Switch Mode Power Supply S8VM (15/30/50/100/150/300/600/1,500-W Models) Power Supply Featuring OMRON's Unique, New Undervoltage Alarm Function with Compact Body Contributing to Machine Downsizing * New undervoltage alarm function assists in determining causes of errors (S8VM-@@@24A@/P@ only). * Power failure alarm function provides notification of output voltage errors (300-, 600-, and 1,500-W models only). * Broad range of possibilities with 8 capacities and 29 models to choose from. * RoHS-compliant including lead-free construction. * Safety standards: UL508/60950-1/1604, CSA C22.2 No. 14/No. 60950-1/No. 213, EN50178, EN60950-1 (The 300-, 600-, and 1,500-W models will not conform to safety standards if the customer replaces the fan.) * Harmonic current emissions: Conforms to EN61000-3-2 (except for 15- and 30-W models). * New, attentive design prevents screws from falling out of terminal block (except for output terminals of 300-, 600-, and 1,500-W models). * Finger protection prevents electric shock. * DIN Rail mounting. Note: Refer to Precautions for Safe Use on page 32. Model Number Structure Model Number Legend Note: Not all combinations are possible. Please refer to the list of models in Ordering Information on page 2. S8VM- @@@@@@@ 1 1. Power Ratings 015: 15 W 030: 30 W 050: 50 W 100: 100 W 150: 150 W 300: 300 W 600: 600 W 152: 1,500 W 2. Output Voltage 05: 5 V 12: 12 V 15: 15 V 24: 24 V 2 3 4 3. Configuration/Functions None: Open-frame type Standard type C: Covered type Standard type A: Covered type Undervoltage alarm type (Sinking) (See note 1.) P: Covered type Undervoltage alarm type (Sourcing) (See note 1.) 4. Configuration None Bottom mounting type (See note 2.) D DIN Rail mounting bracket type Note: 1. The housing and terminal of the connector for the undervoltage alarm output are provided with the S8VM-05024A@/P@, S8VM10024A@/P@ and S8VM-15024A@/P@. 2. Bottom mounting models cannot be used for front mounting. For a front mounting configuration, use a DIN Rail mounting bracket model or Mounting Brackets (sold separately). 3. A forced-air cooling method with a fan is used with 300-, 600-, and 1,500-W models. Switch Mode Power Supply S8VM 1 Ordering Information Note: For details on normal stock models, contact your nearest OMRON representative. Configuration Power ratings Open-frame 15 W type Input voltage 100 to 240 VAC 30 W 50 W 100 W 150 W Covered type 15 W 30 W 50 W 100 W 150 W 300 W (See note 4.) Note: 1. 2. 3. 4. 5. 2 100 to 240 VAC Output voltage Output current 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 3A 1.3 A 1A 0.65 A 6A 2.5 A 2A 1.3 A 10 A 4.3 A 3.5 A 2.2 A 20 A 8.5 A 7A 4.5 A 27 A 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12 V 15 V 24 V 5V 12.5 A 10 A 6.5 A 3A 1.3 A 1A 0.65 A 6A 2.5 A 2A 1.3 A 10 A 4.3 A 3.5 A 2.2 A 20 A 8.5 A 7A 4.5 A 27 A 12 V 15 V 24 V 5V 12 V 15 V 24 V 12.5 A 10 A 6.5 A 60 A 27 A 22 A 14 A Peak current: 16.5 A (200 VAC) 120 A 53 A 43 A 27 A Peak current: 31 A (200 VAC) 65 A (100 VAC) 70 A (200 VAC) Peak current: 105 A (200 VAC) 600 W (See note 4.) 5V 12 V 15 V 24 V 1,500 W (See note 4.) 24 V Bottom mounting Standard model Undervoltage alarm model Sinking Sourcing S8VM-01505 ----S8VM-01512 ----S8VM-01515 ----S8VM-01524 ----S8VM-03005 ----S8VM-03012 ----S8VM-03015 ----S8VM-03024 ----S8VM-05005 ----S8VM-05012 ----S8VM-05015 ----S8VM-05024 ----S8VM-10005 ----S8VM-10012 ----S8VM-10015 ----S8VM-10024 ----S8VM-15005 ----(See note 2.) S8VM-15012 ----S8VM-15015 ----S8VM-15024 ----S8VM-01505C ----S8VM-01512C ----S8VM-01515C ----S8VM-01524C S8VM-01524A (See note 1.) S8VM-03005C ----S8VM-03012C ----S8VM-03015C ----S8VM-03024C S8VM-03024A (See note 1.) S8VM-05005C ----S8VM-05012C ----S8VM-05015C ----S8VM-05024C S8VM-05024A S8VM-05024P S8VM-10005C ----S8VM-10012C ----S8VM-10015C ----S8VM-10024C S8VM-10024A S8VM-10024P S8VM-15005C ----(See note 2.) S8VM-15012C ----S8VM-15015C ----S8VM-15024C S8VM-15024A S8VM-15024P S8VM-30005C ----S8VM-30012C ----S8VM-30015C ----S8VM-30024C ----- DIN Rail mounting bracket Standard model Undervoltage alarm model Sinking Sourcing S8VM-01505D ----S8VM-01512D ----S8VM-01515D ----S8VM-01524D ----S8VM-03005D ----S8VM-03012D ----S8VM-03015D ----S8VM-03024D ----S8VM-05005D ----S8VM-05012D ----S8VM-05015D ----S8VM-05024D ----S8VM-10005D ----S8VM-10012D ----S8VM-10015D ----S8VM-10024D ----S8VM-15005D ----(See note 2.) S8VM-15012D ----S8VM-15015D ----S8VM-15024D ----S8VM-01505CD ----S8VM-01512CD ----S8VM-01515CD ----S8VM-01524CD S8VM-01524AD (See note 1.) S8VM-03005CD ----S8VM-03012CD ----S8VM-03015CD ----S8VM-03024CD S8VM-03024AD (See note 1.) S8VM-05005CD ----S8VM-05012CD ----S8VM-05015CD ----S8VM-05024CD S8VM-05024AD S8VM-05024PD S8VM-10005CD ----S8VM-10012CD ----S8VM-10015CD ----S8VM-10024CD S8VM-10024AD S8VM-10024PD S8VM-15005CD ----(See note 2.) S8VM-15012CD ----S8VM-15015CD ----S8VM-15024CD S8VM-15024AD S8VM-15024PD ------------------------- S8VM-60005C S8VM-60012C S8VM-60015C S8VM-60024C --------- --------- --------- --------- --------- S8VM-15224C (See note 3.) --- --- --- --- --- No outputs are built into these models. The output capacity of the S8VM-15005@@ is 135 W. M8 bolts and nuts for the output terminals are not included with the S8VM-15224C. The 300-, 600-, and 1,500-W models have fans. To perform front mounting using the bottom mounting models, use the Mounting Brackets (S82Y-VM@@F, sold separately). Switch Mode Power Supply S8VM Specifications Ratings/Characteristics Item Efficiency Input Output Additional functions Other Power rating 5-V models 12-V models 15-V models 24-V models Voltage (See note 1.) Frequency (See note 1.) Current 100-V input 200-V input Power factor 100-V input 200-V input Harmonic current emissions Leakage current 100-V input 200-V input Inrush current 100-V input (See note 2.) 