Du line®
Fieldbus Installationbus
Specifications are subject to change without notice (26.03.01) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description Ordering Key
Type: Dupline®
H8-housing
Master channel generator
Supply
Master Channel Generator
Type G 3890 0014
Programmable channel generator
Configuration based on Windows 95/98/NT software
Light control functions
Alarm monitoring
AnaLink set-point control
Rollerblind control
Real-time, timer and logic functions
Print-out of events with date and time tags
Alarms and events can be sent as SMS to GSM-phones
(Only version <3.00)
Controlling of functions via SMS from GSM-phones
(Only version <3.00)
H8-housing
For DIN-rail mounting (EN 50022)
AC or DC power supply
Modbus-RTU interface RS 232 (only version > 2.02)
Option for connecting two Dupline®Master Channel
Generator Networks (only version > 2.02)
Multiplex or normal mode
Programmable channel gen-
erator with built-in intelligent
functions for light control,
alarm monitoring, AnaLink
set-point control, rollerblind
control etc. Programming is
easily performed through
windows-based configuration
software. A specific function
with associated parameters
can be assigned to each
address and logic operations
can be used to link the func-
tions together. Surveillance
and control of functions can
be made via SMS from GSM-
phones by means of the
GSM8 modem.
Supply Ordering no.
115/230 VAC G 3890 0014 230
10 to 30 VDC G 3890 0014 800
Type Selection
Serial Port RS 232
9-pole female SUB-D
Pin assignment TxD Pin 2
RxD Pin 3
GND Pin 5
Dielectric voltage
Com.port - Dupline®2 kVAC (rms)
Parallel Port Centronic
25-pole female SUB-D
Pin assigment Strobe Pin 1
Data D0-D7 Pins 2-9
Busy Pin 11
Paper out Pin 12
GND Pins 18-25
Dielectric voltage
Com.port - Dupline®2 kVAC (rms)
Dupline®-Output Dupline®carrier
Output voltage 8.2 V
Current < 100 mA
Short-circuit protection Yes
Sequence time
32 channels 38.6 ms
128 channels 132.3 ms
Watchdog-Output 1 NPN transistor
Function Watchdog
Output voltage VDD 35 VDC
Output current 100 mA
Output voltage drop 2 V
Off-state leakage current 100 µA
Short-circuit protection None
Built-in protective diodes None
Dielectric voltage
Output - Dupline®4 kVAC (rms)
Output - Input 4 kVAC (rms)
Inductive loads External noise suppression
required
Input/Output Specifications
Supply Specifications
Power supply AC-Types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 24
jumper term. 22 & 23 230 VAC ± 15% (IEC 60038)
jumper term. 21 & 23
and term. 24 & 22 115 VAC ± 15% (IEC 60038)
Frequency 45 to 65 Hz
Rated operational power Typ. 7 VA/3 W
Rated impulse withstand
voltage 115/230 V 4 kV
Dielectric voltage
Supply - Dupline®4 kVAC (rms)
Supply - Output 4 kVAC (rms)
Supply - Input 4 kVAC (rms)
Supply - Com. ports 4 kVAC (rms)
Power supply DC-Types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 10-30 VDC
Reverse polarity protection Yes
Rated operational power 7 W
Inrush current 1 A
Rated impulse withstand volt. 800 V
Dielectric voltage
Supply - Dupline®500 V
Supply - Output 200 V
G 3890 0014 230
Du line®
Fieldbus Installationbus
2Specifications are subject to change without notice (26.03.01)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
G 3890 0014
Input Back-up supply
Function Real-time clock
Isolated in groups of 1 x 1
Input voltage range 4.5 to 9 V
Reverse polarity protection Yes
Rated operational current 10 to 100 µA
Input resistance > 47 k
Cable length < 0.5 m
Dielectric voltage
Input - Dupline® (230 V Version)
4 kVAC (rms)
Input - Dupline
®
(800 V Version)
500 V
Adjustment Time, Date, Year, Day
4 tactile pushbuttons
(Mode, Up, Down, Enter) RS 232 functions
LPT functions
Communication
LPT Centronic
For serial printer / DOS-
commands
RS232
Normal mode Download of configuration
Spec. mode Modbus-RTU protocol
(Short-cut pin 7 and pin 8)
Txd Pin 2
Rxd Pin 3
Gnd Pin 5
RTS Pin 7
CTS Pin 8
Input/Output Specifications (cont.)
