Preface SIMATIC ET 200S distributed I/O IM151-1 COMPACT modules What do COMPACT modules offer? 1 ______________ SIMATIC ET 200S distributed I/O IM151-1 COMPACT modules Manual Configuration options of the COMPACT modules 2 ______________ IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) 3 ______________ 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) 4 ______________ 5 Parameters ______________ 6 Error and system messages ______________ Response times for the ET 200S 7 ______________ 03/2007 A5E01077635-01 Safety Guidelines Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Prescribed Usage Note the following: WARNING This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. Trademarks All names identified by (R) are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Automation and Drives Postfach 48 48 90327 NURNBERG GERMANY Ordernumber: A5E01077635-01 10/2007 Copyright (c) Siemens AG 2007. Technical data subject to change Preface Preface Purpose of the manual This manual supplements the ET 200S Distributed I/O System Operating Instructions. General functions for the ET 200S are described in the ET 200S Distributed I/O System Operating Instructions. The information in this document along with the operating instructions enables you to commission the ET 200S. Basic knowledge requirements To understand these operating instructions you should have general knowledge of automation engineering. Scope of the manual This manual applies to this ET 200S module. It describes the components that are valid at the time of publication. Recycling and disposal Thanks to the fact that it is low in contaminants, this ET 200S module is recyclable. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste. Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner The portal to our technical documentation for the various SIMATIC products and systems is available at: http://www.siemens.com/automation/simatic/portal The online catalog and ordering system are available at: http://www.siemens.com/automation/mall IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 3 Preface Training center We offer courses to help you get started with the ET 200S and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D 90327, Nuremberg, Germany. Phone: +49 (911) 895-3200. http://www.siemens.com/sitrain Technical Support You can reach technical support for all A&D projects using the support request web form: http://www.siemens.com/automation/support-request Phone: + 49 180 5050 222 Fax: + 49 180 5050 223 For more information about our technical support, refer to our Web site at http://www.siemens.de/automation/service Service & Support on the Internet In addition to our documentation services, you can also make use of our comprehensive online knowledge base on the Internet. http://www.siemens.com/automation/service&support There you will find: Our Newsletter, which constantly provides you with the latest information about your products. The right documentation for you using our Service & Support search engine. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs, spare parts. Lots more can be found on our "Services" pages. 4 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Table of contents Preface ...................................................................................................................................................... 3 1 What do COMPACT modules offer? .......................................................................................................... 7 2 Configuration options of the COMPACT modules...................................................................................... 9 3 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) ...................................................................... 11 4 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0)............................................... 19 5 Parameters .............................................................................................................................................. 29 6 7 5.1 Parameters for IM151-1 COMPACT............................................................................................29 5.2 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 Parameter description..................................................................................................................30 Enable startup for set <> actual configuration .............................................................................30 Analog-value format.....................................................................................................................30 Interference frequency suppression ............................................................................................30 Reference junction slot ................................................................................................................30 Reference junction input ..............................................................................................................31 Error and system messages .................................................................................................................... 