PowerLogic™ EM3500
Description
The EM3500 Series DIN Rail Meter combines exceptional performance and easy
installation to deliver a cost-effective solution for power monitoring applications. The
EM35xx can be installed on standard DIN rail or surface mounted as needed. Pulse
output and phase alarms provide additional versatility. The Modbus and BACnet
output options offer added exibility for system integration. The data logging
capability (EM3555 and EM3560) protects data in the event of a power failure.
Modbus, pulse output, and phase alarms are all provided to suit a wide variety of
applications.
Additional pulse inputs on EM3560 provide an easy way to incorporate simple ow
sensors to track gas, water, steam, or other energy forms using a BACnet system in
addition to full monitoring of electrical energy.
The EM3555 models adds a bi-directional monitoring feature designed expressly for
renewable energy applications, allowing measurement of power imported from the
utility grid as well as power exported from the renewable energy source (e.g. solar
panels). In this way, a facility administrator track all energy data, ensuring accuracy
in billing and crediting.
Applications
b Energy monitoring in building automation systems
b Renewable energy monitoring
b Energy management
b Commercial submetering
b Industrial monitoring
b Cost allocation
Features
All Models: A compact solution for panelboard monitoring
b DIN rail mounting option; easy installation
b ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S; great for cost allocation
b Real energy output and phase loss alarm output on EM3502, EM3550, and
EM3555 models; one device serves multiple applications
b 90-600 VAC; application versatility with fewer models to stock
b Bright backlit LCD; easy visibility in dark enclosures
b Data logging capability EM3555 and EM3560; safeguard during power failures
b Compatible with LVCTs from 5A to 32000A; wide range of service types
b User-enabled password protection; prevents tampering
b System integration via Modbus EM355x or BACnet MS/TP EM3560; convenient
compatibility with existing systems
b Native BACnet MS/TP support (no gateway) with serial rates up to 115.2 kbaud
EM3560
EM3555 Models: An essential solution for Solar and other renewable energy
applications
b Bi-directional metering (4-quadrant); allows net metering
b Data logging capability; ensures long term data retrieval
b CSI approved
EM3500
Functions and characteristics
Basic energy metering
Model Description Part Numbers
EM3502 Pulse out only METSEEM3502
EM3550 Modbus - 2 quadrant METSEEM3550
EM3555 Modbus - 4 quadrant with logging METSEEM3555
EM3560 BACnet with logging METSEEM3560
PB105418PB105419
EM3500 parts and connection terminals
EM3502/EM355x parts and connection terminals
Version 1.0
PLSED310035EN.indd 3
EM3500
Functions and characteristics (cont.)
Basic energy metering
Selection guide
Electrical characteristics
Inputs Control Power, AC 50/60 Hz; 5VA max.; 90V min.;
UL Maximums: 600V L-L (347V L-N );
CE Maximums: 300V L-N (520V L-L )
Control Power, DC 3W max.; UL and CE: 125 to 300VDC
(external DC current limiting required)
Voltage Input UL: 90 V L-N to 600 V L-L ;
CE: 90 V L-N to 300 V L
Current Input Scaling 5 A to 32,000 A
Input Range 1/3V and 1V nominal LVCT (selectable)
Pulse Inputs (EM3560 only) Two sets of contact inputs to pulse accumulators
Accuracy Real Power and Energy 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S)
Outputs All Models (except
EM3560)
Real Energy Pulse: N.O. static;
Alarm contacts: N.C. static
EM3502 Reactive energy pulse 30 VAC/DC
EM355x RS-485 2-wire Modbus RTU
(1200 baud to 38.4 kbaud)
EM3560 RS-485 2-wire BACnet MS/TP
(9600 baud to 115.2 kbaud)
Mechanical characteristics
Mounting DIN Rail or 3-point screw mount
Environmental conditions
Operating temperature Range -30° to 70°C (-22° to 158°F)
Storage Temperature Range -40° to 85°C (-40° to 185°F)
Humidity Range <95% RH noncondensing
Accessories
NEMA4 enclosure (EM3500-ENC, pictured)
Lock and key set (EM3500-KEY)
Split-core low voltage CTs (LVCTxx)
Fuse kits (EFP1, EFP2, EFP3)
Safety
US and Canada (cULus) UL508 (open type device)/CSA 22.2 No. 14-05
Europe (CE) EN61010-1:2001
PB105437
EM3500 in enclosure with door open
EM3500 in enclosure with door open
Version 1.0 PLSED310035EN.indd
4
PE86288
PowerLogic™ ION7550 / ION7650 rear view.
EM3502
EM3550
EM3555
EM3560
Measurement Capability - Full Data Set
Bi-directional Energy Measurements b
Power (3-phase total and per phase) - Real (kW), Reactive (kVAR), and
Apparent (kVA)
bbbb
Power Factor: 3-phase average and per phase bbbb
Present Power Demand - Real (kW), Reactive (kVAR), and Apparent (kVA) bbbb
Import and Export totals of Present Power Demand - Real (kW), Reactive
(kVAR), and Apparent (kVA)
b
Peak Power Demand - Real (kW), Reactive (kVAR), and Apparent (kVA) bbbb
Current: (3-phase average and per phase) bbbb
Voltage - Line-Line and Line-Neutral: (3-phase average and per phase) bbbb
Frequency bbbb
Accumulated Energy - Real (kWh), Reactive (kVARh), and Apparent (kVAh) b b b
Import and Export Accumulators of Real and Apparent Energy b
Reactive Energy Accumulators by Quadrant (3-phase total and per phase) b
Congurable Demand Subinterval bbbb
Demand Interval Conguration: Fixed or Rolling Block bbbb
Demand Interval Conguration: External Sync to Comms bbb
Data Logging (store up to 60 days at 15-minute interval):
Data Logging - 10 16-Bit Congurable (can include Date/Time) Data Buffers b
Data Logging - 3 Timestamped 32-Bit Congurable Data Buffers b
Outputs:
PE86002
Alarm Output (N.C.) bbb
1 Pulse Output (N.O.) b b
2 Pulse Outputs (N.O.)
RS-485 Serial (Modbus RTU Protocol) b b
RS-485 Serial (BACnet MS/TP Protocol) b
Inputs:
2 Pulse Contact Accumulator Inputs b
EM3500
Functions and characteristics (cont.)
Basic energy metering
Screen Name or Units
Diagnostic Alert
Numeric Data
Alive Indicator
Export
Import
Transmit Data
Receive Data
Receive Data Error
Display Screen Diagram