Mechanical thermostats
Tested to ATEX 94/9/EC
Temperature monitoring
in explosion-endangered areas
Temperature switches with special equipment can also be used in
explosion risk areas Zone 1, 2 and 21, 22.
The following alternatives are possible:
1. Type of ignition protection Ex-d, Ex-e and Ex-t:
The thermostat with protection type "Flameproof Ex-d and Increased Saftey Ex-e" can be used in
hazardous areas of zone 1 and 2 for flammable gas mixtures. For use in dust atmospheres, the
protection is "prtected by enclosure Ex-t".
The thermostat may be used in hazardous areas of zones 21 and 22 for explosive dusts. In addition,
for the dust – explosion protect zone 20 on the sensor (device screwed into container walls, which
may occur in the interior permanent dust atmosphere).
The permissible values for switching voltage, switching capacity and ambient temperature please
refer to the detailed description of the Ex equipment, and the installation and operating instructions.
In addition, please note the general rules for the use and installation of equipment in hazardous
atmosphere.
Special circuits, as well as versions with adjustable switching differential or internal interlock
(reclosing lock) are not possible.
2. Ignition protection Ex-i
All thermostat with features for intrinsically safe circuits can be used in hazardous areas Zone 1 and
2 (Gas) and zones 21 and 22 (Dust). A circuit is considered to be "intrinsically safe" if the amount of
energy conveyed therein is not capable of generating an ignitable sparks. This thermostat can only
be operated in combination with a suitable isolating switching amplifier, which is approved for the
type Ex-i. Because of the low voltages and currents in intrinsically safe circuits, micro switches with
gold contacts are used for temperature monitors with automatic reset. FEMA thermostats for use in
intrinsically safe circuit are marked by blue terminals and cable entries. In addition, the thermostats
has been tested by a "notified body". The units get a serial number and the nameplate inform about
the ignition protection and registration number.
Isolating
amplifier
Ingniton protection for pressure monitoring in Zone 0 (20), 1 (21) and 2 (22)
Intrinsically safe Ex-i
(EN 60079-11:2012)
T…-513, …-563
Marking:
s 0035 II 2G Ex ia IIC T6 Gb
s 0035 II 2D Ex ia IIIC T80°C Db
ATEX approval for the complete
switching device
ATEX approval for isolating amplifiers
Thermostat with gold-plated contacts
Rated value without resistor combination
…-513 /…-563:
Ui: 24VDC
Ii: 100mA
Ci: 1nF
Li: 100µH
Thermostat will be installed in Ex-Zone.
The isolating amplifier must be installed
outside the Ex-Zone.
Marking, use in thermowell:
s 0035 II 2G Ex d e IIC T6 Gb
s 0035 II 1/2D Ex ta/tb IIIC T80°C Da/Db
Exception: EX-TRM…:
s 0035 II 2G Ex d e IIC T6 Gb
s 0035 II 2D Ex tb IIIC T80°C Db
ATEX approval for the complete switching device
Thermostat with a silver contact
Switching capacity:
max. 3 A, 250 VAC
min. 2 mA, 24 VDC
Thermostat can be installed within the Ex-Zone
Pressure-proof encapsulation Ex-d (EN60079-0:2009)
Enhanced safety Ex-e (EN60079-7:2007)
Protection via housing Ex-t (EN60079-31:2009)
Ex-T…