200-V input Voltage adjustment range (See note 3.) Ripple 15 W 30 W 50 W 100 W 150 W 75% min. 75% min. 80% min. 81% min. 81% min. 78% min. 79% min. 79% min. 81% min. 81% min. 78% min. 79% min. 79% min. 81% min. 81% min. 80% min. 81% min. 80% min. 82% min. 83% min. 100 to 240 VAC (85 to 264 VAC) 50/60 Hz (47 to 63 Hz) 0.5 A max. 0.9 A max. 0.8 A max. 1.4 A max. 2.0 A max. 0.25 A max. 0.45 A max. 0.4 A max. 0.7 A max. 1.0 A max. --0.98 min. --0.94 min. --Conforms to EN 61000-3-2 0.4 mA max. (at rated output) 0.75 mA max. (at rated output) 17.5 A max. (for cold start at 25C) 35 A max. (for cold start at 25C) -20% to 20% (with V. ADJ) (S8VM-@@@24A@/P@: -10% to 20%) 3.2% (p-p) max. (5 V), 3.2% (p-p) max. (5 V), 1.5% (p-p) max. (12 V), 1.5% (p-p) max. (12 V), 1.2% (p-p) max. (15 V), 1.2% (p-p) max. (15 V), 1.0% (p-p) max. (24 V), 0.75% (p-p) max. (24 V), (at rated input/output voltage) (at rated input/output voltage) Input variation influence 0.4% max. (at 85 to 264 VAC input, 100%) Load variation influence (rated input voltage) 0.8% max. (with rated input, 0 to 100% load) Temperature variation influence 0.02%/C max. Start up time (See note 2.) 1,100 ms max. (at rated input/output voltage) 800 ms max. (at rated input/output voltage) Hold time (See note 2.) 20 ms typ. (15 ms min.) (at rated input/output voltage) Overload protection (See note 2.) 105% to 160% of rated load current, voltage 105% to 160% of rated load current, drop, intermittent, automatic reset voltage drop (12 V, 15 V, and 24 V), voltage drop, intermittent (5 V), automatic reset Overvoltage protection (See note 2.) Yes (See note 4.) Undervoltage alarm indication Yes (color: yellow (DC LOW1), red (DC LOW2)) (S8VM-@@@24A@/P@ only) Undervoltage alarm output No Yes (S8VM-@@@24A@/P@ only) (Transistor output), 30 VDC max., 50 mA max. (See note 8.) Power failure alarm indication No Power failure alarm output No Series operation Yes Parallel operation No Remote sensing function No Yes Ambient operating temperature Refer to the derating curve in Engineering Data (15-W, 30-W, 50-W, 100-W, 150-W Models). (with no icing or condensation) (See note 2.) Storage temperature -25 to 65C Ambient operating humidity 30% to 85% (Storage humidity: 25% to 90%) Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE/FG terminals; detection current: 20 mA) 500 VAC for 1 min. (between all outputs and PE/FG terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs (except the detection output terminals) and detection output terminals; detection current: 20 mA) (S8VM-@@@24A@/P@ only) Insulation resistance 100 M min. (between all outputs and all inputs, PE/FG terminals) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in X, Y, Z directions Output indicator EMI Conducted Emission Radiated Emission EMS Approved standards Weight (See note 7.) Yes (color: green) Conforms to EN61204-3 EN55011 Class B and based on FCC Class B (See note 5.) Conforms to EN61204-3 EN55011 Class B (See note 6.) Conforms to EN61204-3 High severity levels UL: UL508 (Listing), UL60950-1, UL1604 (Class I/Division 2, Listing) CSA: cUL: C22.2 No.14, No.213 (Class I/Division 2), cUR: No. 60950-1 EN: EN50178, EN60950-1 SELV (EN60950-1) According to VDE0160/P100 SEMI-F47 (200 VAC input) 180 g max. 220 g max. 290 g max. 460 g max. 530 g max. Note: 1. Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. 2. Refer to the Engineering Data (15-W, 30-W, 50-W, 100-W, 150-W Models) section on page 9 to 11 for details. 3. If the V. ADJ adjuster is turned, the voltage will increase by more than +20% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON. 5. Conducted emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class B when the aluminum plate is laid under the Power Supply. For 15-W models, insert a clamp filter (ZCAT2436-1330 by TDK: 50 min. [50 to 500 MHz], or the equivalent) in the output wire to reduce noise. 6. Radiated emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class B when the aluminum plate is laid under the Power Supply. For 150-W models, insert a clamp filter (ZCAT2017-0930 by TDK: 35 min. [50 to 500 MHz], or the equivalent) in the input wire to reduce noise. 7. The weight indicated is for bottom mounting, open-frame models. 8. A@: Sinking type (NPN) P@: Sourcing type (PNP) Switch Mode Power Supply S8VM 3 Item Efficiency Input Power rating 5-V models 12-V models 15-V models 24-V models Voltage (See note 1.) Frequency (See note 1.) Current 100-V input 200-V input Power factor Output Additional functions Other 100-V input 200-V input Harmonic current emissions Leakage current 100-V input 200-V input Inrush current 100-V input (See note 2.) 