Multi-function timer range
Type 83.01
- Multi-function & multi-voltage
- 1 Pole
Type 83.02
- Multi-function & multi-voltage
- 2 Pole (timed + instantaneous options),
external time setting potentiometer option
Type 83.52
- Multi-function & multi-voltage
- 2 Pole (timed + instantaneous options),
external time setting potentiometer option,
pause function option
22.5mm wide
Eight time scales from 0.05s to 10days
High input/output isolation
Wide supply range (24…240)VAC/DC
35mm rail (EN60715) mount
“Blade + cross” - both flat blade and cross head
screw drivers can be used to adjust the range
and function selectors, the timing trimmer, and
to disengage the rail mounting clip
Multi-voltage versions with “PWM clever”
technology
Complies with EN 45545-2:2013 (protection
against fire of materials), EN 61373 (resistance
against random vibrations and shock,
Category 1, Class B), EN 50155 (resistance to
temperature and humidity, T1 class)
83.01 83.02 83.52
Multi-voltage
Multi-function Multi-voltage
Multi-function
Timing can be regulated using ext.
Potentiometer
2 timed contacts or 1 timed + 1
instantaneous contact
Multi-voltage
Multi-function
Timing can be regulated using ext.
Potentiometer
2 timed contacts or 1 timed + 1
instantaneous contact
3 functions with pause option
AI: On-delay
DI: Interval
GI: Pulse delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control
signal
DE: Interval with control signal on
WD: Watchdog (Retriggerable
interval with control signal on)
AI: On-delay
DI: Interval
GI: Pulse delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control
signal
DE: Interval with control signal on
WD: Watchdog (Retriggerable
interval with control signal on)
AE: On-delay with control signal
GE: Pulse delayed with control
signal on
IT: Timing step
FE: Interval with control signal
on and off
EEa: Interval with control signal
off (retriggerable)
DEp: Interval with control signal
on and pause signal
BEp: Off-delay with control signal
and pause signal
SHp: “Shower function
Wiring diagram
(with control signal)
Wiring diagram
(without control signal)
Wiring
diagram
(without control signal)
Wiring
diagram
(with control signal)
Wiring
diagram
(with control signal and external
potentiometer connection)
Wiring
diagram
(with control signal
and pause signal)
(1) Short term (10 min) + 70°C
For outline drawing see page 7
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 16/30 12/30 12/30
Rated voltage/
Maximum switching voltage V
AC 250/400 250/400 250/400
Rated load AC1 VA 4000 3000 3000
Rated load AC15 (230VAC) VA 750 750 750
Single phase motor rating (230VAC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220V A 16/0.3/0.12 12/0.3/0.12 12/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) VAC (50/60Hz) 24…240 24…240 24…240
VDC 24…240 24…240 24…240
Rated power AC/DC VA (50Hz)/W <1.5/<2 <2/<2 <2/<2
Operating range VAC 16.8…265 16.8…265 16.8…265
V DC 16.8…265 16.8…265 16.8…265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5…10)min, (0.05…1)h, (0.5…10)h, (0.05…1)d, (0.5…10)d
Repeatability % ±1 ±1 ±1
Recovery time ms 200 200 200
Minimum control impulse ms 50 50 50
Setting accuracy-full range % ±5 ±5 ±5
Electrical life at rated load in AC1 cycles 50·10360·10360·103
Ambient temperature range °C –20…+60(1) –20…+60(1) –20…+60(1)
Protection category IP 20 IP 20 IP 20
Approvals (according to type)
3
83
SERIES
83 SERIES
Modular timers 12- 16A
V-2019,www.findernet.com
H
Mono-function timer range
Type 83.11
- ON-delay, multi-voltage
Type 83.21
- Interval, multi-voltage
Type 83.41
- Off-delay with control signal,
multi-voltage
1 Pole
22.5mm wide
Eight time scales from 0.05s to 10days
High input/output isolation
Wide supply range (24…240)VAC/DC
35mm rail (EN60715) mount
“Blade + cross” - both flat blade and cross head
screw drivers can be used to adjust the range
and function selectors, the timing trimmer, and
to disengage the rail mounting clip
Multi-voltage versions with “PWM clever”
technology
Complies with EN 45545-2:2013 (protection
against fire of materials), EN 61373 (resistance
against random vibrations and shock,
