TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
1
Highlights & Features
Full corrosion resistant Aluminium chassis
Suitable for 24V system up to 40A
Built-in diagnostic monitoring for DC OK, Discharge and
Battery Fail by relay contacts
LED indicator for DC OK, Battery Fail, DC Input, Battery
Reverse Polarity and Battery Discharge
High MTBF > 500,000 hrs as per Telcordia SR-332
Wide operation temperature range from -20°C to +60°C
Conformal coat ing on PCBA to protect against chemical and
dust pollutant s
Safety Standards
CB Certified for worldwide use
Model Number : DRU-24V40ABN
Unit Weight: 0.60 kg
Dimensions (L x W x D): 121 x 50 x 117.3 mm
General Description
The DRU-24V40ABN CliQ II DC-UPS module is designed to support 24V system with up to 40A output and back up time of 4.5
minutes for 15AH battery capacity. It offers a wide input voltage from 24-28V and a wide operating temperature range from -20°C to
+60°C. This product comes with potential free contacts for battery management signals and LED indicator for battery status. The
rugged compact aluminium case is shock and vibration resistant according to IEC 60068-2.
Model Information
CliQ II DC-UPS Mod ul e
Model
Number
Input Voltage Range Output
V
oltage
Output Curr
ent
DRU-24V40ABN 24-28Vdc 24Vdc typ. (Depends on Vin) 40.0A Max
Model Number ing
DR U 24V
40A
B
N
DIN Rail DC-UPS Module Output Voltage Output Current CliQ II Series N - Metal Case,
without Class I, Div 2
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
2
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 24Vdc
Input Voltage Range 24-28Vdc
Input Current Charging Mode 2A ± 1A
Charging Time* < 3hr ± 1hr for battery 24V/15AH
Efficiency Charging Mode > 70.0%
Buffering Mode > 99.0%
*Charging time depends on the last state of discharge w.r.t. buffering time and load current.
Output Ratings / Characteris tic s
Output Voltage Range 23-28Vdc
Output Current 40.0A Max
Output Power 960W Max (24V, 40A)
Voltage Drop Between Input and Output Charging Mode 0V between DC input to load
Buffering Mode 0.1V between battery to load @ 40A load
Battery Input / Output Characteristics
Nominal Battery Voltage 24Vdc, SLA Sealed lead acid battery
2 x 12Vdc, SLA Sealed lead acid battery
Battery Voltage Range 23-28Vdc (continuously operating)
30Vdc Max (the maximum voltage that will not cause
damage to the unit)
14Vdc Min (the voltage level of battery to enable “BAT Fail”
function)
Battery Capacity 7.5AH/ 12AH/ 15AH
Battery Fuse
Auto 50A / 80V, FK3 (Littelfuse) or similar in the battery path.
The battery fuse protects the wires between the battery and
the unit.
Battery Charging Mode CC-mode (constant current) at 2A
End-of-Charge Voltage The unit always charge with fix input voltage value
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
3
Buffering Time
Output
Current
7.5AH
12AH
15AH
2.5A 6,500s 14,500s 19,000s
5A 3,000s 7,000s 9,000s
10A 1,200s 2,400s 3,200s
20A 400s 1,100s 1,500s
30A 120s 450s 600s
40A
25s
200s
280s
Mechanical
Case Cover / Chassis Aluminium
Dimensions (L x W x D) 121 x 50 x 117.3 mm
Unit Weight 0.60 kg
Cooling System Convection
Terminal Input / Output 4 Pi ns (Rated 600V/60A)
Signal 6 Pins (Rated 300V/27A)
Wire Input / Output AWG 12-6 (Load: 0-20A)
AWG 8-6 (Load 20-40A)
Signal
AWG 24-12
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 40dBA
Fig. 1 Buffering Time VS. Output Current
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
4
Environment
Surrounding Air Temperature
Operating -20°C to +60°C (full power)
Storage -40°C to +85°C
Operating Humidity
5 to 95% RH ( Non-Condensing)
Operating Altitude 0 to 3,000 Meters
Shock Test (Non-Operating) IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 ti me per direction, 2 times in total
Vibration (Non-Operating) IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
Pollution Degree 2
Protections
Overload / Overcurrent 42-52A , Lat ch-off Mode
Over Temperature < 90°C Surrounding Air Temperature inside the unit,
Latch-off Mode
Short Circuit (at system) Shutdown, Latch-off Mode
Input Polarity Protection* Yes (DC OK = open contact, LED Status = Orange)
Battery Polarity Protection* Yes (DC OK = open contact, LED Status = Orange)
Wrong Battery Voltage Protection Yes, 30Vdc Max (the maximum voltage that will not cause
damage to the unit)
Deep Discharge Protection Yes (23V ± 0.5V)**
Degree of Protection IP20
Protection Against Shock Class III
*If the orange status LED is on, this indicates a failure in the installation. In this case, do not turn on power supply while the battery is connected. Danger of explosion!
