ACDC
Specification
6501200 Watts
•Rugged Construction
•Variable Fan Speed for Noise Reduction
•20 ºC to +70 ºC Operation
•AC OK, Remote On/Off and Active Current Share
•5 V Standby
•Screw Terminals
•3 Year Warranty
MHP Series
Input
Input Voltage • 650 W: 80-264 VAC, derate output power
10% <90 VAC, and 20% <85 VAC,
1000 W: 85-264 VAC, derate output power
10% <90 VAC
Input Frequency • 47-63 Hz
Input Current • 650 W: 6.5 A at 115 VAC typical, 3.2 A at
230 VAC full load,
1000 W: 10.9 A at 115 VAC typical, 5.1 A
at 230 VAC full load
Inrush Current • 650 W: 40 A max at 264 VAC
1000 W: 60 A max at 264 VAC
Power Factor • >0.9
Earth Leakage Current • 250 µA max at 264 VAC/60 Hz
Input Protection • 650 W: T16 A/250 V, 1000 W: T20 A/250 V
internal fuse in line and neutral
Output
Output Voltage • 12-48 VDC (see tables)
Output Voltage Trim • ±10% V1
Initial Set Accuracy • 650 W: ±1% V1, ±5% V3,
1000 W: ±1% V1, ±5% V2
Minimum Load • No minimum load required
Start Up Delay • 500 ms max
Start Up Rise Time • 50 ms typical
Hold Up Time • 20 ms minimum
Drift • ±0.2% after 20 min warm up
Line Regulation • ±0.5%
Load Regulation • 650 W: ±1% V1, ±5% V3,
1000 W: ±1% V1, ±5% V2
Transient Response • 4% max. deviation, recovery to
within 1% in 500 µs for a 50-75-50%
load change
Ripple & Noise • 1% pk-pk V1, 20 MHz bandwidth
Overvoltage Protection • 115-145% Vnom, recycle input to reset
Overload Protection • 110-140%, V1 only
Overtemperature • Auto reset
Protection
Short Circuit Protection • Constant current characteristic
Temp. Coefficient • 0.05% / °C
Remote Sense • Compensates for 0.5 V total voltage drop
Remote On/Off • Uncommitted isolated optocoupler diode,
powered diode inhibits V1 and fan supply (1)
Current Share • Single wire current share (1)
(1) See longform datasheet for more information
xppower.com
General
Efficiency • 85% typical
Isolation • 4000 VAC In to Out, 2 x MOPP, 1500 VAC
In to Earth, 1 x MOPP, 500 VDC Out to
Earth
Switching Frequency • PFC 70 kHz, main converter 200 kHz,
standby 130 kHz typical
Power Density • 650 W: 8.2 W/in3,1000 W: 8.9 W/in3
Signals • AC OK, remote on/off, current share (1)
MTBF • 260 KHrs to MIL-HDBK-217F at 25 °C, GB
Environmental
Operating Temperature • -20 °C to +70 °C, derate linearly from
+50 °C at 2.5% / °C to 50% at +70 °C,
1000 W: -40 °C start up
Cooling • 650 W: Forced cooled, ‘-TF’ & ‘-EF’
models have integral dual voltage level fan,
which is load dependant, U Channel
requires 5.5 m/s minimum airflow,
1000 W: Forced cooled via integral quad
voltage level fan which is load dependant (1)
Operating Humidity • 95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude • 3000 m
Shock • 30 g pk, half sine, 6 axes
Vibration • 2 g rms, 5 Hz to 500 kHz, 3 axes
EMC & Safety
Emissions • EN55022/ENN55011 class B conducted
EN55022/EN55011 class A radiated
Harmonic Currents • EN61000-3-2 class A,
650 W: class C for loads ≥20%
1000 W: classCfor loads ≥10%
Voltage Flicker • EN61000-3-3
ESD Immunity • EN61000-4-2, level 3 contact, level 3 air,
Perf Criteria A
Radiated Immunity • EN61000-4-3, level 3 Perf Criteria A
EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
Surge • EN61000-4-5, installation class 3,
Perf Criteria A
Conducted Immunity • EN61000-4-6, level 3, Perf Criteria A
Dips & Interruptions • EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms, Perf Criteria
A, A, A, B. Consult longform for 115 VAC
operation
Safety Approvals • IEC60601-1 CB report, CSA 22.2
No.60601-1, ANSI/AAMI ES60601-1, TUV,
EN60601-1 Including Risk Management