Category 1, Class B), EN 50155 (resistance to
temperature and humidity, T1 class)
83.11 83.21 83.41
Multi-voltage
Mono-function
Multi-voltage
Mono-function
Multi-voltage
Mono-function
AI: On-delay DI: Interval BE: Off-delay with control signal
(1) Short term (10 min) + 70°C
For outline drawing see page 7
Wiring diagram
(without control signal)
Wiring diagram
(without control signal)
Wiring diagram
(with control signal)
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 16/30 16/30 16/30
Rated voltage/
Maximum switching voltage V
AC 250/400 250/400 250/400
Rated load AC1 VA 4000 4000 4000
Rated load AC15 (230VAC) VA 750 750 750
Single phase motor rating (230VAC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220V A 16/0.3/0.12 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) VAC (50/60Hz) 24…240 24…240 24…240
VDC 24…240 24…240 24…240
Rated power AC/DC VA (50Hz)/W <1.5/<2 <1.5/<2 <1.5/<2
Operating range VAC 16.8…265 16.8…265 16.8…265
VDC 16.8…265 16.8…265 16.8…265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5…10)min, (0.05…1)h, (0.5…10)h, (0.05…1)d, (0.5…10)d
Repeatability % ±1 ±1 ±1
Recovery time ms 200 200 200
Minimum control impulse ms 50
Setting accuracy-full range % ±5 ±5 ±5
Electrical life at rated load in AC1 cycles 50·10350·10350·103
Ambient temperature range °C –20…+60(1) –20…+60(1) –20…+60(1)
Protection category IP 20 IP 20 IP 20
Approvals (according to type)
4
83 SERIES
Modular timers 16A
83
SERIES
V-2019,www.findernet.com
H
Mono-function and multi-function timer range
Type 83.62
- Power off-delay, multi-voltage, 2 Pole
Type 83.82
- Star-Delta, multi-voltage, star and delta
output contacts
Type 83.91
- Asymmetrical flasher, multi-voltage,
1 Pole
22.5mm wide
Time scales:
Type 83.62 - 0.05s to 3 minutes
Type 83.82/83.91 - 0.05s to 10days
Wide supply range (24…240)VAC / DC
35mm rail (EN60715) mount
Complies with EN 45545-2:2013 (protection
against fire of materials), EN 61373 (resistance
against random vibrations and shock,
Category 1, Class B), EN 50155 (resistance to
temperature and humidity, T1 class)
* (0.05…2)s, (1…16)s, (8…70)s, (50…180)s
** (0.05…1)s, (0.5…10)s, (0.05…1)min,
(0.5…10)min, (0.05…1)h, (0.5…10)h,
(0.05…1)d, (0.5…10)d
*** 0.05 s, 0.2 s, 0.3 s, 0.45 s, 0.6 s, 0.75 s,
0.85 s, 1 s
83.62 83.82 83.91
Multi-voltage
Mono-function
2 pole
Multi-voltage
Mono-function
2 pole
Transfer time can be regulated
(0.05…1)s***
Multi-voltage
Multi-function
BI: Power off-delay (True off-delay) SD: Star-delta LI: Asymmetrical flasher
(starting pulse on)
LE: Asymmetrical flasher (starting
pulse on) with control signal
PI: Asymmetrical flasher
(starting pulse off )
PE: Asymmetrical flasher (starting
pulse off) with control signal
Wiring diagram
(with control signal)
Wiring diagram
(without control signal)
(1) Short term (10 min) + 70°C
For outline drawing see page 7
Wiring diagram
(without control signal)
Wiring diagram
(without control signal)
Contact specification
Contact configuration 2 CO (DPDT) 2 NO (DPST-NO) 1 CO (SPDT)
Rated current/Maximum peak current A 8/15 16/30 16/30
Rated voltage/
Maximum switching voltage VAC 250/400 250/400 250/400
Rated load AC1 VA 2000 4000 4000
Rated load AC15 (230VAC) VA 400 750 750
Single phase motor rating (230VAC) kW 0.3 0.5 0.5
Breaking capacity DC1: 30/110/220V A 8/0.3/0.12 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) VAC (50/60Hz) 24…240 24…240 24…240
VDC 24…220 24…240 24…240
Rated power AC/DC VA (50Hz)/W <1.5/<2 <1.5/<2 <1.5/<2
Operating range VAC 16.8…265 16.8…265 16.8…265
V DC 16.8…242 16.8…265 16.8…265
Technical data
Specified time range * **
Repeatability % ±1 ±1 ±1
Recovery time ms 200 200
Minimum control impulse ms 500 ms (A1 - A2) 50
Setting accuracy-full range % ±5 ±5 ±5
Electrical life at rated load in AC1 cycles 100·10350·10350·103
Ambient temperature range °C –20…+60(1) –20…+60(1) –20…+60(1)
Protection category IP 20 IP 20 IP 20
Approvals (according to type)
5
83
SERIES
83 SERIES
Modular timers 8- 16A
V-2019,www.findernet.com
H
Ordering information
Example: 83 series, modular timers, 1 CO (SPDT) - 16A, supply rated at (24…240)VAC/DC.
