TMCP SOCKET M Modular base, 2-position, for holding two circuit breakers, each with single positions CLIPLINE Data Sheet 104391_en_00 1 (c) PHOENIX CONTACT 2010-05-26 Description The TMCP SOCKET M base is snapped onto a DIN rail and can accommodate two single-position circuit breakers of type ECP..., ECP-E.... or TMCP.... Group indication is fully wired internally. The supply at connection 13 and the signal tap at connection 14 support the quick creation of a signal loop via all circuit breakers. The two-channel bases are modular, which means that larger distribution systems can be created. A TMCP CONNECT LR base termination element is inserted at both the start and end of the system. NOTE: If a slot is free on a base, the ECP...-SB signal bridge must be used here to feed through the signal. The base module has an integrated bridge shaft on the power input side. A plug-in bridge system, which can be cut to any length, can thus be used to create a current distribution with up to 40-positions. The maximum supply current depends on the type of supply and the bridge used. Signal contacts, N/C contacts, and N/O contacts are already integrated in the circuit breakers. All electrical connections are established using spring-cage terminal blocks. Individual indication can be established via connection 11 on the TMCP CONNECT LR base termination elements and connection 12 on the base module. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. This data sheet is valid for the products listed on the following page: TMCP SOCKET M 2 Ordering data Base Description Type Order No. Pcs./Pkt. TMCP SOCKET M 0916589 10 Type Order No. Pcs./Pkt. TMCP CONNECT LR 0916592 3 Spring lock, for mechanical locking in the case of overhead mounting, 1-pos. ECP-LOCK 0912021 10 Spring lock, for mechanical locking in the case of overhead mounting, 1-pos. SPRING-LOCK 0713009 10 Zack marker strip, 10-section, for labeling the center of the terminal block ZB 6 See CLIPLINE catalog UniCard sheets, for labeling terminal blocks using a Zack marker strip groove, 80-section, can be labeled with BLUEMARK and CMS-P1-PLOTTER, color: white UC-TM 6 0818085 10 Fixed bridge, plug-in, not insulated, 500 mm long, can be cut to length, for distribution of the supply potential in the base, Imax = 50 A FBST 500 TMCP 0916615 20 Continuous plug-in bridge, 500 m long, can be cut to length, for potential distribution, Imax = 32 A, red FBST 500-PLC RD 2966786 20 Continuous plug-in bridge, 500 m long, can be cut to length, for potential distribution, Imax = 32 A, blue FBST 500-PLC BU 2966692 20 Signal bridge, plug-in, for bridging group indication when there is a free slot on the TMCP SOCKET M base, Imax = 1 A TCMP SB 0916602 6 Modular base, 2-pos., designed to accommodate two 1-pos. circuit breakers, width of 12.5 mm per position Accessories Description Base termination elements, can be plugged into both the left and right-hand side, contain the connections for the reset inputs/group query 104391_en_00 PHOENIX CONTACT 2 TMCP SOCKET M 3 Technical data General data TMCP CONNECT LR (width x length) 25 mm (2-pos.) x 115 mm TMCP SOCKET M (width x length) 6 mm x 115 mm Height on NS 35/7.5... DIN rail 110.5 mm Height on NS 35/15... DIN rail 118 mm Insulation material PA-F Inflammability class according to UL 94 V0 Rated surge voltage 2.5 kV Pollution degree 2 TMCP SOCKET M Test contact for testing group indication on a cable interrupt o = 2 mm Nominal voltage (without circuit breaker) 433 V AC (65 V DC) Nominal current (without circuit breaker) Input (1) 50 A Output (2) 25 A* Supply (11) 10 A Single output (12), group indication (13, 14) 1A *(When several circuit breakers are mounted in rows, the entire nominal current cannot be led due to the mutual thermal effect. When IN 16 A, the maximum load is 80%. When IN > 16 A, the maximum load is 65%. Internal resistance (without circuit breaker) 5 m Input/output (1, 2) Signaling, parallel (11-12) 9 m/per position serial (13-14) 8 m/per position Supply rail for current distribution, plug-in bridge FBST 500-PLC... Imax = 32 A FBST 500-TMCP (uninsulated power rail Imax = 50 A (the uninsulated power rail is inserted fully and is therefore safe to touch) Imax = 50 A Dielectric strength Between main circuits (without plug-in bridge) 1500 V Main circuit to signal circuit 1500 V Signal circuit to signal circuit 1500 V Weight Central part 85 g, approximately Connection elements (pair) 30 g, approximately Connections Spring-cage terminal blocks for solid wires and stranded cables with and without ferrules. Use the specified screwdriver size (SD) to release the spring cage. Connection Spring-cage terminal blocks for Stripping length Input (1) 1.5 mm ... 10 mm 15 mm SD 2 (0.8 x 4.0 mm) Output (2) 0.25 mm ... 4 mm 12 mm SD 1 (0.6 x 3.5 mm) Auxiliary contacts (11, 13/14) 0.25 mm2 ... 2.5 mm2 10 mm SD 1 (0.6 x 3.5 mm) Single output (12) 0.25 mm2 ... 1.5 mm2 10 mm SD 0 (0.4 x 2.5 mm) Connection capacity ECP... CONNECT LR Screwdriver size (SD) Supply Auxiliary contact 11 Group output Auxiliary contacts 13/14 Nominal voltage 250 V AC (65 V DC) 250 V AC (65 V DC) Nominal current 10 A 1A 10 A for 2.5 mm2 1 A for 2.5 mm2 Maximum load current 104391_en_00 PHOENIX CONTACT 3 TMCP SOCKET M 4 Dimensions 4.1 TMCP dimensions with base and base termination element 4.2 ECP dimensions with base 115 43 110,5 115 118 68 30,5 Figure 2 ECP dimensions... (in mm) 37 6 25 Figure 1 104391_en_00 TMCP dimensions... (in mm) PHOENIX CONTACT 4 TMCP SOCKET M 5 Internal wiring The internal wiring is illustrated in the circuit diagram. Device 1 * 1 WARNING: Always fill empty slots with the TMCP SB signal bridge. 1 11 11 * 13 14 2 12 2 12 * Illustration and definitions when switched off and with zero current. * * 6 Insert ECP... or TMCP... 3. Device 2 Installation * 1 2 6.1 If a slot on the base is empty, the TMCP SB signal bridge is used. It bridges the group signal and replaces the circuit breaker. The bridging option in the base enables supply potential distribution over a maximum of 40 positions. Cut FBST 500... plug-in bridge to length as required and insert in bases 4. Insert the connecting cables into the spring-cage terminal blocks. If required, secure the TMCP... and base using the SPRING-LOCK clamp. If required, secure the ECP... and base using the ECP-LOCK clamp. Locking the base and ECP... If mounted overhead, the ECP... must be connected to the base using the ECP-LOCK clamp. 3 4 To assemble, proceed as follows: * Snap the TMCP SOCKET M base onto a DIN rail according to EN 60751 1. Individual bases can be mounted side by side to create any number of positions. * Push bases together. * Snap on TMCP CONNECT LR base termination elements to the left and right-hand side 2. The termination elements contain the contacts for group indication and the supply for individual indication. 104391_en_00 Figure 3 Installing and removing ECP-LOCK PHOENIX CONTACT GmbH & Co. KG * 32823 Blomberg * Germany * Phone: +49-(0) 5235-3-00 PHOENIX CONTACT * P.O.Box 4100 * Harrisburg * PA 17111-0100 * USA * Phone: +717-944-1300 www.phoenixcontact.com 5