200-V input Voltage adjustment range (See note 3.) Ripple Input variation influence Load variation influence (rated input voltage) Temperature variation influence Start up time (See note 2.) Hold time (See note 2.) Overload protection (See note 2.) Overvoltage protection (See note 2.) Overheat protection (See note 2.) Undervoltage alarm indication Undervoltage alarm output Power failure alarm indication Power failure alarm output Series operation Parallel operation Remote sensing function Remote control function Ambient operating temperature Storage temperature Ambient operating humidity Dielectric strength Insulation resistance Vibration resistance Shock resistance Output indicator EMI Conducted Emission Radiated Emission EMS Approved standards (See note 8.) Weight 300 W 600 W 1,500 W 77% min. 77% min. --78% min. 79% min. --79% min. 80% min. --81% min. 81% min. 82% min. 100 to 240 VAC (85 to 264 VAC) 100 to 240 VAC (85 to 265 VAC) 50/60 Hz (47 to 63 Hz) 4.0 A max. (5 V) 8.0 A max. (5 V) 20.0 A max. 4.3 A max. (12 V, 15 V, and 24 V) 8.3 A max. (12 V, 15 V, and 24 V) 2.0 A max. (5 V) 4.0 A max. (5 V) 11.0 A max. 2.2 A max. (12 V, 15 V, and 24 V) 4.2 A max. (12 V, 15 V, and 24 V) 0.98 min. 0.97 min. 0.94 min. 0.93 min. Conforms to EN61000-3-2 0.4 mA max. 1.5 mA max. 0.75 mA max. 1.5 mA max. 20 A max. (for cold start at 25C) 40 A max. (for cold start at 25C) -20% to 20% (with V. ADJ) 3.8% (p-p) max. (5 V), 2.0% (p-p) max. (12 V), 2.0% (p-p) max. (15 V), 1.25% (p-p) max. (See note 7.), 1.25% (p-p) max. (24 V), (at rated input/output voltage) (at rated input/output voltage) 0.4% max. (at 85 to 264 VAC input, 100%) 0.6% max. (with rated input, 0 to 100% load) 0.02%/C max. 1,000 ms max. (at rated input/output voltage) 20 ms typ. (15 ms min.) (at rated input/output voltage) 105% to 160% of rated load current (5 V, 12 V, and 15 V), 120% to 160% of rated 105% to 160% of rated load current (100 VAC), load current (S8VM-30024C), 115% to 160% of rated load current (S8VM155% to 200% of rated load current (200 VAC), 60024C), voltage drop (12 V, 15 V, and 24 V), voltage drop, intermittent (5 V), voltage drop, automatic reset (Turns OFF automatic reset when continuous for 5 s min.) (See note 4.) Yes (See note 4.) Yes (See note 4.) No No Yes (color: red) Yes (Transistor output), 30 VDC max., 50 mA max. Yes Yes (Up to 2 units) Yes Yes Refer to the derating curve in Engineering Data (300-W, 600-W, 1,500-W Models). (with no icing or condensation) (See note 2.) -25 to 65C 30% to 85% (Storage humidity: 25% to 90%) 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 3.0 kVAC for 1 min. (between all inputs and 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 outputs; detection current: 20 mA) mA) 2.0 kVAC for 1 min. (between all inputs and FG 500 VAC for 1 min. (between all outputs and PE terminals; detection current: 100 terminals; detection current: 20 mA) mA) 500 VAC for 1 min. (between all outputs and 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 FG terminals; detection current: 300 mA) mA) 100 VAC for 1 min. (between all outputs and 500 VAC for 1 min. (between all outputs and PF terminals; detection current: 20 RC terminals; detection current: 100 mA) mA) 500 VAC for 1 min. (between all outputs and PF terminals; detection current: 20 mA) 100 M min. (between all outputs and all inputs, PE terminals) at 500 VDC 100 M min. (between all outputs and all inputs, FG terminals) at 500 VDC 10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions 10 to 55 Hz, 0.15-mm single amplitude for 2 hours each in X, Y, and Z directions 150 m/s2, 3 times each in X, Y, Z directions Yes (color: green) Conforms to EN61204-3 EN55011 Class B and based on FCC Class B Conforms to EN61204-3 EN55011 Class B Conforms to EN61204-3 High severity levels UL: UL508 (Recognition) (5 V, 12 V, and 15 V) UL508 (Listing) (24 V), UL60950-1 UL1604 (Class I/Division 2, Listing) (24 V) (pending) CSA: cUL: C22.2 No.14, cUR: CSA No. 60950-1 EN: EN50178, EN60950-1 SEMI-F47 (200 VAC input) 1,100 g max. 1,700 g max. Conforms to EN61204-3 EN55011 Class A and based on FCC Class A Conforms to EN61204-3 EN55011 Class A UL: UL508 (Recognition), UL60950-1 cUR: CSA C22.2 No.14, No. 60950-1 EN: EN50178, EN60950-1 SEMI-F47 (200 VAC input) 3,800 g max. Note: 1. Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. 2. Refer to the Engineering Data section on page 15 to 17 for details. 3. If the V. ADJ adjuster is turned, the voltage will increase by more than +20% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON. Alternatively, turn OFF the remote control signal and then turn it back ON again. 5. Conducted emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class B when the aluminum plate is laid under the Power Supply. For 600-W models, insert a clamp filter (ZCAT3035-1330 by TDK: 100 min. [50 to 500 MHz], or the equivalent) in the input wire, and ring core (HF60T38X14X22 by TDK: 16 typ. [1 MHz], 46 typ. [10 MHz] , or the equivalent) in the output wire to reduce noise 6. Radiated emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class A when the aluminum plate is laid under the Power Supply (1,500-W models). 7. The measuring method conforms to JEITA standard RC-9131A. Refer to Ripple under Safety Precautions on page 34. 