33 6.1 Diagnostics using LED display.....................................................................................................33 6.2 Diagnostic messages of the electronic modules..........................................................................35 6.3 6.3.1 6.3.2 6.3.3 6.3.4 6.3.5 6.3.6 6.3.7 6.3.8 Diagnostics with STEP 7..............................................................................................................36 Diagnostics readout .....................................................................................................................36 Structure of the slave diagnostics ................................................................................................38 Station statuses 1 to 3 .................................................................................................................39 Master PROFIBUS address.........................................................................................................40 Identifier-related diagnostics ........................................................................................................41 Module status...............................................................................................................................42 Channel-specific diagnostics .......................................................................................................43 Incorrect module configurations of ET 200S on the PROFIBUS DP ...........................................44 Response times for the ET 200S ............................................................................................................. 45 Index........................................................................................................................................................ 47 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 5 Table of contents 6 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 What do COMPACT modules offer? 1 COMPACT modules combine the functions of an interface module with the functions of a digital electronic module. In combination with a terminal module TM-C and a terminating module, the IM151-1 COMPACT constitutes a complete slave. Characteristics of the COMPACT module The familiar ET 200S handling also applies to COMPACT modules (mounting, wiring, equipping and configuring). Also, an ET 200S configuration with only one COMPACT module must be connected to the right with the terminating module. The IM151-1 COMPACT can be expanded with up to 12 peripheral modules, with the exception of fail-safe modules. The expansion can be undertaken without additional power modules, if the maximum load in the final voltage groups is not exceeded. The peripheral modules are supplied via the backplane bus from the final voltage group. The total current may not exceed 5 A. The terminal module for COMPACT modules can be expanded with additional terminals for connecting additional potentials. This means that connection to 3 and 4 conductor technology is possible. IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 7 What do COMPACT modules offer? 8 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Configuration options of the COMPACT modules 2 Which COMPACT module matches your application: Table 2-1 Assignment of COMPACT modules and applications COMPACT modules IM151-1 COMPACT Applications * * * * * * * IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Connecting the PROFIBUS DP via the RS485 interface Operation as a DPV0 slave Direct data exchange Bus length of the ET 200S: not relevant Integrated peripherals: - 32DI: Digital inputs - 16DI/16DO: Digital inputs/outputs Number of additional modules: max. 12 Module types: all except fail-safe modules Transmission rates: 9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud, 1.5; 3; 6; 12 Mbit/s 9 Configuration options of the COMPACT modules 10 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 3 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Properties The COMPACT module IM151-1 COMPACT 32DI 24 V DC has the following features: It connects the ET 200S with PROFIBUS DP via the RS485 interface. The maximum parameter length is 218 bytes. The maximum address space is 100 bytes for inputs and 100 bytes for outputs. Operation as a DPV0 slave A maximum of 12 additional modules can be operated on the IM151-1 COMPACT 32DI 24 V DC. The maximum bus length is not relevant. Integrated peripherals: 32 digital inputs Nominal input voltage 24 VDC Diagnostics: Short circuit of the encoder supply. Diagnostics: No load voltage Suitable for switches and proximity switches (BEROs) Terminal assignment for PROFIBUS DP The following table shows the terminal assignment of the IM151-1 COMPACT 32DI 24 V DC for PROFIBUS DP: Table 3-1 Terminal assignment of the IM151-1 COMPACT 32DI 24 V DC for PROFIBUS DP View Signal name 1 - Name - 2 - - 3 RxD/TxD-P Data line B 4 RTS Request To Send 5 M5V2 Data reference potential (station) 6 P5V2 Supply plus (station) 7 - - 8 RxD/TxD-N Data line A 9 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 11 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Terminal assignment of TM-C120x for IM151-1 COMPACT 32DI 24 V DC Terminal Assignment Description 1L+ L+ 24 VDC 2L+ L+ 24 VDC (for loop through) 1M M Chassis ground 2M M Ground (for loop through) 1, 2 L+ Load voltage 24 VDC for voltage group 0 3, 4 M 5, 6, 9, 10, 13, 14, 17, 18, 25, 26, 29, 30, 33, 34, 37, 38 DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12, DI13, DI14, DI15 DIn: Input signal, Channel n 7, 8, 11, 12, 15, 16, 19, 20, 27, 28, 31, 32, 35, 36, 39, 40 L+ Sensor power supply 24 VDC 41, 42 L+ Load voltage 24 VDC for voltage group 2 43, 44 M 45, 46, 49, 50, 53, 54, 57, 58, 65, 66, 69, 70, 73, 74, 77, 78 DI16, DI17, DI18, DI19, DI20, DI21, DI22, DI23, DI24, DI25, DI26, DI27, DI28, DI29, DI30, DI31 DIn: Input signal, Channel n 47, 48, 51, 52, 55, 56, 59, 60, 67, 68, 71, 72, 75, 76, 79, 80 L+ Sensor power supply 24 VDC 21, 22, 23, 24, 61, 62, 63, 64 n. c. Not connected (max. 30 V DC can be connected) Supply voltage Digital inputs 12 Ground for voltage group 0 Ground for voltage group 2 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Usable terminal modules Usable terminal modules for IM151-1 COMPACT 32DI (6ES7151-1CA00-1BL0) TM-C120C (6ES7193-4DL00-0AA0) Spring terminal TM-C120S (6ES7193-4DL10-0AA0) Screw-type terminal 6DPSOHFRQQHFWLRQ / ZLUH ', / 0 / 0 6DPSOHFRQQHFWLRQ ZLUH / / 0 0 ', / 0 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 13 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Usable terminal modules for IM151-1 COMPACT 32DI (6ES7151-1CA00-1BL0) 6DPSOHFRQQHFWLRQ ZLUH / / 0 0 ', / 0 3( $8; 14 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Block diagram 6) %) 21 (OHFWURQLFV (OHFWULFDO 352),%86'3 LVRODWLRQ FRQQHFWLRQ $ $ % % 352),%86DGGUHVV ,QWHUQDO SRZHU VXSSO\ // 00 (76EDFNSODQHEXVFRQQHFWLRQ %DFNSODQHEXV ,QSXW HOHFWURQLFV 5HYHUVHSRODULW\ SURWHFWLRQ /RDGYROWDJH PRQLWRULQJ 6KRUW FLUFXLW GHWHFWLRQ 9ROWDJHJURXS (QFRGHUVXSSO\ 0 / ,QSXW HOHFWURQLFV 5HYHUVHSRODULW\ SURWHFWLRQ /RDGYROWDJH PRQLWRULQJ 6KRUW FLUFXLW GHWHFWLRQ 3 9ROWDJHJURXS (QFRGHUVXSSO\ 0 9 3 Figure 3-1 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 / Block diagram for IM151-1 COMPACT 32DI 24 V DC 15 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Technical data for IM151-1 COMPACT 32DI DC24V (6ES7151-1CA00-1BL0) Dimensions and weight Dimension B (mm) 120 Weight Approx. 230 g Module-specific data Data transmission rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud, 1.5; 3; 6; 12 Mbit/s Bus protocol PROFIBUS DP Interface RS 485 SYNC capability yes FREEZE capability Yes Manufacturer ID 8201H Direct data exchange yes Cycle synchronization No Parameter length 23 bytes Address space * Interface module 100-byte inputs / 100-byte outputs * I/Os 4-byte inputs Option handling No I&M data No Firmware update No Max. output current of the PROFIBUS DP interface (5, 6) 80 mA Power dissipation of the module Typically 3 W Voltages, currents, potentials Rated supply voltage of the electronic components (1L+) 24 VDC * Incorrect polarity protection Yes * Power failure bypass No Max. current carrying capacity 5 A, for I/O modules connected after the IM151-1 COMPACT Galvanic isolation 16 * Between the backplane bus and electronic components No * Between the PROFIBUS DP and electronic components yes * Between the supply voltage and electronic components No Permitted potential difference (to the rail) 75 VDC / 60 VAC Insulation test voltage 500 VDC Current consumption from rated supply voltage (1L+) Approx. 100 mA IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Status, interrupts, diagnostics Interrupts None Diagnostics functions (for PROFIBUS DP) yes Diagnostics functions (for internal periphery) module granular (A peripheral fault will not cause the station to fail.) * * Group error PROFIBUS DP bus monitoring Red "SF" LED red "BF" LED * Monitoring of the power supply voltage of the electronics Green "ON" LED Integral I/O Number of inputs 32DI Cable lengths * Unshielded * Shielded max. 600 m max. 1000 m Integrated periphery (voltages, currents, potentials) Rated load voltage * 24 VDC Incorrect polarity protection yes Galvanic isolation * Between the channels No * Between the channels and backplane bus yes Permissible potential difference * Between the different circuits Insulation test voltage 75 VDC / 60 VAC 500 VDC Current consumption * from load voltage dependent on the sensor Integrated peripherals (status, interrupts, diagnostics) Status display green LED per channel Diagnostics functions yes * Short-circuit at sensor supply * No load voltage Sensor supply outputs Output voltage * With load min. L+ (-0.5 V) Output current * Rated value 500 mA * Permitted range 0 to 500 mA Short-circuit protection IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 yes, electronic 1 17 IM151 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0) Data for selecting a sensor Input voltage * Rated value 24 VDC * For signal "1" 15 to 30 V * For signal "0" -30 to 5 V Input current * At signal "1" Typically 3 mA (at 24 V) Input delay * At "0" to "1" * At "1" to "0" Typically 3 ms (1.2 to 4.8 ms) Input characteristic curve According to IEC 61131, type 1 Connection of two-wire BEROs Supported * 1 18 Typically 3 ms (1.2 to 4.8 ms) Permitted bias current max. 1.5 mA per voltage group IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) 4 Properties The COMPACT-module M151-1 COMPACT 16DI/16DO 24 VDC/0.5 A has the following features: It connects the ET 200S with PROFIBUS DP via the RS485 interface. The maximum parameter length is 244 bytes. The maximum address space is 100 bytes for inputs and 100 bytes for outputs. Operation as a DPV0 slave A maximum of 12 additional modules can be operated on the M151-1 COMPACT 16DI/16DO 24 VDC/0.5 A. The maximum bus length is not relevant. Integrated peripherals: 16 digital inputs - Nominal input voltage 24 VDC - Diagnostics: Short circuit on the encoder supply - Diagnostics: No load voltage - Suitable for switches and proximity switches (BEROs) 16 digital outputs - Output current 0.5 A per output - Rated load voltage 24 VDC - Diagnostics: No load voltage - Suitable for solenoid valves, DC contactors, and indicator lights - Substitute value behavior configurable IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 19 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Terminal assignment for PROFIBUS DP The following table shows the terminal assignment of the IM151-1 COMPACT 16DI/16DO 24 VDC/0.5 A for PROFIBUS DP: Table 4-1 Terminal assignment of the IM151-1 COMPACT 16DI/16DO 24 VDC/0.5 A for PROFIBUS DP View Signal name Name 1 - - 2 - - 3 RxD/TxD-P Data line B 4 RTS Request To Send 5 M5V2 Data reference potential (station) 6 P5V2 Supply plus (station) 7 - - 8 RxD/TxD-N Data line A 9 Terminal assignment of TM-C120x for IM151-1 COMPACT 16DI/16DO 24 VDC/0.5 A Terminal Assignment Description 1L+ L+ 24 VDC 2L+ L+ 24 VDC (for loop through) 1M M Chassis ground 2M M Ground (for loop through) 