8 3 . 0 1 . 0 . 2 4 0 . 0 0 0 0
Series
Type
0 = Multi-function
(AI, DI, GI, SW, BE, CE, DE, WD)
1 = On-delay (AI)
2 = Interval (DI)
4 = Off-delay with control signal (BE)
5 = Multi-function
(AE, GE, IT, FE, EEa, DEp, BEp, SHp)
6 = Power off-delay (True off-delay) (BI)
8 = Star-delta (SD)
9 = Asymmetrical flasher (LI, LE, PI, PE)
Versions
0000 = Standard
Supply voltage
240 = (24 … 240)VAC/DC
Supply version
0 = AC (50/60Hz)/DC
No. of poles
1 = 1 CO (SPDT)
2 = 2 CO (DPDT) for 83.02, 83.52 and 83.62
2 = 2 NO (DPST-NO) for 83.82
Technical data
Insulation
Dielectric strength between input and output circuit VAC 4000
between open contacts VAC 1000
Insulation (1.2/50µs) between input and output kV 6
EMC specifications
Type of test Reference standard 83.01/02/52/11/21/41/82/91 83.62
Electrostatic discharge contact discharge EN61000-4-2 4kV 4kV
air discharge EN61000-4-2 8kV 8kV
Radio-frequency electromagnetic field (80÷1000MHz) EN61000-4-3 10V/m 10V/m
(1000÷2700MHz) EN61000-4-3 3V/m 3V/m
Fast transients (burst) (5-50ns, 5 and 100kHz) on Supply terminals EN 61000-4-4 7kV 6kV
on control signal terminal (B1) EN 61000-4-4 7kV 6kV
Surges (1.2/50µs) on Supply terminals common mode EN61000-4-5 6kV 6kV
differential mode EN61000-4-5 6kV 4kV
on control signal terminal (B1) common mode EN61000-4-5 6kV 6kV
differential mode EN61000-4-5 4kV 4kV
Radio-frequency common mode (0.15÷80MHz) EN61000-4-6 10V 10V
on Supply terminals (80÷230MHz) EN61000-4-6 10V 10V
Radiated and conducted emission EN55022 class A class A
Other data
Current absorption on control signal (B1) <1mA
- max cable length (capacity of ≤10nF/100m) 150m
- when applying a control signal to B1, which
is different from the supply voltage at A1/A2
B1 is isolated from A1 and A2 by an opto-coupler, and can therefore be
operated at a voltage other than the supply voltage.
If using a control signal of between (24… 48)VDC and a supply voltage
of (24…240)VAC, ensure that the signal - is connected to A2 and the +
is applied to B1, and that L is applied to B1 and N to A2.
External potentiometer for 83.02/52 Use a 10kΩ/≥0.25W linear potentiometer. Maximum cable length 10
m. When using an external potentiometer, the timer automatically use
its setting in place of the internal setting.
Consider the voltage potential at the potentiometer to be the same as
the timer supply voltage.