8. The Power Supply will not conform to safety standards if the customer replaces the fan. 4 Switch Mode Power Supply S8VM Connections Block Diagrams S8VM-015@@@@ (15 W) S8VM-01524A@ DC LOW1 DC LOW2 Undervoltage alarm indication Undervoltage detection +V AC (L) Fuse 2A INPUT Noise filter AC (N) DC OUTPUT Inrush Smoothing current protection circuit Rectification -V Rectifier/smoothing circuit Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit Photocoupler /FG S8VM-030@@@@ (30 W) S8VM-03024A@ Undervoltage DC LOW1 alarm indication DC LOW2 Undervoltage detection +V AC (L) Fuse 3.15 A INPUT Noise filter AC (N) DC OUTPUT Inrush Smoothing current protection circuit Rectification -V Rectifier/smoothing circuit Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit Photocoupler /FG S8VM-050@@@@ (50 W) S8VM-05024A@ (Sinking) S8VM-05024P@ (Sourcing) Undervoltage DC LOW1 alarm indication DC LOW2 Undervoltage DC LOW1 alarm indication DC LOW2 Alarm DC LOW1 Undervoltage detection Alarm DC LOW2 Common Photocoupler AC (L) INPUT AC (N) Fuse 2A Alarm DC LOW1 Undervoltage detection Alarm DC LOW2 Common Photocoupler +V Noise filter DC OUTPUT Inrush SmoothRectification Harmonic current ing current protection suppression circuit Rectifier/smoothing circuit -V Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit /FG Photocoupler Switch Mode Power Supply S8VM 5 S8VM-100@@@@ (100 W) Fuse 3.15 A INPUT Undervoltage DC LOW1 alarm indication DC LOW2 Undervoltage DC LOW1 alarm indication DC LOW2 Inrush Harmonic current current protection Rectification suppression circuit AC (L) S8VM-10024P@ (Sourcing) S8VM-10024A@ (Sinking) Undervoltage detection AC (N) Alarm DC LOW1 Alarm DC LOW1 Noise filter Smoothing Undervoltage detection Alarm DC LOW2 Common Photocoupler Alarm DC LOW2 Common Photocoupler +V DC OUTPUT -V Drive Rectifier/smoothing circuit +S Remote sensing -S Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit Photocoupler /FG S8VM-150@@@@ (150 W) S8VM-15024P@ (Sourcing) S8VM-15024A@ (Sinking) Inrush Harmonic current current protection Rectification suppression circuit Undervoltage DC LOW1 alarm indication DC LOW2 Undervoltage DC LOW1 alarm indication DC LOW2 Fuse 5A INPUT Noise filter Undervoltage detection AC (N) Alarm DC LOW1 Alarm DC LOW1 AC (L) Smoothing Alarm DC LOW2 Common Undervoltage detection Photocoupler Photocoupler +V DC OUTPUT -V Drive Rectifier/smoothing circuit +S Remote sensing -S Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit Photocoupler /FG S8VM-300@@C (300 W) Harmonic current Rectification suppression AC (L) Fuse 10 A INPUT Inrush current protection circuit Fan detection Power failure alarm indication PF Alarm PF-C PF-E Noise filter AC (N) Smoothing Power failure alarm detection Photocoupler +V DC OUTPUT -V Rectifier/smoothing circuit +V Drive Output voltage monitor -V Control circuit Overcurrent detection circuit +S Remote sensing Rectifier/smoothing circuit Voltage detection circuit Over heat detection circuit Overvoltage detection circuit Fan Rectifier/smoothing circuit 6 -S CB Power supply balance circuit Auxiliary power supply circuit Current balance CBG +RC Remote control Photocoupler Switch Mode Power Supply S8VM Alarm DC LOW2 Common -RC S8VM-600@@C (600 W) Harmonic current suppression AC (L) Fuse 15 A INPUT AC (N) Inrush current protection circuit Fan detection Power failure alarm indication PF Alarm PF-C PF-E Noise filter Rectification Power failure alarm detection Smoothing Photocoupler +V DC OUTPUT -V Rectifier/smoothing circuit Output voltage monitor -V Overcurrent detection circuit Control circuit Auxiliary power supply circuit +V Drive Rectifier/smoothing circuit +S Remote sensing Voltage detection circuit Over heat detection circuit -S CB Power supply balance circuit Overvoltage detection circuit Fan Current balance CBG +RC Remote control Rectifier/smoothing circuit S8VM-15224C (1,500 W) Inrush current protection circuit AC (L) Fuse 30 A INPUT -RC Photocoupler Harmonic current suppression Fan detection Power failure alarm indication Noise filter AC (N) Rectification Power failure alarm detection Smoothing Photocoupler PF Alarm PF-C PF-E +V DC OUTPUT Overcurrent detection circuit -V Rectifier/smoothing circuit Drive +V Output voltage monitor -V Control circuit +S Remote sensing Rectifier/smoothing circuit Auxiliary power supply circuit Voltage detection circuit Over heat detection circuit -S CB Power supply balance circuit Overvoltage detection circuit Fan Current balance CBG +RC Remote control Rectifier/smoothing circuit Photocoupler -RC /FG Switch Mode Power Supply S8VM 7 Construction and Nomenclature (15-W, 30-W, 50-W, 100-W, 150-W Models) Nomenclature No. Name 1 AC input terminals (L), (N) 15-W, 30-W, 50-W Models Open-frame Models Covered Models S8VM-015@@/S8VM-015@@D S8VM-030@@/S8VM-030@@D S8VM-050@@/S8VM-050@@D S8VM-015@@C@/S8VM-01524A@ S8VM-030@@C@/S8VM-03024A@ S8VM-050@@C@/S8VM-05024A@/P@ 2 8 9 10 5 4 3 7 6 2 1 3 PE terminal: Protective earthing terminal (S8VM-@@@@@C@/S8VM-@@@@@A@/ S8VM-@@@@@P@) FG terminal: Frame ground terminal (S8VM-@@@@@/S8VM-@@@@@D) DC output terminals (-V), (+V) 4 Output indicator (DC ON: Green) 5 6 Output voltage adjuster (V. ADJ) Undervoltage alarm indicator 1 (DC LOW1: Yellow) (See note 3.) 7 Undervoltage alarm indicator 2 (DC LOW2: Red) (See note 3.) 8 Undervoltage alarm output terminal 1: (DC LOW1) (See note 4.) 9 Undervoltage alarm output terminal 2: (DC LOW2) (See note 4.) 10 11 Common terminal for undervoltage alarm output (See note 4.) Remote sensing terminals (See note 5.) 12 Short bars (See note 5.) 