FieldIT Data Sheet SS/264XC_2 2600T Series Pressure Transmitters Model 264DC Differential/Gauge Model 264HC Gauge Model 264NC Absolute with flanged direct mount seal Base accuracy : 0.075% Span limits - 0.54 to 16000kPa; 2.14inH2O to 2320psi - 1.1 to 16000kPa abs; 8mmHg to 2320psia Reliable sensing system coupled with very latest digital technologies Comprehensive sensor choice - optimize in-use total performance and stability 5-year stability Flexible configuration facilities - provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform Multiple protocol availability - provides integration with HART(R), PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities Broad selection of variants, options, fill fluids and wetted materials - allows total flexibility maximizing cost-effective aspect, also providing applications with critical process media at extended temperature range PED compliance to sound engineering practice (SEP) ABB 2600T Series Engineered solutions for all applications 2600T Pressure Transmitters Model 264DC, 264HC, 264NC SS/264XC_2 General Description Model 264DC and 264HC/NC detailed in this data sheet apply for those transmitters which include on high pressure measuring side, a direct mount seal which is integral to the transducer by a short capillary connection inside a protective rigid tube. This construction forms a standalone single assembly suitable to be mounted to the process by the seal mounting facilities. By properly selecting the high and low pressure side variant in the ordering codes model 264DC can be in the following versions : a) one direct mount seal and one flange for process connection, 1/4in NPT direct or 1/2in NPT through adapter; this allows also to connect the other leg (wet or dry) for differential measurement. A proper filter is supplied as standard when 1/4in NPT connection is selected, in order to plug the unused entry, leaving it vented for gauge measurement with reference to atmosphere. b) one direct mount seal and one remote seal with capillary; the two seals allow again a differential measurement and must be selected of same type/size. Model 264HC and 264NC have the direct mount seal on the positive side, respectively with the reference at atmospheric or vacuum pressure, for gauge or absolute measurements. Allowed types of direct mount seal are those mainly used for chemical application: - flush diaphragm flange mounted seal - extended diaphragm flange mounted seal These are suitable also for other process applications including food and sanitary, using FDA approved filling, which are defined as food fills and are Generally Recognized As Safe (GRAS) by the US Food and Drug Administration (FDA). Refer to seal data sheet for all data and details relevant to seal element. The following table list the types of standard seal which can be mounted with 264DC/HC/NC transmitters (the mnemonic is used as reference in the compatibility table). Seal type Size Mnemonic Flanged flush diaphragm 2in / DN50 3-4in / DN80-100 P2 P3 Flanged extended diaphragm 2in / DN50 3in / DN80 4in / DN100 E2 E3 P3 All following specification data apply for identical characteristics of the two seals when the transmitter has the remote seal in addition to the direct mount one. Functional Specifications Range and span limits Sensor Code E F G H M P Q S 16kPa 160mbar 64inH2O 40kPa 400mbar 160inH2O 65kPa 650mbar 260inH2O 160kPa 1600mbar 642inH2O 600kPa 6bar 87psi 2400kPa 24bar 348psi 8000kPa 80bar 1160psi Lower Range Limit 264DC 264DC Direct mount Direct mount differential gauge -16kPa -16kPa -160mbar -160mbar -64inH2O -64inH2O -40kPa -40kPa -400mbar -400mbar -160inH2O -160inH2O -65kPa -65kPa -650mbar -650mbar -260inH2O -260inH2O -160kPa 0.07kPa abs () -1600mbar 0.7mbar abs () -642inH2O 0.5mmHg () -600kPa 0.07kPa abs () -6bar 0.7mbar abs () -87psi 0.5mmHg () -2400kPa 0.07kPa abs () -24bar 0.7mbar abs () -348psi 0.5mmHg () -8000kPa 0.07kPa abs () -80bar 0.7mbar abs () -1160psi 0.5mmHg () 16000kPa 160bar 2320psi -16000kPa -160bar -2320psi Upper Range Limit (URL) 0.07kPa abs () 0.7mbar abs () 0.5mmHg () (LRL) 264HC/NC Direct mount gauge/absolute Minimum span 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 0.54kPa 5.4mbar 2.14inH2O 0.67kPa 6.7mbar 2.67inH2O 1.1kPa 11mbar 4.35inH2O 2.67kPa 26.7mbar 