63
STEGO - PRODUCT CATALOGUE
TECHNICAL DATA
Axial fans, ball bearing service life 50,000 h at +25 °C (+77 °F), 65 % RH
fan body aluminium, rotor plastic
Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing plastic according to UL94 V-0, light grey;
weather proof and UV light resistant according UL746C (f1)
Filter mat ISO coarse 55% acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100 °C, self-extinguishing class F1,
moisture resistant to 100 % RH,
reusable – cleaning by washing or vacuuming
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class IP32 / I (earthed)
Approvals EAC, VDE (AC 230 V only)
Important note: For reasons of pressure compensation the roof filter fan must always be operated in combination with a passive
intake filter (e.g. Art. No. 11803.0-00) or another filter fan (e.g. Art. No. 01803.0-00).
Roof filter fans find use in enclosures and housings, from which warm air has to be diverted to lower the internal
temperature. These low-noise roof filter fans are used to expel warm air from within the enclosure which has
been
generated by the stray power of the components and so protects the internal devices from overheating. To
exchange
the filter mat the hood can be easily opened without tools. The roof exit filter provides passive
ventilation.
> Very low noise
> Minimal depth in enclosure
> High through-flow air volume
> High reliability
> Time-saving installation and mat
exchange
Photo: Art. No. 01860.0-00
Photo: Art. No. 01861.0-00
Roof Filter Fan (01860.0-XX)
FILTER MAT FM 086
ROOF EXIT FILTER REP 118
ROOF FILTER FAN RFP 018
Roof Filter Fan (01861.0-XX)
Hole centers
ROOF FILTER FAN
RFP 018 | 300 m³/h, 500 m³/h
Enclosure cut-out
Filter mat 282 x 282 mm
G3 (1 packing unit = 3 pcs.) Art. No. 08613.0-01
Art. No. Operating
voltage
Air volume,
free flow
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in enclosure Enclosure cut-out Weight
(approx.)
Operating / Storage temperature
01860.0-00 AC 230 V, 50 Hz 300 m³/h 68 W 55 dB (A) 52 mm 246 x 246 mm + 0.4 3.3 kg -10 to +70 °C (+14 to +158 °F) /
-40 to +70 °C (-40 to +158 °F)
01861.0-00 AC 230 V, 50 Hz 500 m³/h 64 W 67 dB (A) 107 mm 246 x 246 mm + 0.4 2.6 kg -25 to +70 °C (-13 to +158 °F)
01860.0-02 AC 120 V, 60 Hz 345 m³/h 60 W 55 dB (A) 52 mm 246 x 246 mm + 0.4 3.3 kg -10 to +70 °C (+14 to +158 °F) /
-40 to +70 °C (-40 to +158 °F)
01861.0-02 AC 120 V, 60 Hz 575 m³/h 85 W 67 dB (A) 107 mm 246 x 246 mm + 0.4 2.6 kg -25 to +70 °C (-13 to +158 °F)
Art. No. Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type
11860.0-00 11 mm 246 x 246 mm + 0.4 1.0 kg ISO coarse 55% acc. to ISO 16890 (G3), initial gravimetric arrestance 57 % IP32
COOLING
29.01.2020 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
63
TECHNICAL DATASHEET