Product Net Depth: 105 mm
Product Net Weight: 1.815 kg
4 lb
Rated Operational Current AC-
21A (I ):
(380 ... 415 V) 160 A
(500 V) 160 A
(690 V) 160 A
Rated Operational Current AC-
22A (I ):
(380 ... 415 V) 160 A
(500 V) 160 A
(690 V) 160 A
Rated Operational Current AC-
23A (I ):
(380 ... 415 V) 160 A
(500 V) 160 A
(690 V) 160 A
Rated Operational Power AC-23A
(P ):
(220 ... 240 V) 45 kW
(400 V) 75 kW
(415 V) 75 kW
(500 V) 90 kW
(690 V) 132 kW
Conventional Free-air Thermal
Current (I ):
q = 40 °C 160 A
Conventional Thermal Current (I
):
Fully Enclosed 160 A
Rated Impulse Withstand Voltage
(U ):
12 kV
Rated Insulation Voltage (U ): 1000 V
Rated Operational Voltage: 690 V AC
Rated Short-time Withstand
Current (I ):
for 1 s 5 kiloampere rms
Power Loss: at Rated Operating Conditions per Pole 9 W
Pollution Degree: 3
Handle Type: Handle and shaft not included
Switches Operating Mechanism: 03 (Left Side)
Position of Line Terminals: Top In - Bottom Out
Bottom In - Top Out
Fuse Size: 100 A
Fuse System: Class J
Operating Mode: Front Operated
Standards: UL98
Mounting Type: Base mounting
Number of Poles: 3
Terminal Type: Lug terminals
Terminal Width: 20 mm
Horsepower Rating UL/CSA: (acc. to UL 240 V) 30 Hp
(acc. to UL 480 V) 60 Hp
(acc. to UL 600 V) 75 Hp
Ampere Rating UL/CSA: 100 A
Tightening Torque UL/CSA: Wire-Clamp 120 in·lb
Cable Lug 50 in·lb