10
Product offering
DCNH
600VDC
Minimum Breaking Capacity = 2In ; Maximum Breaking Capacity = 50 KA
Maximum operating
voltage Rated Current Size Cat. Number Packaging
600VDC @ L/R = 2ms
50A 00 DC00GS60V050PV 3
63A 00 DC00GS60V063PV 3
80A 00 DC00GS60V080PV 3
100A 00 DC00GS60V100PV 3
600VDC @ L/R = 2ms
125A 1 DC1GS60V125PV 3
160A 1 DC1GS60V160PV 3
200A 1 DC1GS60V200PV 3
250A 1 DC1GS60V250PV 3
280A 1 DC1GS60V280PV 3
Cat. Number Watt Losses @ 0.7In & 20°C
DC00GS60V050PV 4.35
DC00GS60V063PV 4.85
DC00GS60V080PV 5.65
DC00GS60V100PV 6.35
DC1GS60V125PV 9.0
DC1GS60V160PV 10
DC1GS60V200PV 11
Size A B C H L M N P R T
00 29.5 47.5 59.5 15 79 13.1 13.1 43.4 50 35
00 1.16” 1.87” 2.34” 0.59” 3.11” 0.52” 0.52” 1.71” 1.97” 1.38”
139.5 52.5 64.5 20 135 32.1 32.1 43.4 68 40
11.56” 2.07” 2.54” 0.79” 5.32” 1.26” 1.26” 1.71” 2.68” 1.57”
Drawing
HelioFuse
0.4
P/P0,7In
0.45 0.50.550.6 0.65 0.70.750.8I/In
0.9
1.0
1.0
1.1
1.1
1.2
1.2
010203040506070
P(T)/P(20)
Ta (°C)
Corrective factor for power losses vs. ambient temperature
0.20
0.40
0.60
0.80
1.00
1.20
1.40
Electrical characteristics
Ferraz ShawmutSolar solutions 11
Cat. Number Fuse size Nb of poles Packaging Model Udc maxi
operating
BB001RFS 00 1 3 IP2X Finger Safe
including cover
690V
BB11PPRFS 113 690V
Fuse bases
Remote signalling
system for fitting on
fuses equipped with
micro-switch support.
Accessories
Cat. Number Contact Qty of NO-NC separated circuits Packaging
MSNH2-B6PRES Mini = 20V 50mA • Maxi = 10A 1 3
MSNH2-B2PRES Mini = 20V 100mA • Maxi = 5A 1 3
Dimensions
(mm) A B C D E F G H I J K L M N O
Size 00 32 20 117 100 8 2 14 25 145 21.5 856 52 85 84
Size 1 60 32 209 176 10,5 30 20,5 25 250 35 M10 81 71 122,5 146