Power lost to the environment without contact current W 1.4
with rated current W 3.2
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm21x6 / 2x4 1x4 / 2x2.5
AWG 1x10 / 2x12 1x12 / 2x14
6
83 SERIES
Modular timers 16A
83
SERIES
V-2019,www.findernet.com
H
Outline drawings
Type 83.01
Screw terminal
Types 83.02/52
Screw terminal
Type 83.11
Screw terminal
Type 83.21
Screw terminal
Type 83.41
Screw terminal
Type 83.62
Screw terminal
Type 83.82
Screw terminal
Type 83.91
Screw terminal
7
83
SERIES
83 SERIES
Modular timers 16A
V-2019,www.findernet.com
H
Accessories
060.48
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
83.01/11/21/41/62/82, plastic, 48 tags, 6x12mm 060.48
087.02.2
Z1 Z2
Potentiometer usable as external potentiometer for type 83.02/52
10kΩ/0.25W linear, IP 66 087.02.2
Functions LED* Supply
voltage
NO output
contact
Contacts
Open Closed
OFF Open 15 - 18
25 - 28
15 - 16
25 - 26
ON Open 15 - 18
25 - 28
15 - 16
25 - 26
ON Open
(Timing in Progress)
15 - 18
25 - 28
15 - 16
25 - 26
ON Closed 15 - 16
25 - 26
15 - 18
25 - 28
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
*
* With DC supply, positive polarity has to be connected to B1 terminal (according to EN60204-1).
** ** A voltage other than the supply voltage can be applied to the control signal (B1), example:
A1 - A2 = 230VAC
B1 - A2 = 12VDC
8
83 SERIES
Modular timers 16A
83
SERIES
V-2019,www.findernet.com
H
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Multi-function
without control signal
83.01
***
83.02
Type
83.01
83.02
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset time has
elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(GI) Pulse delayed.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs after a fixed time of 0.5s.
(SW) Symmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately and
cycle between ON and OFF for as long as power is applied. The ratio
is 1:1 (time on= time off).
with control signal
83.01
83.02
***
*** Type 83.02: regulated using
an external potentiometer
(10 kΩ - 0.25 W).
(BE) Off-delay with control signal.
Power is permanently applied to the timer. The output contacts
transfer immediately on closure of the control signal (S).
Opening the control signal initiates the preset delay, after which
time the output contacts reset.
(CE) On- and off-delay with control signal.
Power is permanently applied to the timer.
Closing the control signal (S) initiates the preset delay, after which
time the output contacts transfer. Opening the control signal
initiates the same preset delay, after which time the output contacts
reset.
(DE) Interval with control signal on.
Power is permanently applied to the timer.
On momentary or maintained closure of control signal (S), the
output contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
(WD) Watchdog (Retriggerable interval with control signal on).
Power is permanently applied to the timer.
On momentary or maintained closure of control signal (S), the
output contacts transfer, and remain so for the duration of the
preset delay, after which they reset; subsequent closures of control
signal during the delay will extend the time. If the closure of the
control signal (S) is longer than the preset time (T) then the output
contacts reset.
NOTE: The timing function must be set when the timer is de-energised. Or for the 83.02/52, when the contact mode selector is in the OFF position.
83.02 type
Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE)
2 timed contacts
Both output contacts (15-18 and 25-28)
follow the timing function
Both output contacts (15-18 and 25-28)
follow the timing function
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
1 timed +
1 instantaneous contact
The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U)
The output contact 15-18 follows the timing function
The output contact 21-24 follows the control signal (S)
9
83
SERIES
83 SERIES
Modular timers 16A
V-2019,www.findernet.com
H
Functions
Wiring diagram U = Supply voltage S = Signal switch P = Pause switch = Output contact
Multi-function
with control signal
***
*** Regulated using an
external potentiometer
(10kΩ- 0.25W).
Type
83.52
AE
T
(AE) On-delay with control signal.
Power is permanently applied to the timer.
Closing the Signal Switch (S) initiates the preset delay, after which times the
output contacts transfer and remain so until the power is removed.
(EEa) Interval with control signal off (retriggerable).
Power is permanently applied to the timer.
On opening of the Signal Switch (S) the output contacts transfer, and remain so
for the duration of the preset delay, after which they reset.
(FE) Interval with control signal on and off.
Power is permanently applied to the timer.
Both the opening and the closing of the Signal Switch (S) initiates the transfer of
the output contacts. In both instances the contacts reset after the preset delay
has elapsed.