Real-time clock
Accuracy
Better than ± 1 minute/month
Internal back-up time Typ. 120 hours
Unit parameter back-up time > 1 year
Power ON delay < 2.5 s
Indication for
Supply ON LED, green
ON Line LED, yellow
Busy LED, yellow
Fault LED, red
Time, date etc. 4-digit LCD display
red background light
Environment
Degree of protection IP 20
Pollution degree 3 (IEC 60664)
Operating temperature to +50°C (+32° to +122°F)
Storage temperature -2 to +85°C (-4° to +185°F)
Humidity (non-condensing) 20 to 80% RH
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information") H8-housing
Weight 540 g
General Specifications
Wiring Diagrams
Key Operation Diagram
Set-Up
[SEt]
Set
Time
[HrS]
Time
Format
[FOr]
Set
Date
[dAtE]
Display
Time of day
Show
date
Show
year
Show day
of the
week
Date
Format
[FOr]
Set
Day
[dAY]
Set
Year
[YEAr]
Main Setting Mode
Power supply
230 VAC Power supply
115 VAC
Centronic
RS 232
Backup
4.5-9 V
Watchdog NPN
Noise red.
G 3890 0014 800
Dupline®
S
Supply 10-30 VDC 7 W
+-
+-
1 2 3 4 5 6 7 8 9 10111213141516
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
0.1 A
35 V
Centronic
RS 232
Backup
4.5-9 V
Watchdog NPN
Noise red.
G 3890 0014 230
Dupline®
S
Supply
+-
1 2 3 4 5 6 7 8 9 10111213141516
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
0.1 A
35 V
Du
l
ine®
Fieldbus Installationbus
Specifications are subject to change without notice (26.03.01) 3
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
G 3890 0014
Mode of Operation
The G 3890 0014 master gener-
ator is a programmable channel
generator which is particularly
well suited for building automa-
tion applications like lighting
control, rollerblind control, tem-
perature control, and alarm-
monitoring. Through an easy-to-
use windows-based configura-
tion software, the unit can be
configured to perform real-time
control, logic and timer func-
tions, ISA, water, smoke and
Intruder alarm-monitoring and
Code/ Door lock armouring.
Print-outs of time-tagged user-
defined text in case of channel
output changes.
Keys
In the display mode, the four
front-keys are used to change
the display showing time, date,
day of the week, year or soft-
ware revision of the master gen-
erator (Press < enter >). The keys
are also used to set the time,
date, day of the week, year and
definition of operation and
parameters of the parallel ports.
Display
The back-lighted 4-digit LCD
display is used to show all the
relevant information that can be
changed by using the keys. If no
key is pressed for 2 minutes, the
display automatically shows the
actual time. In case of an Error
the display shows an Error code.
Back-up Terminals
In case of missing power the
internal calendar and clock are
supported by a super-capacitor.
Under normal ambient tempera-
ture this back-up will maintain
the correct date and time for
typically 5 days. If longer power
shutdowns can occur, an exter-
nal battery of 4.5 to 9 VDC may
be connected between terminal
35 (+) and terminal 36 (-).
Alarm Output Terminals
An open collector NPN-transistor
output with NC function signals
alarms and faults in the system.
Attention by the local personnel
is requested whenever this out-
put switches off. The display
and/or the LED´s gives an indi-
cation of the cause of problem.
Master Generator Configura-
tion
The master generator is as fac-
tory default configured to oper-
ate as a standard channel-gen-
erator without intelligent func-
tions. To obtain full utilisation of
the advanced features, the gen-
erator has to be configured.