1, 2 L+ Load voltage 24 VDC for voltage group 0 3, 4 M 5, 6, 9, 10, 13, 14, 17, 18, 25, 26, 29, 30, 33, 34, 37, 38 DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12, DI13, DI14, DI15 DIn: Input signal, Channel n 7, 8, 11, 12, 15, 16, 19, 20, 27, 28, 31, 32, 35, 36, 39, 40 L+ Sensor power supply 24 V DC 21, 22, 23, 24 n. c. Not connected (max. 30 V DC can be connected) Supply voltage Digital inputs 20 Ground for voltage group 0 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Terminal Digital outputs Assignment Description 41, 42 L+ Load voltage 24 VDC for voltage group 2 61, 62 L+ 43, 44 M 63, 64 M 45, 46, 49, 50, 53, 54, 57, 58, 65, 66, 69, 70, 73, 74, 77, 78 DO0, DO1, DO2, DO3, DO4, DO5, DO6, DO7, DO8, DO9, DO10, DO11, DO12, DO13, DO14, DO15 DOn: Output signal, Channel n 47, 48, 51, 52, 55, 56, 59, 60, 67, 68, 71, 72, 75, 76, 79, 80 M Chassis ground Load voltage 24 VDC for voltage group 3 Ground for voltage group 2 Ground for voltage group 3 Usable terminal modules Usable terminal modules for IM151-1 COMPACT 16DI/16DO (6ES7151-1CA00-3BL0) TM-C120C (6ES7193-4DL00-0AA0) Spring terminal TM-C120S (6ES193-4DL10-0AA0) Screw-type terminal :LULQJH[DPSOHV ZLUH / / 0 0 ', IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 ', '2 / 0 '2 21 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Usable terminal modules for IM151-1 COMPACT 16DI/16DO (6ES7151-1CA00-3BL0) ', '2 :LULQJH[DPSOHV ZLUH / / 0 0 ', ', '2 / 0 0 / '2 :LULQJH[DPSOHV ZLUH / / 0 0 22 ', '2 / 0 0 / 3( $8; 3( $8; IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Block diagram 6) %) 21 (OHFWURQLFV (OHFWULFDO 352),%86'3 LVRODWLRQ FRQQHFWLRQ $ $ % % 352),%86DGGUHVV ,QWHUQDO SRZHU VXSSO\ // 00 (76EDFNSODQHEXVFRQQHFWLRQ %DFNSODQHEXV ,QSXW HOHFWURQLFV 5HYHUVHSRODULW\ SURWHFWLRQ /RDGYROWDJH PRQLWRULQJ 6KRUW FLUFXLW GHWHFWLRQ 9ROWDJHJURXS (QFRGHUVXSSO\ 0 / /RDGYROWDJH PRQLWRULQJ 9ROWDJHJURXS 0 9 / /RDGYROWDJH PRQLWRULQJ 3 3 Figure 4-1 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 9ROWDJHJURXS 0 / 9 Block diagram for IM151-1 COMPACT 16DI/16DO 24 VDC/0.5 A 23 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Technical data for IM151-1 COMPACT 16DI/16DO DC24V/0.5 A (6ES7151-1CA00-3BL0) Dimensions and weight Dimension B (mm) 120 Weight Approx. 230 g Module-specific data Data transmission rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud, 1.5; 3; 6; 12 Mbit/s Bus protocol PROFIBUS DP Interface RS 485 SYNC capability Yes FREEZE capability Yes Manufacturer ID 8200H Direct data exchange yes Cycle synchronization No Parameter length 26 bytes Address space * Interface module 100-byte inputs / 100-byte outputs * I/Os 2-byte inputs/2-byte outputs Option handling No I&M data No Firmware update No Max. output current of the PROFIBUS DP interface (5, 6) 80 mA Power dissipation of the module Typically 3 W Voltages, currents, potentials Rated supply voltage of the electronic components (1L+) 24 V DC * Reverse polarity protection Yes * Power failure bypass No Max. current carrying capacity 5 A, for I/O modules connected after the IM151-1 COMPACT Galvanic isolation 24 * Between the backplane bus and electronic components No * Between the PROFIBUS DP and electronic components yes * Between the supply voltage and electronic components No Permitted potential difference (to the rail) 75 VDC / 60 VAC Insulation test voltage 500 VDC Current consumption from rated supply voltage (1L+) Approx. 100 mA IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Status, interrupts, diagnostics Interrupts None Diagnostics functions (for PROFIBUS DP) yes Diagnostics functions (for internal periphery) module granular (A peripheral fault will not cause the station to fail.) * * Group error PROFIBUS DP bus monitoring Red "SF" LED red "BF" LED * Monitoring of the power supply voltage of the electronics Green "ON" LED Integral I/O Number of inputs / outputs 16 / 16 Cable lengths * Unshielded * Shielded max. 600 m max. 1000 m Integrated peripherals - inputs (voltages, currents, potentials) Rated load voltage * 24 V DC Reverse polarity protection Yes Electrical isolation * Between the channels No * Between the channels and backplane bus yes Permissible potential difference * Between the different circuits Insulation test voltage 75 VDC / 60 VAC 500 V DC Current consumption * from load voltage Dependent on the sensor Integrated peripherals - inputs (status, interrupts, diagnostics) Status display green LED per channel Diagnostics functions yes * Short-circuit at sensor supply * No load voltage Sensor supply outputs Output voltage * With load min. L+ (-0.5 V) Output current * Rated value 500 mA * Permitted range 0 to 500 mA Short-circuit protection IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 yes, electronic 1 25 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Data for selecting a sensor Input voltage * Rated value 24 VDC * For signal "1" 15 to 30 V * For signal "0" -30 to 5 V Input current * At signal "1" Typically 3 mA (at 24 V) Input delay * At "0" to "1" * At "1" to "0" Typically 3 ms (1.2 to 4.8 ms) Typically 3 ms (1.2 to 4.8 ms) Input characteristic curve According to IEC 61131, type 1 Connection of 2-wire BEROs Supported * Permitted bias current max. 1.5 mA Integrated peripherals - outputs (voltages, currents, potentials) Rated load voltage L+ * Reverse polarity protection 24 V DC yes Total current for outputs (per voltage group) * Horizontal assembly - up to 30 C - Up to 40 C - up to 60 C * Vertical assembly - up to 55 C max. 4 A max. 3 A max. 2 A Max. 2 A Galvanic isolation * Between the channels Yes, each in groups of up to 8 * Between the channels and backplane bus yes Permissible potential difference * Between the different circuits Insulation tested 75 VDC / 60 VAC 500 V DC Current consumption * From