(GE) Pulse delayed with control signal on.
Power is permanently applied to the timer.
Closing the Signal Switch (S) initiates the preset delay, after which the output
contacts transfer. Reset occurs after a fixed time of 0.25s.
(IT) Timing step.
Closing the Signal Switch (S) the output contacts transfer and remain so, after S
opening, for the duration of the preset delay, after which they reset. During the
timing period it is possible to immediate open the contact with a further impulse on S.
with control signal and pause
signal
(BEp) Off-delay with control signal and pause signal.
Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. The current state of the output contacts will be maintained. On
opening of the pause switch, timing resumes from the retained value.
(DEp) Interval with control signal on and pause signal.
Power is permanently applied to the timer. On momentary or maintained closure
of Signal Switch (S), the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset. Closure of the pause switch (X1-X2)
will immediately halt the timing process, but the elapsed time will be retained. The
current state of the output contacts will be maintained. On opening of the pause
switch, timing resumes from the retained value.
(SHp) “Shower” function (Off-delay with control signal and pause signal).
Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. During the pause, the output contacts 15-18 and 25-28 will
be open. On opening of the pause switch, timing resumes from the retained value
and the output contacts will take the previous condition.
83.52 type
Contact mode selector Functions with control signal and pause signal
(example: BEp) Function SHp
2 timed contacts
Both output contacts (15-18 and 25-28) follow the timing function Both output contacts (15-18 and 25-28) follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] stay permanently open Both output contacts [15-18 and 25(21)-28(24)] stay permanently open
1 timed +
1 instantaneous contact
The output contact 15-18 follows the timing function
The output contact 21-24 follows the control signal (S) The output contact 15-18 follows the timing function.
The output
contact 21-24 is always open, unless during the pause, when is closed
10
83 SERIES
Modular timers 16A
83
SERIES
V-2019,www.findernet.com
H
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Mono-function
without control signal
83.11
83.21
83.82
83.62
Type
83.11
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset time has
elapsed. Reset occurs when power is removed.
83.21 (DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
83.62 (BI) Power off-delay (True off-delay).
Apply power to timer (minimum 500ms). Output contacts transfer
immediately. Removal of power initiates the preset delay, after which
time the output contacts reset.
83.82 (SD) Star-delta.
Apply power to timer. The star contact ( ) closes immediately. After
preset delay has elapsed the star contact ( ) resets.
After a further time (settable from 0.05s to 1s) the delta contact ( )
closes and remains in that position, until reset on power off.
with control signal (S)
83.41
83.41 (BE) Off-delay with control signal.
Power is permanently applied to the timer.
The output contacts transfer immediately on closure of the control
signal (S). Opening the control signal initiates the preset delay, after
which time the output contacts reset.
Asymmetrical recycler
without control signal
83.91
Z1-Z2 open: (LI) function
Z1-Z2 linked: (PI) function
Z1-Z2 open: (LE) function
Z1-Z2 linked: (PE) function
83.91
with control signal
83.91 (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
Apply power to timer. Output contacts transfer immediately and cycle
between ON and OFF for as long as power is applied. The ON and OFF
times are independently adjustable.
(PI) Asymmetrical flasher (starting pulse off) - (Z1-Z2 linked).
Apply power to timer. Output contacts transfer after time T1 has
elapsed and cycle between OFF and ON for as long as power is applied.
The ON and OFF times are independently adjustable.
(LE) Asymmetrical flasher (starting pulse on) with control signal -
(Z1-Z2 open).
Power is permanently applied to the timer.
Closing control signal (S) causes the output contacts to transfer
immediately and cycle between ON and OFF, until opened.
(PE) Asymmetrical flasher (starting pulse off) with control signal -
(Z1-Z2 linked).
Power is permanently applied to the timer.
Closing the control signal (S) initiates delay T1 after which the output
contacts transfer and continue to cycle between OFF and ON, until the
control signal is opened.
Times scales
Rotary switch position series 83
1 s10 s1 m 10 m10 h
1 h1 d10 d
(0.05
1)s (0.5
10)s (0.05
1)min (0.5
10)min (0.05
1)h (0.5
10)h (0.05
1)d (0.5
10)d
Please see general technical information 11
83
SERIES
83 SERIES
Modular timers 16A