-D 10 2CDS 253 001 R0101 53090 3
13 S 203-D 13 2CDS 253 001 R0131 53091 0
16 S 203-D 16 2CDS 253 001 R0161 53092 7
20 S 203-D 20 2CDS 253 001 R0201 53093 4
25 S 203-D 25 2CDS 253 001 R0251 53094 1
32 S 203-D 32 2CDS 253 001 R0321 53095 8
40 S 203-D 40 2CDS 253 001 R0401 53096 5
50 S 203-D 50 2CDS 253 001 R0501 55205 9
63 S 203-D 63 2CDS 253 001 R0631 55206 6
0.5 S 204-D 0.5 2CDS 254 001 R0981 53112 2 0.500 2
1 S 204-D 1 2CDS 254 001 R0011 53113 9
1.6 S 204-D 1.6 2CDS 254 001 R0971 53114 6
2 S 204-D 2 2CDS 254 001 R0021 53115 3
3 S 204-D 3 2CDS 254 001 R0031 53116 0
4 S 204-D 4 2CDS 254 001 R0041 53117 7
6 S 204-D 6 2CDS 254 001 R0061 53118 4
8 S 204-D 8 2CDS 254 001 R0081 53119 1
10 S 204-D 10 2CDS 254 001 R0101 53120 7
13 S 204-D 13 2CDS 254 001 R0131 53121 4
16 S 204-D 16 2CDS 254 001 R0161 53122 1
20 S 204-D 20 2CDS 254 001 R0201 53123 8
25 S 204-D 25 2CDS 254 001 R0251 53129 0
32 S 204-D 32 2CDS 254 001 R0321 53130 6
40 S 204-D 40 2CDS 254 001 R0401 53131 3
50 S 204-D 50 2CDS 254 001 R0501 55209 7
63 S 204-D 63 2CDS 254 001 R0631 55210 3
D
SK 018 B 01
Selection table
Miniature circuit-breakers
S 200 series S 200-D
2
SK 019 B 01
SK 020 B 019
SK 030 B 01
3
4
suitable for flow-type heaters 12 kW suitable for flow-type heaters 21, 24 and 27 kW
suitable for flow-type heaters 18 kW UBmax 125 V ... with 2 poles connected in series
UBmax
440 V
60 V ...
UBmax
440 V
125 V ...
UBmax
440 V
UBmax
440 V
125 V ...
6000
3
41
System
pro M compact ®
BSelection table
1
No. of rated order details bbn price price w'ght pack.
poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
6S 201 M-B 6 2CDS 271 001 R0065 54942 4 0.125 10/40
10 S 201 M-B 10 2CDS 271 001 R0105 54943 1
13 S 201 M-B 13 2CDS 271 001 R0135 54944 8
16 S 201 M-B 16 2CDS 271 001 R0165 54945 5
20 S 201 M-B 20 2CDS 271 001 R0205 54946 2
25 S 201 M-B 25 2CDS 271 001 R0255 54947 9
32 S 201 M-B 32 2CDS 271 001 R0325 54948 6
40 S 201 M-B 40 2CDS 271 001 R0405 54949 3
50 S 201 M-B 50 2CDS 271 001 R0505 54381 1
63 S 201 M-B 63 2CDS 271 001 R0635 54382 8
6 S 202 M-B 6 2CDS 272 001 R0065 54958 5 0.250 5/20
10 S 202 M-B 10 2CDS 272 001 R0105 54959 2
13 S 202 M-B 13 2CDS 272 001 R0135 54960 8
16 S 202 M-B 16 2CDS 272 001 R0165 54961 5
20 S 202 M-B 20 2CDS 272 001 R0205 54962 2
25 S 202 M-B 25 2CDS 272 001 R0255 54963 9
32 S 202 M-B 32 2CDS 272 001 R0325 54964 6
40 S 202 M-B 40 2CDS 272 001 R0405 54965 3
50 S 202 M-B 50 2CDS 272 001 R0505 54385 9
63 S 202 M-B 63 2CDS 272 001 R0635 54386 6
6 S 203 M-B 6 2CDS 273 001 R0065 54966 0 0.375 3/12
10 S 203 M-B 10 2CDS 273 001 R0105 54967 7
13 S 203 M-B 13 2CDS 273 001 R0135 54968 4
16 S 203 M-B 16 2CDS 273 001 R0165 54969 1
20 S 203 M-B 20 2CDS 273 001 R0205 54970 7
25 S 203 M-B 25 2CDS 273 001 R0255 54971 4
32 S 203 M-B 32 2CDS 273 001 R0325 54972 1
40 S 203 M-B 40 2CDS 273 001 R0405 54973 8
50 S 203 M-B 50 2CDS 273 001 R0505 54387 3
63 S 203 M-B 63 2CDS 273 001 R0635 54388 0
6 S 204 M-B 6 2CDS 274 001 R0065 54982 0 0.500 2
10 S 204 M-B 10 2CDS 274 001 R0105 54983 7
13 S 204 M-B 13 2CDS 274 001 R0135 54984 4
16 S 204 M-B 16 2CDS 274 001 R0165 54985 1
20 S 204 M-B 20 2CDS 274 001 R0205 54986 8
25 S 204 M-B 25 2CDS 274 001 R0255 54987 5
32 S 204 M-B 32 2CDS 274 001 R0325 54988 2
40 S 204 M-B 40 2CDS 274 001 R0405 54989 9
50 S 204 M-B 50 2CDS 274 001 R0505 54391 0
63 S 204 M-B 63 2CDS 274 001 R0635 54392 7
2
3
Miniature circuit-breakers
S 200 series M
10000
3
4
S 200 M-B
SK 032 B 02
UBmax
440 V
60 V ...
UBmax
440 V
125 V ...
UBmax
440 V
125 V ...
UBmax
440 V
suitable for flow-type heaters 12 kW suitable for flow-type heaters 21, 24 and 27 kW
suitable for flow-type heaters 18 kW UBmax 125 V ... with 2 poles connected in series
42
System
pro M compact ®
No. of rated order details bbn price price w'ght pack.
poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
With disconnecting neutral NA
6 S 201 M-B 6 NA 2CDS 271 103 R0065 54950 9 0.250 50/40
10 S 201 M-B 10 NA 2CDS 271 103 R0105 54951 6
13 S 201 M-B 13 NA 2CDS 271 103 R0135 54952 3
16 S 201 M-B 16 NA 2CDS 271 103 R0165 54953 0
20 S 201 M-B 20 NA 2CDS 271 103 R0205 54954 7
25 S 201 M-B 25 NA 2CDS 271 103 R0255 54955 4
32 S 201 M-B 32 NA 2CDS 271 103 R0325 54956 1
40 S 201 M-B 40 NA 2CDS 271 103 R0405 54957 8
50 S 201 M-B 50 NA 2CDS 271 103 R0505 54383 5
63 S 201 M-B 63 NA 2CDS 271 103 R0635 54384 2
6 S 203 M-B 6 NA 2CDS 273 103 R0065 54974 5 0.500 2/20
10 S 203 M-B 10 NA 2CDS 273 103 R0105 54975 2
13 S 203 M-B 13 NA 2CDS 273 103 R0135 54976 9
16 S 203 M-B 16 NA 2CDS 273 103 R0165 54977 6
20 S 203 M-B 20 NA 2CDS 273 103 R0205 54978 3
25 S 203 M-B 25 NA 2CDS 273 103 R0255 54979 0
32 S 203 M-B 32 NA 2CDS 273 103 R0325 54980 6
40 S 203 M-B 40 NA 2CDS 273 103 R0405 54981 3
50 S 203 M-B 50 NA 2CDS 273 103 R0505 54389 7
63 S 203 M-B 63 NA 2CDS 273 103 R0635 54390 3 0.580
Miniature circuit-breakers
S 200 series M
BSelection table
1
+
NA
3
+
NA
S 200 M-B
SK 032 B 02
UBmax
440 V
60 V ...
UBmax
440 V
suitable for flow-type heaters 12 kW suitable for flow-type heaters 21, 24 and 27 kW
suitable for flow-type heaters 18 kW
10000
3
43
System
pro M compact ®
1
No. of rated order details bbn price price w'ght pack.
poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
0.5 S 201 M-C 0.5 2CDS 271 001 R0984 54990 5 0.125 10/40
1 S 201 M-C 1 2CDS 271 001 R0014 54992 9
1.6 S 201 M-C 1.6 2CDS 271 001 R0974 54991 2
2 S 201 M-C 2 2CDS 271 001 R0024 54993 6
3 S 201 M-C 3 2CDS 271 001 R0034 54994 3
4 S 201 M-C 4 2CDS 271 001 R0044 54995 0
6 S 201 M-C 6 2CDS 271 001 R0064 54996 7
8 S 201 M-C 8 2CDS 271 001 R0084 54997 4
10 S 201 M-C 10 2CDS 271 001 R0104 54998 1
13 S 201 M-C 13 2CDS 271 001 R0134 54999 8
16 S 201 M-C 16 2CDS 271 001 R0164 55000 0
20 S 201 M-C 20 2CDS 271 001 R0204 55001 7
25 S 201 M-C 25 2CDS 271 001 R0254 55002 4
32 S 201 M-C 32 2CDS 271 001 R0324 55003 1
40 S 201 M-C 40 2CDS 271 001 R0404 55004 8
50 S 201 M-C 50 2CDS 271 001 R0504 54393 4
63 S 201 M-C 63 2CDS 271 001 R0634 54394 1
0.5 S 202 M-C 0.5 2CDS 272 001 R0984 55020 8 0.250 5/20
1 S 202 M-C 1 2CDS 272 001 R0014 55022 2
1.6 S 202 M-C 1.6 2CDS 272 001 R0974 55021 5
2 S 202 M-C 2 2CDS 272 001 R0024 55023 9
3 S 202 M-C 3 2CDS 272 001 R0034 55024 6
4 S 202 M-C 4 2CDS 272 001 R0044 55025 3
6 S 202 M-C 6 2CDS 272 001 R0064 55026 0
8 S 202 M-C 8 2CDS 272 001 R0084 55027 7
10 S 202 M-C 10 2CDS 272 001 R0104 55028 4
13 S 202 M-C 13 2CDS 272 001 R0134 55029 1
16 S 202 M-C 16 2CDS 272 001 R0164 55030 7
20 S 202 M-C 20 2CDS 272 001 R0204 55031 4
25 S 202 M-C 25 2CDS 272 001 R0254 55032 1
32 S 202 M-C 32 2CDS 272 001 R0324 55033 8
40 S 202 M-C 40 2CDS 272 001 R0404 55034 5
50 S 202 M-C 50 2CDS 272 001 R0504 54397 2
63 S 202 M-C 63 2CDS 272 001 R0634 54398 9
0.5 S 203 M-C 0.5 2CDS 273 001 R0984 55035 2 0.375 3/12
1 S 203 M-C 1 2CDS 273 001 R0014 55037 6
1.6 S 203 M-C 1.6 2CDS 273 001 R0974 55036 9
2 S 203 M-C 2 2CDS 273 001 R0024 55038 3
3 S 203 M-C 3 2CDS 273 001 R0034 55039 0
4 S 203 M-C 4 2CDS 273 001 R0044 55040 6
6 S 203 M-C 6 2CDS 273 001 R0064 55041 3
8 S 203 M-C 8 2CDS 273 001 R0084 55042 0
10 S 203 M-C 10 2CDS 273 001 R0104 55043 7
13 S 203 M-C 13 2CDS 273 001 R0134 55044 4
16 S 203 M-C 16 2CDS 273 001 R0164 55045 1
20 S 203 M-C 20 2CDS 273 001 R0204 55046 8
25 S 203 M-C 25 2CDS 273 001 R0254 55047 5
32 S 203 M-C 32 2CDS 273 001 R0324 55048 2
40 S 203 M-C 40 2CDS 273 001 R0404 55049 9
50 S 203 M-C 50 2CDS 273 001 R0504 54399 6
63 S 203 M-C 63 2CDS 273 001 R0634 54400 9
0.5 S 204 M-C 0.5 2CDS 274 001 R0984 55065 9 0.500 2
1 S 204 M-C 1 2CDS 274 001 R0014 55067 3
1.6 S 204 M-C 1.6 2CDS 274 001 R0974 55066 6
2 S 204 M-C 2 2CDS 274 001 R0024 55068 0
3 S 204 M-C 3 2CDS 274 001 R0034 55069 7
4 S 204 M-C 4 2CDS 274 001 R0044 55070 3
6 S 204 M-C 6 2CDS 274 001 R0064 55071 0
8 S 204 M-C 8 2CDS 274 001 R0084 55072 7
10 S 204 M-C 10 2CDS 274 001 R0104 55073 4
13 S 204 M-C 13 2CDS 274 001 R0134 55074 1
16 S 204 M-C 16 2CDS 274 001 R0164 55075 8
20 S 204 M-C 20 2CDS 274 001 R0204 55076 5
25 S 204 M-C 25 2CDS 274 001 R0254 55077 2
32 S 204 M-C 32 2CDS 274 001 R0324 55078 9
40 S 204 M-C 40 2CDS 274 001 R0404 55079 6
50 S 204 M-C 50 2CDS 274 001 R0504 54403 0
63 S 204 M-C 63 2CDS 274 001 R0634 54404 7
CSelection table
Miniature circuit-breakers
S 200 series M S 200 M-C
2
3
4
SK 045 B 02 SK 044 B 02
SK 046 B 02
suitable for flow-type heaters 12 kW suitable for flow-type heaters 21, 24 and 27 kW
suitable for flow-type heaters 18 kW UBmax 125 V ... with 2 poles connected in series
UBmax
440 V
60 V ...
UBmax
440 V
125 V ...
UBmax
440 V
125 V ...
UBmax
440 V
10000
3
44
System
pro M compact ®
No. of rated order details bbn price price w'ght pack.
poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
With disconnecting neutral NA
0.5 S 201 M-C 0.5 NA 2CDS 271 103 R0984 55005 5 0.250 5
1 S 201 M-C 1 NA 2CDS 271 103 R0014 55007 9
1.6 S 201 M-C 1.6 NA 2CDS 271 103 R0974 55006 2
2 S 201 M-C 2 NA 2CDS 271 103 R0024 55008 6
3 S 201 M-C 3 NA 2CDS 271 103 R0034 55009 3
4 S 201 M-C 4 NA 2CDS 271 103 R0044 55010 9
6 S 201 M-C 6 NA 2CDS 271 103 R0064 55011 6
8 S 201 M-C 8 NA 2CDS 271 103 R0084 55012 3
10 S 201 M-C 10 NA 2CDS 271 103 R0104 55013 0
13 S 201 M-C 13 NA 2CDS 271 103 R0134 55014 7
16 S 201 M-C 16 NA 2CDS 271 103 R0164 55015 4
20 S 201 M-C 20 NA 2CDS 271 103 R0204 55016 1
25 S 201 M-C 25 NA 2CDS 271 103 R0254 55017 8
32 S 201 M-C 32 NA 2CDS 271 103 R0324 55018 5
40 S 201 M-C 40 NA 2CDS 271 103 R0404 55019 2
50 S 201 M-C 50 NA 2CDS 271 103 R0504 54395 8 0.290
63 S 201 M-C 63 NA 2CDS 271 103 R0634 54396 5
0.5 S 203 M-C 0.5 NA 2CDS 273 103 R0984 55051 2 0.500 2
1 S 203 M-C 1 NA 2CDS 273 103 R0014 55052 9
1.6 S 203 M-C 1.6 NA 2CDS 273 103 R0974 55050 5
2 S 203 M-C 2 NA 2CDS 273 103 R0024 55053 6
3 S 203 M-C 3 NA 2CDS 273 103 R0034 55054 3
4 S 203 M-C 4 NA 2CDS 273 103 R0044 55055 0
6 S 203 M-C 6 NA 2CDS 273 103 R0064 55056 7
8 S 203 M-C 8 NA 2CDS 273 103 R0084 55057 4
10 S 203 M-C 10 NA 2CDS 273 103 R0104 55058 1
13 S 203 M-C 13 NA 2CDS 273 103 R0134 55059 8
16 S 203 M-C 16 NA 2CDS 273 103 R0164 55060 4
20 S 203 M-C 20 NA 2CDS 273 103 R0204 55061 1
25 S 203 M-C 25 NA 2CDS 273 103 R0254 55062 8
32 S 203 M-C 32 NA 2CDS 273 103 R0324 55063 5
40 S 203 M-C 40 NA 2CDS 273 103 R0404 55064 2
50 S 203 M-C 50 NA 2CDS 273 103 R0504 54401 6 0.580
63 S 203 M-C 63 NA 2CDS 273 103 R0634 54402 3
Miniature circuit-breakers
S 200 series M
CSelection table
1
+
NA
3
+
NA
S 200 M-C
SK 032 B 02
UBmax
440 V
60 V ...
UBmax
440 V
suitable for flow-type heaters 12 kW suitable for flow-type heaters 21, 24 and 27 kW
suitable for flow-type heaters 18 kW
10000
3
Attention:
S 200 M, B and C
with integrated auxiliary contact
on request.
Description order details bbn price price w'ght pack.
40 16779 1 piece group 1 pc. unit
type code order code EAN kg pc.
