Error and system messages
6.1 Diagnostics using LED display
IM151-1 COMPACT modules
34 Manual, 03/2007, A5E01077635-01
Status and error displays by means of LEDs on COMPACT modules
The table below shows the status and error displays on the IM151-1 COMPACT module.
Table 6-1 Status and error displays on the IM151-1 COMPACT (interface part)
Event (LEDs)
SF BF ON
Cause Remedy
off off off No supply voltage available on COMPACT
module.
Hardware defect on COMPACT module.
Switch on the power supply voltage 24 VDC
on the COMPACT module.
* * values Supply voltage available on COMPACT
module.
---
* Flashin
g
values The COMPACT module is not configured or is
configured incorrectly. No data exchange is
taking place between the DP master and the
COMPACT module.
Causes:
• The PROFIBUS address is incorrect.
• Configuration error
• Configuration error
• Check the COMPACT module.
• Check the configuration and parameter
assignment.
• Check the PROFIBUS address.
* values values Transmission rate detection, illegal
PROFIBUS address, or bottom DIP switch
(PROFIBUS address) not in the OFF position.
Causes:
• The response monitoring interval has
elapsed.
• Bus communication to the COMPACT
module via PROFIBUS DP is interrupted.
Set a valid PROFIBUS address (1 to 125) on
the COMPACT module or check the bus
configuration.
• Check that the bus connector is correctly
inserted.
• Check whether the bus cable to the DP
master has been disconnected.
• Switch the 24 VDC supply voltage off and
on again at the COMPACT module.
The IM151-1 COMPACT (ET 200S)
configuration structure doe not coincide with
the actual structure of the station.
Check the structure of the ET 200S for missing
or defective modules or whether an
unconfigured module is inserted.
Check the configuration (using COM
PROFIBUS or STEP 7, for example) and
correct the parameter assignment error.
values * values
There is an error in an I/O module, or the
COMPACT module is defective.
Replace the COMPACT module, or contact
your Siemens representative.
values off values • Parameter assignment incorrect
• Hardware defect in the COMPACT
module's integrated I/O.
• A short circuit is present in the digital input
sensor power supply or in the digital output
load voltage.
• Check the parameter assignment.
• Exchange the COMPACT module.
• Check the power supply lines.
off off values Data exchange is taking place between the DP
master and IM151-1 COMPACT.
The preset configuration and actual
configuration of IM151-1 COMPACT (ET
200S) coincide.
----
* not relevant