Product data sheet
20 31 020 0102
Current Sensor HCM 200A-0-20-CCA-T
Current Sensor HCM 200A-0-20-CCA-T
Image is for illustration purposes only. Please refer to product description.
Part number 20 31 020 0102
Specification Current Sensor HCM 200A-0-20-CCA-T
HARTING eCatalogue https://b2b.harting.com/20310200102
Identification
Series HCM
Element Current sensor
Sensor technology Hall-Effekt
Closed loop
Features
Hall effect compensated current sensor
Measurable currents: AC, DC, pulsed, mixed ...
High accuracy over the entire measuring range
Galvanic insulation between primary and secondary current
Switchboard mounting
Housing material and potting mass have a flammability rating UL 94 V-0
Applications: frequency converters, electrical drives, switched mode power
suppplies, UPS
Version
Field of application Industrial version
Termination Spring clamp termination
Pack contents Counter connector included
Technical characteristics
IPN Nominal primary current 200A
IPM Primary current, measuring range 0 ... ±300 A
RM Measuring resistance
@ IPM max, UC max, TA max
5 ... 58 Ω For other primary currents see diagram.
ISN Nominal secondary current 100mA
KN Turns ratio 1 : 2000
UC Power supply ±12 ... ±15 V ±5 %
Page1/4 | Creation date2020-07-21 | Please note that the data specified here were taken as extracts from the online catalogue. Please refer to
the user documentation for the complete and up-to-date information and data. Please also note that the user is responsible for validating functionality,
conformity with applicable laws and directives, as well as for the electrical safety in the particular application.
HARTING Electric GmbH & Co. KG | Wilhelm-Harting-Straße 1 | 32339 Espelkamp | Germany
Phone +49 5772 47-97100 | electric@HARTING.com | www.HARTING.com