load voltage L+ (no load) max. 5 mA per voltage group Integrated peripherals - outputs (status, interrupts, diagnostics) 26 Status display green LED per channel Diagnostics functions yes * No load voltage IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) Data for selecting an actuator Output voltage * At signal "1" min. L+ (-0.8 V) Output current * At signal "1" - Rated value - Permitted range 0.5 A 7 mA to 0.6 A * With signal "0" (residual current) max. 0.5 mA Output delay (for resistive load) * At "0" to "1" max. 500 s * At "1" to "0" max. 1.3 ms Load resistor range 48 to 4 k Lamp load max. 5 W Connecting two outputs in parallel * For redundant triggering of a load yes (per voltage group) * To increase performance No Control of a digital input yes Switch rate * For resistive load 100 Hz * on inductive load 2 Hz * For lamp load 10 Hz Limitation (internal) of the voltage induced on circuit interruption Typically L+ (-55 V to -60 V) Reverse-voltage proof yes, when using the same load voltage as on the voltage group infeed Short-circuit protection of the output Yes2 * Threshold on 1 per voltage group 2 per channel IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 0.7 to 1.9 A 27 16DI/16DO 24 V DC/0.5 A IM151-1 COMPACT (6ES7151-1CA00-3BL0) 28 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 5 Parameters 5.1 Parameters for IM151-1 COMPACT Table 5-1 Parameters for IM151-1 COMPACT IM151-1 COMPACT Value range Default setting Applicability Operation at set <> actual configuration disable/enable Disable Slave station Identifier-related diagnostics disable/enable enable Slave station Module status disable/enable enable Slave station Channel-specific diagnostics disable/enable enable Slave station Analog-value format 1 SIMATIC S7/ SIMATIC S5 S7 Slave station Interference frequency suppression 50 Hz / 60 Hz 50 Hz Slave station Reference junction slot None /2 to 13 None Slave station Reference junction input RTD on channel 0/ RTD on channel 1 0 Slave station disable/enable Disable Voltage group Diagnostics: No load voltage for disable/enable voltage groups Disable Voltage group disable/enable Disable Voltage group Diagnostics: No load voltage for disable/enable voltage groups Disable Voltage group Response to CPU/master STOP Switch substitution value / hold last value Substitute a value Module Substitute value 2 "0"/ "1" "0" Channel Integrated periphery 32DI Diagnostics: Short circuit at voltage groups encoder supply Integrated periphery 16DI/16DO Diagnostics: Short-circuit sensor supply voltage group 0 1 The parameter only exists when configuring via the GSD file. If the supply voltage to the COMPACT module fails, the digital outputs will not supply a substitute value. Output value = 0 2 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 29 Parameters 5.2 Parameter description 5.2 Parameter description 5.2.1 Enable startup for set <> actual configuration When this parameter is enabled, and modules next to IM151-1 COMPACT are removed and plugged during operation, then a station failure of ET 200S will not occur. The actual configuration differs from the expected configuration, the ET 200S remains engaged in data transfer with the DP master. When this parameter is disabled, and modules next to IM151-1 COMPACT are removed and plugged during operation, then a station failure of ET 200S will occur. The actual configuration differs from the expected configuration, there is no data transfer between the DP master and the ET 200S. 5.2.2 Analog-value format Here you set the number format for all analog electronic modules positioned next to the IM151-1 COMPACT. 5.2.3 Interference frequency suppression The frequency of your AC power system can interfere with the measured value, particularly when measuring in low voltage ranges and using thermocouple elements. You can enter the mains frequency for your system here (50 Hz or 60 Hz). The interference frequency suppression parameter applies to all analog electronic modules. With this parameter, you also specify the integration and conversion time of the various modules. See the technical data for the analog electronic modules. 5.2.4 Reference junction slot This parameter allows you to assign a slot (none, 2 to 13) where the channel for measuring the reference temperature is located (calculation of the compensation value). Reference For information on connecting thermocouples, refer to the manuals for the analog electronic modules. 30 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Parameters 5.2 Parameter description 5.2.5 Reference junction input This parameter can be used to set the channel (0/1) for measuring the reference temperature (calculation of the compensation value) for the assigned slot Reference For information on connecting thermocouples, refer to the manuals for the analog electronic modules. IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 31 Parameters 5.2 Parameter description 32 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 6 Error and system messages 6.1 Diagnostics using LED display COMPACT modules LED displays on COMPACT modules: 6) %) 21 3:5 3:5 3:5 Batch error (red) Bus fault (red) Power supply (green) Load voltage voltage group n present (green) Status display for input/output status (green) IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 33 Error and system messages 6.1 Diagnostics using LED display Status and error displays by means of LEDs on COMPACT modules The table below shows the status and error displays on the IM151-1 COMPACT module. Table 6-1 Status and error displays on the IM151-1 COMPACT (interface part) Cause Event (LEDs) SF BF ON off off off No supply voltage available on COMPACT module. Remedy Switch on the power supply voltage 24 VDC on the COMPACT