For configuration, the delivered
software SW G 3890 0014 has
to be installed on a Win
95/98/NT based PC.
This software handles all config-
uration of the G 3890 0014 mas-
ter generator. The software ver-
sion must be consistent with the
firmware version of the Master
Generator. Press <Enter> on top
of the Master Generator to see
the version in the display.
Configuration is done entirely on
the PC, and when completed,
the set-up is downloaded into
the generator via the serial port.
(COM1 or COM2).
Two Dupline®networks*
Two channel generators can be
connected via communication
cable. Thereby addresses, i.e.
master commands, can be
transferred from one network to
the other by means of the matrix
mapping in the configuration
software. Entering "1" in the
desired Dupline®address per-
forms selection of the channel
status from the other Dupline®
network.
Modbus-RTU*
Modbus-RTU is implemented as
a function of a slave. The follow-
ing Modbus functions are sup-
ported: 01, 02, 03, 05, 06 and 16.
See: Modbus-RTU Memory
Mapping.
SMS**
Surveillance and control of
Dupline®channels can take
place by means of the SMS
option. The G38900014 module
can call up several GSM phones,
when an event or alarm appears,
and a GSM phone can change
the status of a Dupline®chan-
nel/function. The last option is
"Dial-in number" and password
protected.
* Rev. 2.02 or higher required
**Rev 3.xx or higher required
Pin Assignment RS 232 Cables
2
3
5
7
8
2
3
5
7
8
2
3
5
7
8
2
3
5
7
8
9-pin male
to controller #1
9-pin male
to controller 9-pin female
to PC
9-pin male
to Controller #2
5
9
1
6
Pin Signal
2 T x D
3 R x D
5 Signal Ground
7RTS
8 CTS
13
25
1
14
Pin Signal
1 Strobe
2-9 Do - D7
11 Busy
12 Paper out
18-25 GND
Two Dupline®Networks Cable
Configuration Cable
2
3
5
7
8
2
3
5
9-pin male
to controller 9-pin female
to PC
Modbus RTU Cable
2
3
5
7
8
Term 4
Term 5
Term 1
9-pin male
to controller GSM8
GSM modem Cable
Function Code 06
Preset single Register Data Word
Address MSB…HB LB…LSB
1000 B8…B1 A8…A1
1001 D8…D1 C8…C1
1007 P8…P1 O8…O1
Du
l
ine®
Fieldbus Installationbus
4Specifications are subject to change without notice (26.03.01)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Accessories
User manual MAN G3890 0014 ENG
GSM modem GSM8
For further information refer to "Accessories".
1 x Master Channel Generator G 3890 0014 ..
1 x User manual MAN G 3890 0014 ENG
1 x RS 232 cable RS 232-9 M/9 F
1 x Configuration software SW G 389XX14 version 3.00
Scope of Supply
Function Code 03
Read Multiple Registers Data Word
Address MSB…HB LB…LSB
0000 B8…B1 A8…A1
0001 D8…D1 C8…C1
0007 P8…P1 O8…O1
0100 Analink A1
0101 Analink A2
017F Analink P8
0200 #0 0..99 0..99 0..99 0..99
0202 #1 0..99 0..99 0..99 0..99
0204 #2 0..99 0..99 0..99 0..99
2FC #126 0..99 0..99 0..99 0..99
2FE #127 0..99 0..99 0..99 0..99
Modbus-RTU Memory Mapping
Function code 01
Read Output Table Dupline®Channel
Address
500 A1
501 A2
57F P8
Function code 02
Read Input Table Dupline®Channel
Address
600 A1
601 A2
67F P8
Function code 05
Set single Output Bit Dupline®Channel
Address
1500 A1
1501 A2
157F P8
Function Code 16
Preset Multiple Registers Data Word
Address MSB…HB LB…LSB
1000 B8…B1 A8…A1
1001 D8…D1 C8…C1
1007 P8…P1 O8…O1