10.7inH2O 10kPa 0.1bar 1.45psi 40kPa 0.4bar 5.8psi 134kPa 1.34bar 19.4psi 0.07kPa abs () 0.7mbar abs () 0.5mmHg () 267kPa 2.67bar 38.7psi Compatibility (allowed seal for 264DC) Direct mount and Direct mount one remote seal seal only (max length in m.) P2 (*), P3 E3 (*) P3 (3) E3 (2) (*) P2, P3 E2 (*), E3 P2 (2) (*), P3 (5) E3 (3) P2, P3 E2 (*), E3 P2 (2) (*), P3 (5) E3 (3) P2, P3 E2, E3 P2 (5), P3 (8) E2 (4), E3 (6) P2, P3 E2, E3 P2 (8), P3 (8) E2 (6), E3 (8) P2, P3 E2, E3 P2 (8), P3 (8) E2 (6), E3 (8) P2, P3 E2, E3 P2 (8), P3 (8) E2 (6), E3 (8) P2, P3 E2, E3 P2 (8), P3 (8) E2 (6), E3 (8) The combinations sensor code/seal type marked (*) modify the base accuracy rating and static pressure effect; refer to performance specifications. ALL AVAILABLE SEALS FOR DIRECT MOUNT ARE SUITABLE FOR LISTED RANGES OF MODELS 264HC/NC WITHOUT LIMITATION. () Double the value with inert filling 2 2600T Pressure Transmitters Model 264DC, 264HC, 264NC Span limits Maximum span = URL (can be further adjusted up to URL (TD = 0.5) for differential models, within the range limits) IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. Zero suppression and elevation Zero and span can be adjusted to any value within the range limits detailed in the table as long as: - calibrated span minimum span Damping Selectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s. This is in addition to sensor response time Turn on time Operation within specification in less than 1s with minimum damping. SS/264XC_2 Operative limits Temperature limits C (F) : Ambient (is the operating temperature) Model 264DC Filling Sensors Sensor E F to S Silicone oil -40 and +85 -25 and +85 DC 200TM (-40 and +185) (-13 and +185) -20 and +85 -10 and +85 Inert GaldenTM (-4 and +185) (+14 and +185) -20 and +85 -10 and +85 Inert HalocarbonTM (-4 and +185) (+14 and +185) Models 264HC/NC Sensors G to S -40 and +85 (-40 and +185) -20 and +85 (-4 and +185) -20 and +85 (-4 and +185) Lower ambient limit for LCD indicators: -20C (-4F) Upper ambient limit for LCD indicators: +70C (+158F) Note : For Hazardous Atmosphere applications see the temperature range specified on the certificate/approval relevant to the aimed type of protection Insulation resistance > 100M at 1000VDC (terminals to earth) Process Lower limit (low pressure side 264DC only) - refer to lower ambient limits; -20C (-4F) for Viton gasket Upper limit (low pressure side 264DC only) - Silicone oil: 121C (250F) (1) - Inert fluid: 100C (212F) (2) (1) 100C (212F) for application below atmospheric pressure (2) 65C (150F) for application below atmospheric pressure The following table show characteristics of fill fluids when used in transmitters with direct mount seal on high pressure side. OPERATING CONDITIONS FILL FLUIDS (APPLICATION) Tmax Pmin Tmax Tmin @ Pabs>of mbar abs @ P min (psia) Silicone oil-DC200TM 200 (390) 0.7 160 -40 (General purpose) @ 35mbar (0.01) (320) (-40) Silicone oil-AN140TM 250 (480) 0.7 250 -5 (High temperature)) @ 0.7mbar (0.01) (480) (+23) Silicone Polymer-SylthermXLTTM100 (212) 2 20 -100 (Low temperature) @ 110mbar (0.03) (68) (-148) Vegetable oil-Neobee M-20TM 200 (390) 130 150 -18 (Food-Sanitary) FDA @ 1bar (1.9) (300) (0) Glycerin Water (70%) 93 (200) 1000 93 -7 (Food-Sanitary) FDA @ 1bar (14.5) (200) (+20) Mineral oil-MARCOL 82TM 200 (390) 33 40 -40 (Food-Sanitary) FDA @ 200mbar (0.5) (104) (-40) Inert - GaldenTM 160 (320) 0.7 65 -18 (Oxygen Service) @ 1bar (0.01) (150) (0) Inert - HalocarbonTM4.2 180 (356) 4 70 -20 (Oxygen Service) @ 400mbar (0.06) (158) (-4) ABB fill 250 (480) 0.7 160 -10 (Paints and specials) @ 35mbar (0.01) (320) (+14) Storage Lower limit: -50C (-58F); -40C (-40F) for LCD indicators Upper limit: +85C (+185F) 3 2600T Pressure Transmitters Model 264DC, 264HC, 264NC SS/264XC_2 Pressure limits Shock resistance (according to IEC 60068-2-27) Overpressure limits (without damage to the transmitter) 0.067kPa abs, 0.67mbar abs, 0.01psia (double with inert filling) to transmitter sensor limit or flange rating of seal, whichever is less: - 16MPa, 160bar, 2320psi for all sensor codes of model 264DC - 21MPa, 210bar, 3045psi for all sensor codes of models 264HC/NC - 2MPa, 20bar, 290psi for ANSI CL 150 flange 50g Duration: 11ms Wet and dust-laden atmospheres The transmitter is dust