module. Hardware defect on COMPACT module. * * * values Supply voltage available on COMPACT module. Flashin values The COMPACT module is not configured or is g configured incorrectly. No data exchange is taking place between the DP master and the COMPACT module. Causes: * The PROFIBUS address is incorrect. * Configuration error * Configuration error * values values Transmission rate detection, illegal PROFIBUS address, or bottom DIP switch (PROFIBUS address) not in the OFF position. Causes: * The response monitoring interval has elapsed. * Bus communication to the COMPACT module via PROFIBUS DP is interrupted. values * values The IM151-1 COMPACT (ET 200S) configuration structure doe not coincide with the actual structure of the station. --* * * Check the COMPACT module. Check the configuration and parameter assignment. Check the PROFIBUS address. Set a valid PROFIBUS address (1 to 125) on the COMPACT module or check the bus configuration. * Check that the bus connector is correctly inserted. * Check whether the bus cable to the DP master has been disconnected. * Switch the 24 VDC supply voltage off and on again at the COMPACT module. Check the structure of the ET 200S for missing or defective modules or whether an unconfigured module is inserted. Check the configuration (using COM PROFIBUS or STEP 7, for example) and correct the parameter assignment error. There is an error in an I/O module, or the COMPACT module is defective. values off values * * * off off Replace the COMPACT module, or contact your Siemens representative. * Parameter assignment incorrect * Hardware defect in the COMPACT module's integrated I/O. * A short circuit is present in the digital input sensor power supply or in the digital output load voltage. Check the parameter assignment. Exchange the COMPACT module. Check the power supply lines. values Data exchange is taking place between the DP ---master and IM151-1 COMPACT. The preset configuration and actual configuration of IM151-1 COMPACT (ET 200S) coincide. * not relevant 34 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Error and system messages 6.2 Diagnostic messages of the electronic modules Table 6-2 Status and error displays on the IM151-1 COMPACT (integrated periphery) Event (LEDs) SF 1 41 61 5 6 9 ::: Cause 38 45 46 49 ::: 78 valu es No configuration or incorrect module plugged in. There is a diagnostic message. Check the parameter assignments. Evaluate the diagnostics. valu es Load voltage voltage group 0 available. valu es Load voltage voltage group 2 available. valu es Load voltage voltage group 3 available. valu es Input on channel 0 activated. valu es Input on channel 1 activated. valu es Input on channel 2 activated. ::: ::: valu es Input on channel 15 activated. valu es Input/output on channel 16 activated. valu es Input/output on channel 17 activated. valu es Input/output on channel 18 activated. ::: ::: valu es 6.2 Input/output on channel 31 activated. Diagnostic messages of the electronic modules Actions following a diagnostic message in DPV0 mode The error is entered in the diagnostics frame in the channel-specific diagnostics: The SF LED on the interface module lights up. Several diagnostic messages can be output simultaneously. IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 35 Error and system messages 6.3 Diagnostics with STEP 7 6.3 Diagnostics with STEP 7 6.3.1 Diagnostics readout Introduction The slave diagnostics comply with IEC 61784-1:2002 Ed1 CP 3/1. Depending on the DP master, slave diagnostics can be read out with STEP 7 for all DP slaves that comply with the standard. Length of the diagnostics frame For the ET 200S with the COMPACT module, the maximum frame length is 44 bytes. The minimum frame length is - 6 bytes (identifier-related diagnostics, module status, and channel-specific diagnostics disabled via parameter assignment). Options for reading out the diagnostics The table below shows the options for reading out the diagnostics with STEP 7 on PROFIBUS DP. Table 6-3 Reading out the diagnostics with STEP 7 on PROFIBUS DP Automation system with DP master SIMATIC S7/M7 36 Block or tab in STEP 7 Application "DP Slave Diagnostics" tab Slave diagnostics in plain text on the STEP 7 user interface SFC 13 "DP NRM_DG" Reading out slave diagnostics SFC see STEP 7 Online Help (store in the data area of the user program) Reference "Diagnosing hardware" in STEP 7 Online Help IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Error and system messages 6.3 Diagnostics with STEP 7 Example of reading out S7 diagnostics using SFC 13 "DP NRM_DG" Here, you will find an example of how to use SFC 13 to read out the slave diagnostics for a DP slave in the STEP 7 user program. For the purpose of this STEP 7 user program, the following is assumed: The diagnostic address of the ET 200S is 1022 (3FEH). The slave diagnostics are to be stored in DB 82: Starting from address 0.0, length = 43 bytes. The slave diagnostics can be up to 43 bytes long. STEP 7 user program STL Description CALL SFC 13 REQ :=TRUE Read request LADDR :=W#16#3FE Diagnostic address of the ET 200S RET_VAL :=MW0 RET_VAL of SFC 13 RECORD :=P#DB82.DBX 0.0 BYTE 43 Data record for the diagnostics in DB 82 BUSY :=M2.0 The read process runs through several OB 1 cycles IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 37 Error and system messages 6.3 Diagnostics with STEP 7 6.3.2 Structure of the slave diagnostics Structure of the slave diagnostics The figure below shows the structure of the slave diagnostics. %\WH %\WH %\WH 6WDWLRQVWDWXVWR %\WH 0DVWHU352),%86DGGUHVV %\WH +LJK%\WH /RZ%\WH %\WH %\WH 0DQXIDFWXUHU,' ,GHQWLILHUUHODWHG GLDJQRVWLFV %\WH %\WH 0RGXOHVWDWXV 0RUHLQIRUPDWLRQ %\WH %\WH %\WH %\WH FKDQQHOVSHFLILFGLDJQRVWLFV E\WHVSHUFKDQQHO &KDQQHOVSHFLILFGLDJQRVWLFV YDU\IURPWRE\WHV 7KLVGHSHQGVRQWKHQXPEHURI FKDQQHOVSHFLILFGLDJQRVWLFV %\WH 7KHVHGLDJQRVWLFVFDQEHGLVDEOHGRUHQDEOHGXVLQJSDUDPHWHUV,I\RX GLVDEOHWKHPWKH\ZLOOEHUHPRYHGIURPWKHGLDJQRVWLFIUDPH Figure 6-1 Structure of the slave diagnostics Note In the case of the COMPACT modules, the length of the diagnostics frame is 44 bytes. You can identify the length of the last received diagnostics frame in STEP 7 by referring to the RET_VAL parameter of the SFC 13. 