Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
24
1Power Protection and Conditioning
STFE Elite Series - Active Tracking® Filters with Surge Protection
The SolaHD STF Elite DIN Rail Mount Series combines
Active Tracking® technology with UL Listed surge
protection to protect against the full spectrum of voltage
transients and surges. It continuously tracks the input AC
power line responding instantly into action upon detecting
extraneous high frequency noise and high voltage transients
caused by everyday events such as turning on machinery,
motors, or equipment.
These devices are designed to meet UL 1449 3rd Edition,
UL 1283, cUL recognized, and CE. STFE attenuates or
reduces the amplitude of normal mode noise to a minimum
of 90dB that occurs in a frequency range of 100KHz to
50MHz, and of common mode noise to a minimum of 60dB
that occurs in a frequency range of 5MHz to 50MHz. STFE
provides the industry’s best IEEE C62.41 Category “A & B”
Ringwave protection.
They are built to meet your unique requirements, and
are available in hardwired DIN Rail mount, single phase
conguration. They are designed for years of trouble free
operation and require little or no operator intervention after
installation.
Related Products
Power Conditioners
Uninterruptible Power System
Power Supplies
Selection Table
Catalog
Number Input Voltage
STFE030-10N 120 V Single Phase 2 Wire + Ground
STFE050-10N 120 V Single Phase 2 Wire + Ground
STFE100-10N 120 V Single Phase 2 Wire + Ground
STFE200-10N 120 V Single Phase 2 Wire + Ground
STFE030-24L 240 V Single Phase 2 Wire + Ground
STFE050-24L 240 V Single Phase 2 Wire + Ground
STFE100-24L 240 V Single Phase 2 Wire + Ground
STFE200-24L 240 V Single Phase 2 Wire + Ground
Features
Series connected DIN Rail mounted lter
Durable metal mount clip
UL Listed surge current capacity – 45,000 Amps
Transient protection in all modes (L-N, L-G, and N-G)
Single Phase applications up to 20 Amp
Operating Temperature from -40°C to +50°C
Screw Terminal Connections
- Reliable and convenient screw clamp connections
- Accept 10-16 AWG wire
- Meet IP20 specications for ingress protection
LED status indication
Form C contact for remote monitoring
UL 1449 3rd Edition, UL 1283, cUL recognized
component, CE
5 Year Limited Warranty
Applications
Control Panels
Factory Automation Installations
Point of Use Industrial Equipment
Programmable Logic Controllers
Dedicated Industrial and Machine Tools Equipment
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 25
1
Power Protection and Conditioning
Description STFEXXX-10N STFEXXX-24L
Input Voltage 120 V (0-150 VRMS) 240 V (0-275 VRMS)
Line Frequency 47 - 63 Hz
Response Time < .5 ns normal mode, <5 ns common mode
Enclosure Fully Enclosed Metal Housing
Fusing Reference Fuse/Circuit Breaker Chart
Status Indication Green LED “OK”/Form C Contact/10 Amps @ 250 Vac or 5 Amps @ 100 Vdc
Connection/Mounting Type DIN Rail Mount
Operating Temperature -40°C to +50°C at full load Derate Linearly to 60% at +70ºC
Weight (Kg) 1.7 lbs (0.7kg)
Dimensions - in (mm)
(H x W x D)
4.88 x 2.56 x 4.56
(124 x 65 x 116)
Operating Humidity 0% to 95% Non-condensing
Peak Surge Current Capability
Per Phase 30,000 Amps
Line to Neutral 20,000 Amps
Line to Ground 10,000 Amps
Neutral to Ground 10,000 Amps
Load Surge Current Rating
10m Sec 5 x Nominal
1 sec 3 x Nominal
10 sec 2 x Nominal
Frequency Response
Normal Mode (Forward-Reverse) 100 kHz to 50 MHz 90 dB Max
Common Mode (Forward-Reverse) 5 MHz to 50 MHz 60 dB Max
Transient Reduction
(IEEE C62.41)
Typical Category A Ringwave
(6 kV, 200A, 100 kHz) < 60 V Peak
Typical Category B Ringwave
(6 kV, 500A, 100 kHz) <100 V Peak UL 1449
Safety UL 1449 3rd Edition, UL1283, cUL Recognized Component, CE
STFE Specifications
Connection Diagram
LINE LOAD
L/L1
N/L2
GND
L/L1
N/L2
GND
L/L1
TO
REMOTE INDICATION
IF NEEDED
TO LOAD OR
EQUIPMENT
PROTECT
RELAY
CONTACTS
NO COM NC
L/L1
N/L2
N/L2
GND
GND
LINE INPUT
FROM SOURCE
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
26
1Power Protection and Conditioning
Dimensional Diagram
Active Tracking Filter
STFE Elite Series
NO COM NC L/L1 N/12
L/L1 N/L2
2.560
4.560
4.880
Catalog Number Amps Min Wire Size*
(AWG Suggested)
Fuse/Circuit Breaker Ampacity
Suggest Max
Single-Phase Models (120 Vac)
STFE030-10N 3.0 24 3A 3.75A
STFE050-10N 5.0 22 5A 6.25A
STFE100-10N 10.0 20 10A 12.5A
STFE200-10N 20.0 12 20A 25A
Single-Phase Models (240 Vac)
STFE030-24L 3.0 24 3A 3.75A
STFE050-24L 5.0 22 5A 6.25A
STFE100-24L 10.0 20 10A 12.5A
STFE200-24L 20.0 12 20A 25A
Wiring Specifications
Internal View
of Components
MOV Array
provides high-energy
all mode protection
Series Blocking Inductor
blocks voltage, smooths current
Silicone Avalanche Diodes
fast responding surge suppressor
Finger Safe Terminals
Green LED Unit Status Indicator
Pulse Capacitor
high-frequency noise absorption
Form C Relay Contacts
DC OK signal
Rear View
DIN Connector
Strong all metal for
horizontal or vertical
mounting
Internal Diagram
*16 AWG wire or larger may be required by code dependent upon
the application.