2Specifications are subject to change without notice (30.04.03)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
G 3430 1149, G 3430 2249, G 3430 4443
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230 230 VAC ± 15% (IEC 60038)
115 115 VAC ± 15% (IEC 60038)
024 24 VAC ± 15%
Frequency 45 to 65 Hz
Voltage interruption ≤40 ms
Rated operational power
G 3430 1149 024/115/230 Typ. 3.5 VA
G 3430 2249 024/115/230 Typ. 4.5 VA
G 3430 4443 024/115/230 Typ. 3.5 VA
Power dissipation
G 3430 1149 024/115/230 ≤6.5 W
G 3430 2249 024/115/230 ≤8 W
G 3430 4443 024/115/230 ≤8 W
Rated impulse withstand
voltage 230 4 kV
115 2.5 kV
024 800 V
Dielectric voltage
Supply - Dupline®≥4 kVAC (rms)
Supply - Outputs ≥4 kVAC (rms)
Power supply DC types
Overvoltage cat. III (IEC 60664)
Operational voltage
through term. 21 & 22 800
10 to 30 VDC (ripple included)
824
15 to 30 VDC (ripple included)
Ripple ≤3 V
Reverse-polarity protection Yes
Rated operational current
G 3430 1149 800 ≤150 mA
G 3430 2249 824 ≤150 mA
G 3430 4443 824 ≤100 mA
Power dissipation
G 3430 1149 800 ≤5.5 W
G 3430 2249 824 ≤5.5 W
G 3430 4443 824 ≤6 W
Inrush current ≤1 A
Rated impulse withstand
voltage 800 V
Dielectric voltage
Supply - Dupline ≥200 VAC (rms)
Supply - Outputs ≥4 kVAC (rms)
General Specifications
Output OFF delay
Upon loss of Dupline carrier 20 ms
Power ON delay Typ. 2 s
Power OFF delay ≤1 s
Indication for
Supply ON LED, green
Output ON LED, red (one per output)
Dupline®carrier LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions
Material
(see Technical informations) H4-housing
Weight
G 3430 1149, G 3430 2249 250 g
G 3430 4443 300 g
Mode of Operation
1-channel receiver with
change-over contact output
The output is coded by
means of the code program-
mer GAP 1605.
The output is normally OFF.
When a transmitter coded to
the selected channel is acti-
vated, the output turns on
and remains on until the
respective channel becomes
deactivated. The default set-
ting is such that upon loss of
Dupline®carrier the output
goes off.
2-channel receiver with two
change-over contact out-
puts
Each output may be coded
individually by means of the
code programmer GAP 1605.
The outputs are normally off.
When a transmitter coded to
the selected channel is ac-
tivated, the output turns on
and remains on until the re-
spective channel becomes
deactivated. The default set-
ting of the module is such
that upon loss of Dupline®
carrier all outputs go off.
4-channel receiver with
four normally open contact
outputs
Each output may be coded
individually by means of the
code programmer GAP 1605.
The default setting of the
module is such that upon
loss of Dupline®carrier all
outputs go off.
For changing the default set-
ting, please refer to the data-
sheet on GAP 1605.
Operation Diagram
Dupline®carrier
Transmission on channel 1
Output 1
Transmission on channel 2
Power supply
Output 2