Timers - Multifunction E3ZM20 ENYA series 7 Functions 7 time ranges Wide input range 2 change over contacts Width 35mm Installation design Technical data 1. Functions The function has to be set before connecting the relay to the supply voltage. E ON delay R OFF delay Ws Single shot leading edge with control input Wa Single shot trailing edge with control input Es ON delay with control input Wu Single shot leading edge voltage controlled Bp Flasher pause first 2. Time ranges Time range Adjustment range 1s 50ms 1s 10s 500ms 10s 1min 3s 1min 10min 30s 10min 1h 3min 1h 10h 30min 10h 100h 5h 100h 7. Control input Input not potential free: terminals A1-B1 Loadable: yes Max. line length: 10m Trigger level (sensitivity): automatic adaption to supply voltage Min. control pulse length: DC 50ms / AC 100ms 3. Indicators Green LED U/t ON: indication of supply voltage Green LED U/t flashes: indication of time period Yellow LED R ON/OFF: indication of relay output 4. Mechanical design Self-extinguishing plastic housing, IP rating IP40 Mounted on DIN-rail TS 35 according to EN 60715 Mounting position: any Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminal capacity: 1 x 0.5 to 2.5mm with/without multicore cable end 1 x 4mm without multicore cable end 2 x 0.5 to 1.5mm with/without multicore cable end 2 x 2.5mm flexible without multicore cable end 5. Input circuit Supply voltage: Terminals: Tolerance: Rated consumption: Rated frequency: Duty cycle: Reset time: Residual ripple for DC: Drop-out voltage: Overvoltage category: Rated surge voltage: 6. Output circuit 2 potential free change over contacts Rated voltage: 250V AC Switching capacity: 2000VA (8A / 250V) Fusing: 8A fast acting Mechanical life: 20 x 106 operations Electrical life: 2 x 105 operations at 1000VA resistive load Switching frequency: max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1) Overvoltage category: III (in accordance with IEC 60664-1) Rated surge voltage: 4kV 8. Accuracy Base accuracy: Adjusting accuracy: Repetition accuracy: Voltage influence: Temperature influence: 1% of maximum scale value <5% of maximum scale value <0.5% or 5ms 0.01% / C 9. Ambient conditions Ambient temperature: Storage temperature: Transport temperature: Relative humidity: Pollution degree: -25 to +55C -25 to +70C -25 to +70C 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) 2, if built in 3 (in accordance with IEC 60664-1) 10. Weight Single packing: 106g 12 to 240V AC/DC A1(+)-A2 -10% to +10% 6VA (2W) AC 48 to 63Hz 100% 100ms 10% >30% of minimum rated supply voltage III (in accordance with IEC 60664-1) 4kV www.tele-online.com E3ZM20 Functions ON delay (E) When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied. ON delay with control input (Es) The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When teh control contact S is closed, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired , the interval already expired is erased and is restarted with the next cycle. U U LED U/t LED U/t S R