** The unit will stop operating when the battery voltage detected is less tha n 2 3V ± 0.5V
Reliability Data
MTBF > 500,000 hrs. as per Telcordia SR-332
Safety Standards / Directives
Electrical Equipment in Power Installations EN 50178 / IEC 62103
Electrical Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and
CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA
to CSA C22.2 No. 107.1-01 (F i le No. 1815 64)
CE In conformance with EMC Directive 2004/108/EC and Low
Voltage Directive 2006/95/EC
Material and Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolat i on Power Port to Housing 1.0KVac
Signal Port to Housing 1.0KVac
Power Port to Signal Port 1.0KVac
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
5
EMC
EMC / Emissions CISPR 22, EN 55022, EN 55011,
FCC Title 47: Class B
Component Power Supply for General Use EN 61204-3
Immunity to EN 55024, EN 61000-6-2
Electrostatic Discharge IEC 61000-4-2 Level 4 Crit eria A
1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field IEC 61000-4-3 Level 3 Criteria A1)
80MHz-1GHz, 10V/M, 80% modulation (1KHz)
1.4GHz-2GHz, 3V/M, 80% modulation (1KHz)
2GHz-2.7GHz, 1V/M, 80% modulation (1KHz)
Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A
1)
2kV (Input power ports)
Surge IEC 61000-4-5 Level 3 Criteria A1)
0.5kV (Input power ports)
Conducted IEC 61000-4-6 Level 3 Criteria A
1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A
1)
10A/Meter
1) Criteria A: Normal performance within the specification limits
Block Diagram
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
6
Device Description
1) Input / Output ter min al bloc k connector
2) Signal terminal block connector
3) LED display status
4) Universal mounting rail system
Dimensions
L x W x D: 121 x 50 x 117.3 mm
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
7
Engineering Data
De-rating
Assembly & Installation
The unit can be mounted on 35mm DIN rails in accordance with EN 60715. For Vertical Mounting, the device should be installed with
Input / Output terminal block on the bottom. For Horizontal Mounting, the device should be installed with Input / Output terminal block
on the left side.
Each device is delivered ready to install.
Mounting
Note
1. The unit may degrade, or be damaged, when
it is continuously used outside the shaded
region, refer to the graph shown in Fig. 2.
2. When the DC-UPS module is used with
power supply of different ratings, user must
follow power supply derating curve or
whichever is lower.
3. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 50mm above and below
the device as well as a lateral distance of
20mm (for Vertical Mounting) or 50mm (for
Horizontal Mounting)
with adjacent units
while the device is in operation .
4.
Depending on the surrounding air
temperature and output load delivered by the
power supply, the device can be very hot!
5. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com f or more detai ls.
Fig. 2 No power de-rating across the entire operating temperature range
(-20°C to +60°C)
Dismounting
Fig. 3.1 Mounting
Snap on the DIN rail as shown in Fig. 3.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom fr ont side for lockin g.