100-W Models Open-frame Models Covered Models S8VM-100@@/S8VM-100@@D S8VM-100@@C@/S8VM-10024A@/P@ 6 7 5 4 11 12 3 12 12 11 2 1 10 9 8 12 150-W Models Open-frame Models Covered Models S8VM-150@@/S8VM-150@@D S8VM-150@@C@/S8VM-15024A@/P@ 12 Protective earthing connection 5 4 11 12 3 11 2 1 7 6 12 Ground 300-W, 600-W, 1,500-W Models Note: Refer to page 14. Output Color Label This color label identifies the output voltage by color. Green: Blue: Yellow: White: 5V 12 V 15 V 24 V Color label identifying output voltage 8 Connect the load lines to these terminals. Lights (green) while a direct current (DC) output is ON. Use to adjust the voltage. Lights only when a momentary drop in output voltage is detected. This status is maintained. Lights only when the output voltage drops to approximately 20 V or lower. Outputs only when a momentary drop in output voltage is detected. This status is maintained. (The transistor turns OFF when a voltage drop occurs.) Outputs only when the output voltage drops to approximately 20 V or lower. (The transistor turns OFF when a voltage drop occurs.) Common terminal (See note 6.) for terminals 8 and 9 Correct the voltage drop in the load lines. --- Note: 1. The fuse is located on the (L) side. It is NOT user-replaceable. 2. If mounting is performed using a DIN Rail, the protective earthing connection is the panel mounting hole shown in the figure below. (A protective earthing connection stipulated in safety standards is used. Connect the ground completely (S8VM@@@@@D only)). Ground terminal: M3 (Depth: 8 mm max.)/Ground wire: AWG 18 8 9 10 12 Function Connect the input lines to these terminals. (See note 1.) Connect the ground line to this terminal. (See note 2.) Switch Mode Power Supply S8VM 3. S8VM-@@@24A@/P@ only 4. S8VM-05024A@/P@, S8VM-10024A@/P@, S8VM15024A@/P@ only. Housing and terminals of the connector for undervoltage detection output are also provided. For details, refer to Undervoltage Alarm Output Connector Harness Manufacture Method on page 33 under Safety Precautions. 5. When not using the remote sensing function, leave the short bar in the same state as when shipped. 6. A@ models: Common terminal (emitter) P@ models: Common terminal (collector) Engineering Data (15-W, 30-W, 50-W, 100-W, 150-W Models) Derating Curve 15W/30W Load ratio (%) Standard Mounting/Horizontal Mounting/Face-up Mounting 120 Opened type 100 A 80 Covered type 60 40 20 0 -20 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) 50W 120 Opened type 100 A Face-up Mounting Load ratio (%) Load ratio (%) Standard Mounting/Horizontal Mounting 120 Opened type 100 80 A 80 Covered type Covered type 60 60 40 40 20 20 0 -20 -10 0 10 20 30 40 50 60 0 -20 70 80 -10 0 10 20 Ambient temperature (C) 30 40 50 60 70 80 Ambient temperature (C) 100W Horizontal Mounting/Face-up Mounting 120 Opened type 100 A Load ratio (%) Load ratio (%) Standard Mounting 120 Opened type 100 80 A 80 Covered type Covered type 60 60 40 40 20 20 0 -20 -10 0 10 20 30 40 50 60 0 -20 70 80 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) Ambient temperature (C) 150W Horizontal Mounting Opened type 100 A Face-up Mounting 120 Opened type 100 A 80 80 Covered type Load ratio (%) 120 Load ratio (%) Load ratio (%) Standard Mounting 120 Opened type 100 Covered type Covered type 60 60 40 40 40 20 20 20 0 -20 0 -20 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) A 80 60 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) 0 -20 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) 300W/600W/1,500W Note: Refer to page 15. Note: 1. Internal parts may occasionally be deteriorated or damaged. Do not use the Power Supply in areas outside the derating curves (i.e., the area shown by shading A in the above graphs). 2. If there is a derating problem, use forced air-cooling. 3. When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them. Multiple 100- and 150-W models cannot be used side by side. Be sure to install the Power Supplies as far away from heat-generating sources as possible. As a reference value, allow at least 50 mm spacing on the right and left sides. If only 20 mm spacing is allowed, use the Power Supply at a load ratio of 80% or less. 4. When using 150-W models for a long period of time at an input voltage of 90 VAC or lower, reduce the load to 80% or less of the above derating curves. Switch Mode Power Supply S8VM 9 Mounting Remote Sensing Function Standard Mounting (DIN Rail Mounting Bracket Models) Correct Standard Mounting (Bottom Mounting Models) (S8VM-100@@@@/150@@@@ only) This function compensates a voltage drop on the load lines. To use this function, connect after removing the two short bars of the remote sensing terminal. Correct Short bar V.ADJ *1 DC ON +S +V -V *1 -S *2 Horizontal Mounting Correct *1 Face-up Mounting Face-up Mounting (DIN Rail Mounting Bracket Models) Incorrect Correct Note: 1. Use a 2-conductor shielded cable as a connection wire (*1). 2. Use as thick a wire as possible since high voltage drops on the load lines (*2) may activate the overvoltage protection function. 3. Use when the voltage drop is 0.3 V or lower. 