and sand tight and protected against immersion effects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or by NEMA to 4X or by JIS to C0920. Hazardous atmospheres - 5MPa, 50bar, 725psi for ANSI CL 300 flange - 10MPa, 100bar, 1450psi for ANSI CL600 flange - 16MPa, 160bar, 2320psi for ANSI CL 900 flange - 1.6MPa, 16bar, 230psi for DIN PN 16 flange - 4MPa, 40bar, 580psi for DIN PN 40 flange - 6.4MPa, 64bar, 930psi for DIN PN 64 flange - 10MPa, 100bar, 1450psi for DIN PN 100 flange - 16MPa, 160bar, 2320psi for DIN PN 160 flange Static pressure Transmitters for differential pressure model 264DC operates within specifications between the following limits: - 1.3kPa abs,13mbar abs, 0.2psia and 16MPa, 160bar, 2320psi or flange rating of seal as above, whichever is less - 0.067kPa abs, 0.67mbar abs, 0.01psia and 16MPa,160bar, 2320psi or flange rating of seal as above, whichever is less, using a second seal remote on negative pressure side. Proof pressure The transmitter can be exposed without leaking to line pressure of up to: - 28MPa, 280bar, 4000psi for model 264DC - 40MPa, 400bar, 5900psi for model 264HC/NC or two times the flange rating of seal, whichever is less. Meet ANSI/ISA-S 82.03 hydrostatic test requirements and SAMA PMC 27.1. Environmental limits Electromagnetic compatibility (EMC) Comply with EN 61000-6-3 for emission and EN 61000-6-2 for immunity requirements and test; Radiated electromagnetic immunity level: (according to IEC 1000-4-3, EN61000-4-3) 30V/m Conducted electromagnetic immunity level : (according to IEC 1000-4-6, EN 61000-4-6) 30V Surge immunity level (with surge protector): (according to IEC 1000-4-5 EN 61000-4-5) 4kV Fast transient (Burst) immunity level: (according to IEC 1000-4-4 EN 61000-4-4) 4kV Pressure equipment directive (PED) Comply with 97/23/EEC following sound engineering practice (SEP). Humidity Relative humidity: up to 100% annual average Condensing, icing: admissible Vibration resistance Accelerations up to 2g at frequency up to 1000Hz (according to IEC 60068-2-26) 4 Acceleration: With or without output meter/integral display - INTRINSIC SAFETY/EUROPE: ATEX/ZELM approval II 1 GD T50C, EEx ia IIC T6 (-40C Ta +40C) T95C, EEx ia IIC T4 (-40C Ta +85C) - TYPE "N"/EUROPE: ATEX/ZELM type examination (for HART) II 3 GD T50C, EEx nL IIC T6 (-40C Ta +40C) T95C, EEx nL IIC T4 (-40C Ta +85C) (FOUNDATION Fieldbus/PROFIBUS PA): pending - FLAMEPROOF/EUROPE: ATEX/CESI approval II 1/2 GD T85C, EEx d IIC T6 (-40C Ta +75C) - CANADIAN STANDARDS ASSOCIATION and FACTORY MUTUAL: - Explosionproof: Class I, Div. 1, Groups A, B, C, D - Dust ignitionproof : Class II, Div. 1, Groups E, F, G - Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2 - Nonincendive: Class I, Div. 2, Groups A, B, C, D - Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G AEx ia IIC T6/T4, Zone 0 (FM) - STANDARDS AUSTRALIA (SAA): pending TS/WCA Approval Ex d IIC T5 (Tamb +85C)/T6 (Tamb +70C) Class 1 Zone 1; Ex ia IIC T4 (Tamb +85C) /T5 (Tamb +55C) T6 Class 1 Zone 0 2600T Pressure Transmitters Model 264DC, 264HC, 264NC SS/264XC_2 Electrical Characteristics and Options Optional surge protection HART digital communication and 4 to 20mA output Power Supply Up to 4kV - voltage 1.2 s rise time / 50 s delay time to half value - current 8 s rise time / 20 s delay time to half value The transmitter operates from 10.5 to 42VDC with no load and is protected against reverse polarity connection (additional load allows operations over 42VDC). For EEx ia and other intrinsically safe approval power supply must not exceed 30VDC. Output signal Two-wire 4 to 20mA, user-selectable for linear or square root output, power of 3/2 or 5/2, 5th order or two 2nd order switching point selectable programmable polynomial output. HART(R) communication provides digital process variable (%, mA or engineering units) superimposed on 4 to 20mA signal, with protocol based on Bell 202 FSK standard. Ripple 20mV max on a 250 load as per HART specifications MINIMUM OPERATING VOLTAGES Output current limits (to NAMUR standard) Overload condition no link on output indicator plugs with CoMeter indicator and HART communication - Lower limit: 3.8mA - Upper limit: 20.5mA with ProMeter output indicator Transmitter failure mode (to NAMUR standard) with optional surge protection