Signalcontact/Auxiliary switch (universal)
Retrofittable to the right side of MCB’s, RCB’s and Shunt trip’s
1 change over S 2C-S/H6R 2CDS 200 922 R0001 56381 9 0.04 1
Auxiliary contact
Retrofittable to the right side of MCB’s
1 change over S 2C-H6R 2CDS 200 912 R0001 56382 6 0.04 1
Shunt trip
AC/DC 12 … 60 V S 2C-A1 2CDS 200 909 R0001 57099 2 0.15 1
AC 110 … 415 V und
DC 110 … 250 V S 2C-A2 2CDS 200 909 R0002 57100 5
Undervoltage release (in preparation)
DC 12 V S 2C-UA 12 2CDS 200 911 R0001 57101 2 0.09 1
AC/DC 24 V S 2C-UA 24 2CDS 200 911 R0002 57102 9
AC/DC 48 V S 2C-UA 48 2CDS 200 911 R0003 57103 6
AC/DC 110 V S 2C-UA 110 2CDS 200 911 R0004 57104 3
AC/DC 220 V S 2C-UA 220 2CDS 200 911 R0005 57105 0
AC 380 V S 2C-UA 380 2CDS 200 911 R0006 57106 7
System
pro M compact ®
Supplementary devices
MCB’s
Range S 200/S 200 M
SK 011 B 02
SK 209 B 02
SC-S/H6R
S 2C-A
51
System
pro M compact ®
Areas of application DIN VDE… Required F 200 F 200 F 172 F220
sensitivity F 660 F 690 FS 200 F 804
InmA F 670
In apartments 32 A
Socket-outlets up to 20 A
Outdoor lightning
installations
0100 – 739 10…30
0100 – 470 10…30
0100 – 714 10…30
F 200 F 172
F 660 FS 200
F 670
Fire protection in
high-risk or
high-danger areas 0100 – 482 10 u. 30
F 200 F 200 F 172
F 660 F 690 FS 200
F 670
Rooms with bath tub
or shower
Swimming pools
0100 – 701 10…30
0100 – 702 10…30
F 200 F 172
F 660 FS 200
F 670
Construction sites
Socket-outlet circuits
up to 32 A and other
socket-outlet circuits
0100 – 704 10…30
BG F&E 300…500
F 200 F 200 F 172 F 220
F 660 F 690 FS 200 F 804
F 670
Type B
Agricultural and
horticultural properties,
General socket-outlet
circuits
300…500
0100 – 705
10…30
F 200 F 200 F 172
F 660 F 690 FS 200
F 670 F 270
P 270
Feed points for caravans
Camp sites 0100 – 708 10…30
F 200 F 172
F 660 FS 200
F 670
Berths
Socket-outlets 0100 – 721 10…30
F 200 F 172
F 660 FS 200
F 670
Temporary buildings,
carny carriages and
caravans, Feed points
0100 – 722 30 and 300
Medical rooms
Group 1
Group 2 a
Group 2 b
at In 32 A
0100 – 710 10…30
10…30
300
F 200 F 200 F 172 F 220
F 660 F 690 FS 200 F 804
F 670
Type B
Equipment of power
installations with electronic
items Ib type A,
test for type B
0160
DIN EN 4kVA 10…30
50 178 > 4kVA 300
Photovoltaics
0100 – 712 E 30
EnBW
F 220
F 802
Type B
Operating areas subject to fire hazards… VdS 2033: 2002 – 02
300 mA
S
F 200 F 200 F 172
F 660 F 690 FS 200
F 670
F 200 F 200 F 172 F 220
F 660 F 690 FS 200 F 804
F 670
Type B
RCCBs and RCBOs
and their fields of applications
52
System
pro M compact ®
ABB STOTZ-KONTAKT GmbH
P.O. Box 10 16 80, 69006 Heidelberg, Germany
Eppelheimer Straße 82, 69123 Heidelberg, Germany
Telephone: +49 (0) 62 21 701- 0
Fax: +49 (0) 62 21 701-723
www.abb.de/stotz-kontakt
Pub. No. 2CDC 002 001 D0203
Approvals and certifications
by classification societies
MCB’s and RCB’s
Type Approvals Ship classification associatons
Sign of
comformity
BD 6 
Code SEV DEMKO NEMKO SEMKO EL. CSA KEMA ÖVE CEBEC UTE VDE BV GL LRS DNV
Inspect.
Valid for CH DK N S SF CDN USA NL A B F D F D GB N
277/480 V~
S 200, B, C
1 – 4 pole  
S 200 M
1 – 4 pole 
F 200 - 16/25/
40 – 0.01/
0.03/0.1/
0.3/0.5
F 200 A, AC, S
2/4 pole  
16…63 A
0.01…0.5 A
FS 201 B
6…40/0,03 A  
C 16/0,03
approved
submitted for aproval/planed to be submitted
Approved variants on request
Approval not required
Back-up protection usually required.
For details contact your importer and/or inspector.