4. When the +S and -S terminals are opened with the short bar removed, the overvoltage protection function is activated and the output voltage will be cut off. 5. If the load line is too long, use an electrolytic capacitor in the following 3 locations: 1) Across the load terminals 2) Between the +S terminal and + terminal 3) Between the -S terminal and - terminal Select the capacity of the connected capacitor from between several tens to several hundreds of F as a guide, and then determine the capacity when actually connecting the capacitor between terminals as shown below. + V.ADJ DC ON +S + +V -V + -S *1 Face-down Mounting (DIN Rail Mounting Bracket Models) Face-down Mounting Incorrect Incorrect Inrush Current, Start Up Time, Output Hold Time Input OFF Input ON AC input voltage Inrush current on input application AC input current 95% 90% Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the Power Supply within the derating curve for the mounting direction that is used. 2. Use the metal plate as the mounting panel (*1). 3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by means of natural air flow. 4. Mounting screw tightening torque (recommended value: M3 (0.49 N*m)) 10 Switch Mode Power Supply S8VM Output voltage Hold time Start up time Reference Values Value Definition Reliability (MTBF) Item 135,000 hrs min. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates the reliability of a device. Therefore, it does not necessarily represent the life of the Power Supply. Life expectancy 10 yrs. min. The life expectancy indicates average operating hours under the ambient temperature of 40C and a load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. 15W/30W 50W/100W/150W (5 V) Intermittent operation Output voltage (V) Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the Power Supply fails. When an excessive voltage that is approximately 140% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again. Output voltage (V) Overvoltage Protection The Power Supply is provided with an overload protection function that protects the Power Supply from possible damage by short-circuit and overcurrent. When the output current rises above 105% min. of the rated current, the protection function is triggered, automatically decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared. Output voltage (V) Overload Protection Overvoltage protection operating Approx. 40% Variable range +20% *1 Rated output voltage Intermittent operation *2 -10% 50 0 100 Output current (%) 50 100 Output current (%) 50W/100W/150W (12 V, 15 V, 24 V) 300W/600W/1,500W Output voltage (V) 0 Note: Refer to page 17. -20% 0V The values shown in the above diagram are for reference only. *1 S8VM-@@@24A@/P@ *2 Except for S8VM-@@@24A@/P@ 0 Note: 1. Do not turn ON the input power again until the cause of the overvoltage has been removed. 2. The overvoltage protection function may be activated when the output voltage adjuster (V.ADJ) is set to a value that exceeds +20% of the rated output voltage. 50 100 Output current (%) The values shown in the above diagrams are for reference only. Note: 1. Internal parts may occasionally deteriorate or be damaged if a short-circuited or other overcurrent state continues during operation. Eliminate the overcurrent state as soon as possible. 2. Internal parts may possibly be deteriorated or damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. Undervoltage Alarm Function (Indication and Output) (Only S8VM-@@@24A@/P@) If an output voltage drop is detected with an S8VM-@@@24A@/P@ with undervoltage alarm function, the DC LOW indicator will light to notify of an output error. The transistor also sends an output externally to notify of the error (except for the S8VM-01524A@ and S8VM-03024A@). Transistor Output: Sinking type: (NPN) (S8VM-@@@24A@) Sourcing type: (PNP) (S8VM-@@@24P@) 30 VDC max., 50 mA max., Residual voltage when ON: 2 V or less, Leakage current when OFF: 0.1 mA or less S8VM-01524A@ S8VM-05024A@/P@ S8VM-10024A@/P@ S8VM-15024A@/P@ S8VM-03024A@ 8 9 10 4 4 7 6 4 8 9 10 6 7 7 6 10 9 8 4 7 6 * Undervoltage Alarm Function 1 (DC LOW1) Only a momentary voltage drop is detected. Detection voltage is automatically adjusted internally by detecting the output voltage (approx. 2.7 V lower than the voltage output at an output voltage of 24.0 V). During detection, the transistor is OFF (with no continuity across 8 and 10) and the LED (6: Yellow) lights. (The Undervoltage Alarm Function 1 is used as a latch holding function.) * Undervoltage Alarm Function 2 (DC LOW2) Detection voltage is set to approx. 20.0 V (from 18.0 to 21.6 V). During detection, the transistor is OFF (with no continuity across 9 and 10) and the LED (7: Red) lights. Note: 1. This function monitors the voltage at the Power Supply output terminals. To check actual voltage, measure voltage on the load side. 2. Gradual voltage drop is not detected by the Undervoltage Alarm Function 1 (DC LOW1). 3. Once undervoltage is detected by Undervoltage Alarm Function 1 (DC LOW1), the transistor turns OFF and status of the LED (6: Yellow) light is maintained. To reset the function, turn OFF the input power for 60 seconds or longer, and then turn it ON again. 4. If the output voltage remains at 15 V or lower for several seconds when using Undervoltage Alarm Function 1 (DC LOW 1), the output hold status for detection may be reset. Switch Mode Power Supply S8VM 11 Probable Causes of Power Supply Errors and Troubleshooting Using Undervoltage Alarm Function Check the following information if the Undervoltage Alarm Function operates. Contact your OMRON representative if the Power Supply does not function normally after checking. The symbols in the table are as follows: : Lit, : Not lit, : Flashing Note: Flashing: The output voltage is unstable, causing the LED to repeatedly turn ON and OFF. DC ON LED D: Green DC LOW1 LED F: Yellow Transistor outputs (H to J) DC LOW2 LED G: Red Transistor outputs (I to J) Output voltage Power Supply status diagnosis ON ON Normal (approx. 