4. Shake the unit slightly to ensure that it is secured.
Fig. 3.2 Dismounting
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 3.2. Then slide the unit in the oppos ite dire ctio n,
release the latch and pull out the unit from the rail.
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
8
Safety Instruc ti ons
Vertical Mounting
When replacing batteries, only use the same type of batteries listed under the “Battery Input / Output Characteristics” section on
Page 2.
Proper disposal of batteries is required. Refer to the relevant local codes for disposal requirements.
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not
turned OFF, there is risk of explosion / severe damage.
If the orange status LED is on, this indicates a failure in the installation. In this case, do not turn on power supply while the battery
is connected. Danger of explosion!
To guarantee sufficient convection cooling, keep a distance of 50mm above and below the device as well as a lateral
distance of 20mm (for Vertical Mounting) or 50mm (for Horizontal Mounting) to other units.
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
The main power must be turned off before connecting or disconnecting wires t o the terminals!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
The unit is a built-in unit and must be installed in a cabinet or room (condensation free environment and indoor location) that is
relatively free of conductive contaminants.
Horizontal Mount ing
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
9
Functions
Relay Contacts Characteristics
Max Relay Contact Rating 24Vdc/Vac, 1.0A
DC BUS OK Relay Contact “DC OK” contact is closed when the DC input voltage is
within 24-28V (±10%) range or the b att ery volta ge is within
23-28V range
LED Indicator Green LED On
Charging Relay Contact DC OK” contact is closed when the unit is in charging mode
LED Indicator Green LED Flashing
Battery Discharge* Relay Contact “Discharging” contact is closed when the unit is in buffering
mode
LED Indicator Orange LED Flashing
Battery Fail Relay Contact
“BAT Fail” contact is closed when the battery fails to function
or battery voltage is less than 14V
LED Indicator Red LED On
Battery Reverse Polarity Relay Contact “DC OK” contact is opened when the battery is in reverse
polarity
LED Indicator Orange LED On
* With output current 3A to 40A.
Signals Wiring Diagram
DC-UPS Status
Relay Output Connector
LED Display
Status
Discharging
BAT Fail
DC OK
Battery Fully
Charged Open Open Close Green LED On
Battery Charging Open Open Close Green LED
Flashing
Battery Discharging*
(Buffering Mode) Close* Open Close Orange LED
Flashing
No Battery
Connected Open Close Open Red LED On
Output Shutdown Open Open Open No Light
*With output current 3A to 40A.
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
10
Charging Mod e Buffering Mode
Typical Application Notes
Fig. 4.1 Provide backup power during AC source interruption or failure
Fig. 4.2 Can be combined with redundancy module (DRR-40A)
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
11
Overload & Overc ur rent Protecti ons
When the output current exceeds the maximum specified output
current. The DC-UPS module will shut down and protect itself.
Normal operation of the module can be resumed upon removal of
fault.
Short Circuit Protection
The module is protected in case of short circuit at customer
system, in the event of short circuit the module will shut down and
protect itself. Normal operation can be resumed upon removal of
fault.
Overvoltage Protection
The DC-UPS module’s overvoltage protection will be activated
when DC input to the module exceeds the maximum specified
input voltage. The unit shall shutdown and return to normal state
when the OVP condition is removed.
Over Temperature Protection
In the event of a higher operating temperature at 100% load, the
power supply will run into OTP when the operating temperature is
beyond what is recommended in the de-rating graph. When
activated, the output voltage will shut down and remain in off
state until the temperature drops to its normal operating
temperature as recommended in the de-rating graph.
TECHNICAL DATASHEET
CliQ II DC-UPS Module
24V 40A
/ DRU-24V40ABN
All parameters are specified at 25°C amb ient unl es s otherwise indicat ed.
www.DeltaPSU.com (September 2014, Rev. 01)
12
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and ele ctr on ic equ ip ment”.
This product conforms to this standard.
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBs or circuit board.
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem
especially in highly conversing atmosphere.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Delta Electronics:
DRU-24V40ABN