38 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Error and system messages 6.3 Diagnostics with STEP 7 6.3.3 Station statuses 1 to 3 Definition Station statuses 1 to 3 provide an overview of the status of a DP slave. Structure of station status 1 (byte 0) Table 6-4 Bit Structure of station status 1 (byte 0) Meaning Cause/Remedy 0 1: The DP slave cannot be accessed by the DP master. * * * * * Is the correct PROFIBUS address set on the DP slave? Is the bus connector plugged in? Is the DP slave connected to the voltage supply? Is the RS-485 repeater set correctly? Has the DP slave been reset? 1 1: The DP slave is not yet ready to exchange data. * Wait, the DP slave is currently starting up. 2 1: The configuration data transferred from the DP master to the DP slave does not match the slave configuration. * Has the correct station type or the correct DP slave configuration been entered in the configuration software? 3 1: External diagnostics information is pending. (Group diagnostics display) * Evaluate the ID-specific diagnostics information, the module status, and/or the channel-specific diagnostics information. As soon as all errors have been eliminated, bit 3 will be reset. The bit will be set again when there is a new diagnostics message in the bytes of the aforementioned diagnostics. 4 1: The required function is not supported by the DP slave (for example, changing the PROFIBUS address by means of software). * Check the configuration. 5 1: The DP master cannot interpret the response of the DP slave. * Check the bus configuration. 6 1: The DP slave type does not match the software configuration. * Has the correct station type been entered in the configuration software? 7 1: Parameters have been assigned to the DP slave by a different DP master (not the one that currently has access to the DP slave). * The bit is always 1, for example, if you access the DP slave with the programming device or another DP master. The PROFIBUS address of the DP master that assigned parameters to the DP slave is located in the "Master PROFIBUS address" diagnostics byte. IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 * 39 Error and system messages 6.3 Diagnostics with STEP 7 Structure of station status 2 (byte 1) Table 6-5 Structure of station status 2 (byte 1) Bit 1 Meaning 0 1: The DP slave parameters need to be reassigned. 1 1: A diagnostics message is pending. The DP slave will not operate until the problem is eliminated (static diagnostics message). 2 1: The bit on the DP slave is always "1". 3 1: The watchdog is activated for this DP slave. 4 1: The DP slave has received the "FREEZE" control command 1. 5 1: The DP slave has received the "SYNC" control command 1. 6 0: Bit is always "0". 7 1: The DP slave is disabled, that is, it has been removed from the processing in progress. The bit is updated only if another diagnostics message changes also. Structure of station status 3 (byte 2) Table 6-6 Structure of station status 3 (byte 2) Bit 0 to 6 7 6.3.4 Meaning 0: Bits are always set to "0". 1: * * There are more diagnostics messages pending than the DP slave is able to store. The DP master cannot enter all the diagnostics messages sent by the DP slave in its diagnostics buffer (channel-specific diagnostics). Master PROFIBUS address Definition The Master PROFIBUS address diagnostics byte contains the PROFIBUS address of the DP master: That assigned parameters to the DP slave That has read and write access to the DP slave The master PROFIBUS address is located in byte 3 of the slave diagnostics. 40 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Error and system messages 6.3 Diagnostics with STEP 7 6.3.5 Identifier-related diagnostics Definition The identifier-related diagnostics indicate whether or not modules of the ET 200S have errors/faults. In the case of the IM151-1 COMPACT modules, identifier-related diagnostics start at byte 6 and are 3 bytes long. Structure of the identifier-related diagnostics The identifier-related diagnostics for ET 200S are structured as follows for the IM151-1 COMPACT modules: %\WH %LWQR /HQJWKRIWKHLGHQWLILHUUHODWHGGLDJQRVWLFV LQFOXGLQJE\WH E\WHV &RGHIRULGHQWLILHUUHODWHGGLDJQRVWLFV %\WH %\WH $OZD\V Figure 6-2 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 %LWQR 0RGXOHWR 0RGXOHWR (YHQWVRQWKHFRUUHVSRQGLQJ PRGXOHDUHLQGLFDWHGE\VHW ELWV 0RGXOH,QWHJUDWHG,2 Structure of the identifier-related diagnostics for IM151-1 COMPACT modules 41 Error and system messages 6.3 Diagnostics with STEP 7 6.3.6 Module status Definition The module status indicates the status of the configured modules and provides more information on the identifier-related diagnostics with respect to the configuration. With the COMPACT module, the module status starts after the identifier-related diagnostics and consists of 8 bytes. Structure of the module status The module status for the ET 200S with COMPACT modules is structured as follows: %\WH %LWQR /HQJWKRIWKHPRGXOHVWDWXV LQFOXGLQJE\WH E\WHV &RGHIRUPRGXOHVWDWXV %\WH + 6WDWXVW\SH0RGXOHVWDWXV %\WH + 1RWDSSOLFDEOH %\WH + 1RWDSSOLFDEOH %\WH %\WH %\WH %LWQR 0RGXOHWR 0RGXOHWR 0RGXOHWR 0RGXOH 0RGXOH 2QERDUG,2 %0RGXOH2.YDOLGXVHUGDWD %0RGXOHHUURULQYDOLGXVHUGDWD %,QFRUUHFWPRGXOHLQYDOLGXVHUGDWD %1RPRGXOH RUPRGXOHIDLOXUH LQYDOLGXVHUGDWD Figure 6-3 42 Structure of the