90% min. Normal status of rated output voltage) 2 OFF ON Normal (approx. 90% min. of rated output voltage) The output voltage has recovered to normal status following a previous sudden voltage drop. 3 ON OFF Output drop (approx. 90% max. of rated output voltage) The output voltage has dropped gradually and remains low. 4 OFF OFF Output drop (approx. 90% max. of rated output voltage) The output voltage remains low following a previous sudden voltage drop. ON Output drop (approx. 80% of rated output voltage) The output voltage remains low and is continuing to fluctuate following a previous sudden voltage drop. OFF Output drop (approx. 80% of rated output voltage) The output voltage has dropped gradually, remains low, and is continuing to fluctuate. OFF OFF No output No output voltage is being output. ON ON Unstable output The output voltage is unstable. 5 OFF 1 OFF 8 12 7 ON 6 ON OFF OFF Switch Mode Power Supply S8VM 24 V 24 V 24 V 24 V 24 V 24 V 24 V Probable cause of error Troubleshooting methods --- --- 1 A momentary power failure has occurred in the Check that the output voltage is normal and no problems have occurred in other devices. No problems input. will be caused by continuing to use the Power Supply as is. To clear DC LOW1 (LED display and transistor output status), turn OFF the input power, and wait at least 60 s before turning ON the input Power Supply again. A momentary overload has occurred. The load current has probably exceeded the rated current. We suggest reducing the connected load or replace the Power Supply with one that has a higher capacity. A momentary output voltage drop has occurred A large inrush current has probably flowed to the load side at startup. We suggest replacing the Power 2 at startup due to the capacity of the capacitive Supply with one that has a higher capacity. factors on the load side or when the load is activated. The output voltage has returned to normal volt- Turn OFF the input power, and wait at least 60 s before turning ON the input power again to clear the age following a rapid drop caused by using the indicator status. output voltage adjuster (V.ADJ). Deterioration due to age (when the Power Sup- The internal parts of the Power Supply may have deteriorated due to age. We suggest replacing the ply has been used for several years) Power Supply. Also replace other Power Supplies that were purchased at the same time. Overload (immediately following first use of the The load current has probably exceeded the rated current. Check the actual load current and Power Power Supply or when increasing the load) Supply capacity. Continued use in overload status may damage the Power Supply. 3 The output voltage dropped to -10% or lower of Adjust the output voltage to the rated values using the output voltage adjuster (V.ADJ). the rated voltage resulting from using the output voltage adjuster (V.ADJ) A sudden overload occurred and the Power An error has probably occurred in the load device. Turn OFF the input power, and check whether any Supply remains in overload status. errors have occurred in the load device. Continued use in overload status may damage the Power Supply. The output voltage remains low after a rapid Adjust the output voltage to the rated values using the output voltage adjuster (V.ADJ). To clear DC voltage drop caused by using the output voltage LOW1 (LED display and transistor output status), turn OFF the input power, and wait at least 60 s beadjuster (V.ADJ). fore turning ON the input power again. The overload status continues to fluctuate following a sudden overload. An error has probably occurred in the load device. Turn OFF the input power, and check whether any errors have occurred in the load device. Continued use in overload status may damage the Power Supply. 4 5 Deterioration due to age (after using the Power The internal parts of the Power Supply may have deteriorated due to age. Replace the Power Supply. Supply for several years) Also replace other Power Supplies that were purchased at the same time. Overload (immediately following first use of the The load current has probably exceeded the rated current. Check the actual load current and Power Power Supply or when increasing the load) Supply capacity. Continued use in overload status may damage the Power Supply. 6 Power Supply interrupted or damaged. Check whether the input power is being applied correctly. If there is no output even though the input power is applied correctly, the internal circuit is probably damaged. Overvoltage protection operation Turn OFF the input power, and wait at least 3 min before turning ON the input power again. If the same status recurs, the internal circuit is probably damaged. 