2 Specifications are subject to change without notice (05.12.2014)
Power ON delay 2 s
Indication for
Com-port TX LED, red
Supply ON LED, green
Dupline® carrier LED, yellow
Environment
Pollution degree 2 (IEC 60664)
Operating temperature
0° to +50°C (+32° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Mode of Operation
The Dupline® Master Module
(DMM) controls a 3-wire bus
with signal, DC-power and
common GND. The DMM
is connected to a standard
DC-supply, which it synchron-
izes with the Dupline® carrier
signal before it is outputted to
supply. The synchronization is
necessary in order to enable
the Dupline® and DC-supply to
share the GND-wire.
The Dupline® Master Module is
a Dupline® Channel Generator
with the function of a mas-
ter. This means that the 128
Dupline® I/O’s will be read/
written by the DMM and then
sent to the PLC.
The DMM can run in two dif-
ferent modes – Normal mode
and split I/O mode. In Normal
mode, Dupline® operates as
a peer-to-peer system, where
the channel generator auto-
matically establishes a con-
nection between Dupline®
inputs and Dupline® outputs
which are coded to the same
Dupline® address. If e.g. an
input coded for B5 is activat-
ed, the output(s) coded for B5
will also be activated.
Consequently, a Dupline®-
output can either be activat-
ed through the output-data
received on DMM or by an
active Dupline® input coded for
the same Dupline®-address. In
“Split I/O” mode, the channel
generator treats the Dupline®
inputs and Dupline® outputs
independently. If e.g. an input
coded for B5 is activated, the
DMM will make the informa-
tion available for the PLC (like
in normal mode), but it will
not automatically activate the
Dupline® output(s) coded to
B5. The Dupline® outputs are
controlled exclusively through
the output data received from
the PLC. In this mode, up
to 128 Dupline® inputs and
128 Dupline® outputs are
available, since an input and
an output coded to the same
Dupline® address can operate
independently.
G 3496 0009
General Specifications
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions H4-Housing
Weight 100 g
Installation Hints
TX-LED
Slow flashing No communication
Check the wiring.
Fast flashing Communication OK.
No Dupline® Carrier-LED
Dupline® Short curcuit Short curcuit between the
two Dupline® wires.
Pin Assignment
1
9
8
7
6
5
4
3
2
7
3
2
Master Module
D-sub. 9p M
FP PLC
D-Sub. 9p M
RS232
4
5
8
9
Dip-Switch Setting
Sw.3 On: 19200 baud
Off: 9600 baud
Sw.4 On: Split I/O Channel Generator Mode
(Receivers activated by the PLC)
Off: Normal Dupline® Monostable Channel
Generator Mode
Sw.5 On: 64 Dupline® channels
Off: 128 Dupline® channels
Address R7.F (P8) = High: Dupline® error
(e.g. short-circuit)
Memory Mapping
Dupline® PLC Dupline® PLC
Channel Read Write Channel Read Write
A1 R00 R80 E1 R20 R100
A2 R01 R81 F1 R28 R108
A3 R02 R82 G1 R30 R110
A4 R03 R83 H1 R38 R118
A5 R04 R84 I1 R40 R120
A6 R05 R85 J1 R48 R128
A7 R06 R86 K1 R50 R130
A8 R07 R87 L1 R58 R138
B1 R08 R88 M1 R60 R140
B8 R0F R8F N1 R68 R148
C1 R10 R90 O1 R70 R150
D1 R18 R98 P1 R78 R158
Table of the memory mapping to the PLC