Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
45
1
Power Protection and Conditioning
Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation)
Selection Tables: Single Phase
Group 3 – MCR Series, 60 Hz Only
Specifications
VA Catalog Number Voltage Input Voltage Output Height
in (mm)
Width
in (mm)
Depth
in (mm)
Ship Weight
lbs (kg)
Design
Style
Elec
Conn
500 63-31-150-8 600 120, 208, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 38.0 (17.24) 1B
1000 63-32-210-8 600 120, 208, 240 17.00 (431.8) 9.00 (228.6) 7.00 (177.8) 62.0 (28.12) 1B
2000 63-32-220-8 600 120, 208, 240 18.00 (457.2) 13.00 (330.2) 10.00 (254.0) 109.0 (49.44) 1B
3000 63-32-230-8 600 120, 208, 240 19.00 (482.6) 13.00 (330.2) 10.00 (254.0) 142.0 (64.41) 1B
5000 63-29-250-8 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 13.00 (330.2) 10.00 (254.0) 221.0 (100.24) 1A
7500 63-29-275-8 208, 240, 480, 600 120, 208, 240 27.00 (685.8) 25.00 (635.0) 10.00 (254.0) 360.0 (163.30) 2A
10000 63-29-310-8 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 25.00 (635.0) 10.00 (254.0) 441.0 (200.03) 2A
15000 63-29-315-8 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 38.00 (965.2) 10.00 (254.0) 706.0 (320.24) 3 A
VA Catalog Number Voltage Input Voltage Output Height
in (mm)
Width
in (mm)
Depth
in (mm)
Ship Weight
lbs (kg)
Design
Style
Elec
Conn
120 63-23-612-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9.00 (228.6) 6.00 (152.4) 8.00 (203.2) 24.0 (10.90) 1 C
250 63-23-625-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11.00 (279.4) 6.00 (152.4) 8.00 (203.2) 27.0 (12.25) 1 C
500 63-23-650-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 40.0 (18.14) 1 C
1000 63-23-710-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18.00 (457.2) 9.00 (228.6) 7.00 (177.8) 64.0 (29.03) 1 C
2000 63-23-720-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18.00 (457.2) 13.00 (330.2) 10.00 (254.0) 113.0 (51.26) 1 C
3000 63-23-730-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27.00 (685.8) 13.00 (330.2) 10.00 (254.0) 162.0 (73.48) 1 C
5000 63-23-750-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 13.00 (330.2) 10.00 (254.0) 266.0 (120.66) 1 C
7500 63-28-775-8 220, 240, 380, 415 110, 120, 220, 240 28.00 (711.2) 26.00 (660.4) 10.00 (254.0) 393.0 (178.26) 2 C1
10000 63-28-810-8 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 26.00 (660.4) 10.00 (254.0) 490.0 (222.26) 2 C2
15000 63-28-815-8 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 38.00 (965.2) 10.00 (254.0) 776.0 (352.00) 3 C2
Parameter Condition Value
Input
Voltage Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current 1at Full Load & 80% of nominal input voltage Iin ≅ (VA/.89)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Output 2
Line Regulation Vin >80% and <110% of nominal ± 5% for 50 Hz units, ± 3% for 60 Hz units
Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current
Output Harmonic Distortion At full load within input range 3% total RMS content
Noise Attenuation Common Mode
Transverse Mode
120 dB
60 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to +85°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 35 dBA to 65 dBA
Warranty 10 + 2 year limited warranty
Notes: 1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.