© PHOENIX CONTACT 2010-05-26
104391_en_00
CLIPLINE
TMCP SOCKET M
Data Sheet
1Description
The TMCP SOCKET M base is snapped onto a DIN rail and
can accommodate two single-position circuit breakers of
type ECP…, ECP-E.... or TMCP….
The two-channel bases are modular, which means that
larger distribution systems can be created.
ATMCPCONNECTLR base termination element is
inserted at both the start and end of the system.
The base module has an integrated bridge shaft on the
power input side. A plug-in bridge system, which can be cut
to any length, can thus be used to create a current
distribution with up to 40-positions. The maximum supply
current depends on the type of supply and the bridge used.
Signal contacts, N/C contacts, and N/O contacts are
already integrated in the circuit breakers.
All electrical connections are established using spring-cage
terminal blocks.
Individual indication can be established via connection 11
on the TMCP CONNECT LR base termination elements
and connection 12 on the base module.
Group indication is fully wired internally. The supply at
connection 13 and the signal tap at connection 14 support
the quick creation of a signal loop via all circuit breakers.
NOTE: If a slot is free on a base, the ECP…-SB
signal bridge must be used here to feed through
the signal.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for the products listed on the following page:
Modular base, 2-position, for holding two circuit
breakers, each with single positions
TMCP SOCKET M
104391_en_00 PHOENIX CONTACT 2
2Ordering data
Base
Description Type Order No. Pcs./Pkt.
Modular base, 2-pos., designed to accommodate two 1-pos. circuit breakers,
width of 12.5 mm per position
TMCP SOCKET M 0916589 10
Accessories
Description Type Order No. Pcs./Pkt.
Base termination elements, can be plugged into both the left and right-hand
side, contain the connections for the reset inputs/group query
TMCP CONNECT LR 0916592 3
Spring lock, for mechanical locking in the case of overhead mounting, 1-pos. ECP-LOCK 0912021 10
Spring lock, for mechanical locking in the case of overhead mounting, 1-pos. SPRING-LOCK 0713009 10
Zack marker strip, 10-section, for labeling the center of the terminal block ZB 6 See CLIPLINE catalog
UniCard sheets, for labeling terminal blocks using a Zack marker strip
groove, 80-section, can be labeled with BLUEMARK and CMS-P1-PLOTTER,
color: white
UC-TM 6 0818085 10
Fixed bridge, plug-in, not insulated, 500 mm long, can be cut to length, for
distribution of the supply potential in the base, Imax = 50 A
FBST 500 TMCP 0916615 20
Continuous plug-in bridge, 500 m long, can be cut to length, for potential
distribution, Imax = 32 A, red
FBST 500-PLC RD 2966786 20
Continuous plug-in bridge, 500 m long, can be cut to length, for potential
distribution, Imax = 32 A, blue
FBST 500-PLC BU 2966692 20
Signal bridge, plug-in, for bridging group indication when there is a free slot
on the TMCP SOCKET M base, Imax = 1 A
TCMP SB 0916602 6
TMCP SOCKET M
104391_en_00 PHOENIX CONTACT 3
3 Technical data
Connections
Spring-cage terminal blocks for solid wires and stranded
cables with and without ferrules. Use the specified
screwdriver size (SD) to release the spring cage.
General data
TMCP CONNECT LR (width x length) 25 mm (2-pos.) x 115 mm
TMCP SOCKET M (width x length) 6 mm x 115 mm
Height on NS 35/7.5... DIN rail
Height on NS 35/15... DIN rail
110.5 mm
118 mm
Insulation material PA-F
Inflammability class according to UL 94 V0
Rated surge voltage 2.5 kV
Pollution degree 2
TMCP SOCKET M
Test contact for testing group indication on a cable interrupt ø = 2 mm
Nominal voltage (without circuit breaker) 433 V AC (65 V DC)
Nominal current (without circuit breaker)
Input (1)
Output (2)
Supply (11)
Single output (12), group indication (13, 14)
50 A
25 A*
10 A
1 A
*(When several circuit breakers are mounted in rows,
the entire nominal current cannot be led due to the
mutual thermal effect.
When IN 16 A, the maximum load is 80%.
When IN > 16 A, the maximum load is 65%.
Internal resistance (without circuit breaker)
Input/output (1, 2)
Signaling,
parallel (11-12)
serial (13-14)
5 mΩ
9 mΩ/per position
8 mΩ/per position
Supply rail for current distribution, plug-in bridge
FBST 500-PLC...
FBST 500-TMCP (uninsulated power rail Imax = 50 A (the uninsulated power
rail is inserted fully and is therefore safe to touch)
Imax = 32 A
Imax = 50 A
Dielectric strength
Between main circuits (without plug-in bridge)
Main circuit to signal circuit
Signal circuit to signal circuit
1500 V
1500 V
1500 V
Weight
Central part
Connection elements (pair)
85 g, approximately
30 g, approximately
Connection Spring-cage terminal blocks for Stripping length Screwdriver size (SD)
Input (1) 1.5 mm² ... 10 mm² 15 mm SD 2 (0.8 x 4.0 mm)
Output (2) 0.25 mm² ... 4 mm² 12 mm SD 1 (0.6 x 3.5 mm)
Auxiliary contacts (11, 13/14) 0.25 mm2 ... 2.5 mm210 mm SD 1 (0.6 x 3.5 mm)
Single output (12) 0.25 mm2 ... 1.5 mm210 mm SD 0 (0.4 x 2.5 mm)
Connection capacity ECP… CONNECT LR Supply Group output
Auxiliary contact 11 Auxiliary contacts 13/14
Nominal voltage 250 V AC (65 V DC) 250 V AC (65 V DC)
Nominal current 10 A 1 A
Maximum load current 10 A for 2.5 mm21 A for 2.5 mm2
TMCP SOCKET M
104391_en_00 PHOENIX CONTACT 4
4Dimensions
4.1 TMCP dimensions with base and base
termination element
Figure 1 TMCP dimensions... (in mm)
4.2 ECP dimensions with base
Figure 2 ECP dimensions... (in mm)
4330,5
115
68
110,5
115
118
625
37
TMCP SOCKET M
104391_en_00 5
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
5 Internal wiring
The internal wiring is illustrated in the circuit diagram.
6 Installation
To assemble, proceed as follows:
Snap the TMCP SOCKET M base onto a DIN rail
according to EN 60751 1.
Individual bases can be mounted side by side to create
any number of positions.
Push bases together.
Snap on TMCP CONNECT LR base termination
elements to the left and right-hand side 2.
The termination elements contain the contacts for
group indication and the supply for individual indication.
Insert ECP… or TMCP… 3.
If a slot on the base is empty, the TMCP SB signal
bridge is used. It bridges the group signal and replaces
the circuit breaker.
The bridging option in the base enables supply potential
distribution over a maximum of 40 positions.
Cut FBST 500... plug-in bridge to length as required and
insert in bases 4.
Insert the connecting cables into the spring-cage
terminal blocks.
If required, secure the TMCP… and base using the
SPRING-LOCK clamp.
If required, secure the ECP… and base using the
ECP-LOCK clamp.
6.1 Locking the base and ECP…
If mounted overhead, the ECP… must be connected to the
base using the ECP-LOCK clamp.
Figure 3 Installing and removing ECP-LOCK
11
14
212212
11
13
11
Device 1 Device 2
Illustration and definitions when switched off and with zero current.
2
34
1
WARNING: Always fill empty slots with the
TMCP SB signal bridge.