module status for the ET 200S with COMPACT module IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Error and system messages 6.3 Diagnostics with STEP 7 6.3.7 Channel-specific diagnostics Definition Channel-specific diagnostics provide information about channel errors in modules and details of the identifier-related diagnostics. The channel-specific diagnostics start after the module status (if parameters are preset accordingly). The maximum length is limited by the maximum total length of slave diagnostics, i.e., 44 bytes in DPV0 mode. Channel-specific diagnostics do not affect the module status. Up to 9 channel-specific diagnostic messages are possible. Structure of channel-specific diagnostics The channel-specific diagnostics for the ET 200S with COMPACT modules are structured as follows: %\WH %LWQR %WR% 6ORWIRUWKHPRGXOHWKDWLVSURYLGLQJWKHFKDQQHOVSHFLILF GLDJQRVWLFV &RGHIRUFKDQQHOVSHFLILFGLDJQRVWLFV %LWQR %\WH &KDQQHOW\SH %\WH %WR%1XPEHURIWKHFKDQQHOYROWDJHJURXS WKDWSURYLGHVWKHGLDJQRVWLFV %,QSXWFKDQQHO %2XWSXWFKDQQHO %,QSXWRXWSXWFKDQQHO (UURUW\SH VHHPDQXDOIRUWKHUHOHYDQWPRGXOH &KDQQHOUHVROXWLRQ %%LW %ELWV %ELWV %%\WH %:RUG %ZRUGV %\WH 8SWR Figure 6-4 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 1H[WFKDQQHOVSHFLILFGLDJQRVWLFPHVVDJH DVVLJQPHQWDVIRUE\WHVWR Structure of the channel-specific diagnostics for the ET 200S with COMPACT module 43 Error and system messages 6.3 Diagnostics with STEP 7 Note The module slot coding is contained in byte 17, bits 0 to 5. The following applies: Displayed number +1 Slot of the module (0 Slot 1; 1 Slot 2; 3 Slot 4, etc.) In bits 6/7 of byte 18, 00B is output if a power module reports channel-specific diagnostics. 6.3.8 Incorrect module configurations of ET 200S on the PROFIBUS DP Invalid module configuration states The following invalid ET 200S module configuration states lead to an ET 200S station failure or prevent entry into data exchange. These responses occur regardless of whether the IM parameters "Operation at set <> actual configuration", "Replace modules during operation", and "Startup at set <> actual configuration" have been enabled. Two missing modules Terminating module missing Number of modules exceeds maximum configuration Backplane bus fault (for example, defective terminal module) Note The station will not start up if one module is missing (gap) and the ET 200S is switched on. Diagnostics You can identify any invalid module configuration states on the basis of the following diagnostics: Identifier-related diagnostics All 13 bits set Module status * * 44 01B: "Module error; invalid user data" for all modules (slots) until the cause of the error is found 11B: "No module; invalid user data" once the cause of the error is found IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 7 Response times for the ET 200S Calculating the response times for the 32DI IM151-1 COMPACT and 16 DI/16 DO IM151-1 COMPACT The following equation enables you to make an approximate calculation of the ET 200S response time: 32DI IM 151-1 COMPACT: Response time [s] = 156 m + 33 do + 486 ai + 374 ao + 1,633 t + 1,576 16 DI/16 DO IM 151-1 COMPACT: Response time [s] = 156 m + 33 do + 486 ai + 374 ao + 1,633 t + 1664 Explanation of the parameters: m: Total number of all modules (power modules, digital electronic modules, analog electronic modules, 4 IQ-SENSE electronic modules, 4POTDIS potential distribution module, RESERVE module, technological modules, and motor starters) do: Sum total of all digital output modules ai: Sum total of all analog input modules and 1SSI fast electronic modules ao: Sum total of all analog output modules t: Total number of technological modules (except 1SSI fast) Example for calculating the ET 200S response time for 32DI COMPACT %XVWHUPLQDWRU '6 '6 30' '6 '29'& ',9'& '29'& ',9'& Figure 7-1 $,8 $2, ',9'& 30(9'& ,0&203$&7 6ORW Example setup for calculating the response time of the 32DI IM151-1 COMPACT Calculation method: m = 12; do = 2; ai = 1; ao = 1; t = 0 Response time = 156 m + 33*do + 486 ai + 374 ao + 1,633 t + 1,576 Response time = 156 12 + 33*2 + 486 1 + 374 1 + 1,633 0 + 1,576 Response time = 4374 s IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 45 Response times for the ET 200S 46 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Index A Applications, 9 B Basic knowledge requirements, 3 C IM151-1 COMPACT 32DI 24 V DC Block diagram, 15 Parameter, 29 Properties, 11 Status and error displays, 34 Terminal assignment, 11 IM151-1 COMPACT 32DI 24 VDC Technical data, 16 IM151-1 COMPACT 32DI 24VDC Technical data, 16 Internet Service & Support, 4 Channel-specific diagnostics, 43 COMPACT modules, 9 COMPACT modules and applications, 9 Configuration options of the COMPACT modules, 9 L D M Definition Station status, 39 Disposal, 3 Master PROFIBUS address, 40 Module status, 42 E Error types Channel-specific diagnostics, 43 I Identifier-related diagnostics, 41 IM151-1 COMPACT 16DI/16DO 24 VDC/0.5 A Block diagram, 23 Parameter, 29 Properties, 19 Status and error displays, 34 Technical data, 24 Terminal assignment, 20 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 Length of the diagnostics frame, 36 O Options, 36 P Parameter IM151-1 COMPACT, 29 R Reading out diagnostics, 36 Recycling, 3 Response times For the ET 200S, 45 47 Index S Scope Manual, 3 Service & Support, 4 SFC 13, 37 Slave diagnostics, 36, 38 Station status 1 Structure, 39 Station status 2 Structure, 40 Station status 3 Structure, 40 Station statuses 1 to 3, 39 Status and error displays, 34 IM151-1 COMPACT, 34 STEP 7 user program, 37 Structure, 38 T Technical Support, 4 Training center, 4 48 IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 SIMATIC ET 200S distributed I/O IM151-1 COMPACT modules Manual, 03/2007, A5E01077635-01 49