The output signal can be user-selected to a value of 3.7 or 22mA on gross transmitter failure condition, detected by self-diagnostics. with optional output analog indicator In case of CPU failure the output is driven <3.7mA or >22mA. with integral display (volts) 10.5 10.7 12.3 12.5 13.3 15.3 Load limitations 4 to 20mA and HART total loop resistance : Supply voltage - min. operating voltage (VDC) --------------------------------------- 22.5 A minimum of 250 is required for HART communication. R(k) = Optional indicators Output meter CoMeter and Prometer LCD : 5-digit (99999 counts) programmable with 7.6mm. high (3in), 7-segment numeric characters plus sign and digital point for digital indication of output value in percentage, current or engineer unit; 10-segment bargraph display (10% per segment) for analog indication of output in percentage; 7-digit with 6mm. high (2.3in), 14-segment alphanumeric characters, for engineer units and configuration display Analog : 36mm (1.4in) scale on 90. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of analog output in percentage. User-definable matrix display mode with HART communication: - process variable in pressure unit or - output signal as percentage, current or engineering units Display also indicates in/out transfer function, static pressure, sensor temperature and diagnostic messages and provides configuration facilities. 5 2600T Pressure Transmitters Model 264DC, 264HC, 264NC SS/264XC_2 PROFIBUS PA output FOUNDATION Fieldbus output Device type Device type Pressure transmitter compliant to Profiles 3.0 Class A & B; ident. number 052B HEX. Power supply The transmitter operates from 10.5 to 32VDC , polarity independent. For EEx ia approval power supply must not exceed 17.5VDC. Intrinsic safety installation according to FISCO model. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Output interface PROFIBUS PA communication according to Profibus DP50170 Part 2/ DIN 19245 part 1-3. Output update time 25ms Function blocks 2 analog input, 1 transducer, 1 physical Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode On gross transmitter failure condition, detected by self-diagnostics, the output signal can be driven to defined conditions, selectable by the user as safe, last valid or calculated value. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. LINK MASTER DEVICE Link Active Scheduler (LAS) capability implemented. Power supply The transmitter operates from 9 to 32VDC, polarity independent. For EEx ia approval power supply must not exceed 24VDC (entity certification) or 17.5VDC (FISCO certification), according to FF-816. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Function blocks/execution period 2 standard Analog Input blocks/25ms max (each) 1 standard PID block/70ms max. Additional blocks 1 standard Resource block, 1 custom Pressure with calibration transducer block. Number of link objects 25 Number of VCRs 24 Output interface FOUNDATION fieldbus digital communication protocol to standard H1, compliant to specification V. 1.5; FF registration number IT019000. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode The output signal is "frozen" to the last valid value on gross transmitter failure condition, detected by self-diagnostics which also indicate a BAD conditions. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. 6 2600T Pressure Transmitters Model 264DC, 264HC, 264NC Performance specifications Stated at reference condition to IEC 60770 ambient temperature of 20C (68F), relative humidity of 65%, atmospheric pressure of 1013hPa (1013mbar), mounting position with vertical diaphragm and zero based range for transmitter with isolating diaphragms in AISI 316 L ss or Hastelloy and silicone oil fill and HART digital trim values equal to 4-20mA span end points, in linear mode. Unless otherwise specified, errors are quoted as % of span. Some performance data are affected by the actual turndown (TD) as ratio between Upper Range Limit (URL) and calibrated span. IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. Accuracy rating % of calibrated span, including combined effects of terminal based linearity, hysteresis and repeatability. For fieldbus versions SPAN refer to analog input function block outscale range Using direct mount seal sizes