7 The short bar has fallen off, or the +S and -S ter- Check whether the +S and -S terminals are open. If so, the overvoltage protection function is activated. minals are open. Therefore, turn OFF the input power and wait at least three minutes before turning it ON again. (S8VM10024A@/P@ and S8VM-15024A@/P@ models only) Output short-circuit Remove the cause of the output short-circuit. Intermittent operation due to overload (S8VM- The load current has probably exceeded the rated current. Check the actual load current and Power 01524A@/03024A@ only) Supply capacity. Continued use in overload status may damage the Power Supply. The Power Supply fails to start repeatedly due A large inrush current has probably flowed to the load side at startup. We suggest replacing the Power to the capacity of the capacitive factors on the Supply with one that has a higher capacity. 8 load side. The input turns ON and OFF repeatedly. Check whether the Power Supply's input voltage is being applied correctly. The status repeatedly switches between normal An error has probably occurred in the load device. Turn OFF the input power, and check whether any operation and output short-circuit. errors have occurred in the load device. Switch Mode Power Supply S8VM 13 Construction and Nomenclature (300-W, 600-W, 1,500-W Models) Nomenclature No. 300-W Models 2 PE terminal: Protective earth- Connect the ground line to this terminal. ing terminal (See note 2.) (S8VM-300@@C/S8VM600@@C) FG terminal: Frame ground terminal (S8VM-15224C) 3 DC output terminals (-V), ( +V) Connect the load lines to these terminals. Output indicator (DC ON: Green) Lights (green) while a direct current (DC) output is ON. 5 Output voltage adjuster (V.ADJ) Use to adjust the voltage. 6 Power failure alarm indicator (PF: Red) Lights when the output voltage decreases, the fan stops, and the system is on standby using the remote control function. 7 Signal I/O connector (See note 1: 3.) 2: 3: 4: 2 1 5: 6: 4 3 5 7 9 11 CN DC output monitor pin (+V) Remote sensing pin (+S) DC output monitor pin (-V) Remote sensing pin (-S) Current balance pin (CB) Signal ground pin for current balance (CBG) 7: Remote control pin (+RC) 8: Remote control pin (-RC) 9: No connect 10: No connect 11: Power failure alarm output pin (PF-C) (collector) 12: Power failure alarm output pin (PF-E) (emitter) Note: 1. The fuse is located on the (L) side. It is NOT user-replaceable. 2. Protective earthing connection is the panel mounting hole of the metal case. (A protective earthing connection stipulated in safety standards is used. Connect the ground completely). Ground terminal: M4 (Depth: 6 mm max.)/Ground wire: AWG 18 3. The enclosed standard connector for signal I/O is mounted to CN when S8VM is shipped. The enclosed signal I/O connector shorts between 1 and 2, between 3 and 4, and between 7 and 8. Do not connect a load to the output voltage monitor terminals (+V, -V). 1,500-W Model S8VM-15224C Output Color Label This color label identifies the output voltage by color. Green: Blue: Yellow: White: 5V 12 V 15 V 24 V Color label identifying output voltage Note: A 300-W model is shown above. The label is in a different place on 600-W models and 1,500-W model. 14 Connect the input lines to these terminals. (See note 1.) 4 6 8 10 12 S8VM-600@@C Function AC input terminal (L), (N) S8VM-300@@C 600-W Models Name 1 Switch Mode Power Supply S8VM Engineering Data (300-W, 600-W, 1,500-W Models) Derating Curve Upside-down Mounting (S8VM-15224C Only) Correct Load ratio (%) 300W/600W/1,500W 120 100 1,500 W 80 *1 Side Mounting 60 Incorrect Incorrect 300 W 600 W Incorrect 40 20 0 -20 -10 0 10 20 30 40 50 60 70 80 Ambient temperature (C) Note: 1. Internal parts may occasionally be deteriorated or damaged. Do not use the Power Supply in areas outside the derating curves (i.e., the area shown by shading A in the above graph). 2. When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them. Always provide at least 50 mm of mounting space for the surface with the fan mounted. Be sure to provide at least 50 mm (S8VM300@@C/600@@C) or 100 mm (S8VM-15224C) of mounting space on the opposite side of the surface with the fan mounted. 3. When using the 1,500-W model for a long period of time at an input voltage of 90 VAC or lower, reduce the load to 80% or less of the above derating curve. 4. The ambient temperature is specified at a location 50 mm in front of the center of the Power Supply's front panel. Standard Mounting Correct Note: 1. The internal parts may occasionally deteriorate or be broken due to adverse heat dissipation depending on the mounting status. Do not use the Power Supply in any mounting direction other than those specified. 2. Use the metal plate as the mounting panel (*1). 3. To ensure sufficient cooling, do not cover the air holes located on the side the fan is mounted and the opposite side. 4. Mounting screw tightening torque (recommended value: M4 (1.27 N*m)) The screws must not protrude more than 6 mm inside the Power Supply. Remote Sensing Function This function is used to compensate for voltage drops on the load lines. Connect the +S pin (pin 2 on CN) to the positive load terminal and the -S pin (pin 4 on CN) to the negative load terminal to enable remote sensing. When not using the remote sensing function, use the standard connector. The +S and +V pins (pin 1 on CN) and the - S and -V pins (pin 3 on CN) will be connected. Mounting Correct 1,500 W Correct +V + S8VM -V CN 300 W 600 W *1 *1 1,500 W +V +S -V *1 *2 -S *1 Horizontal Mounting Correct 300 W Correct *1 600 W Correct *1 1,500 W *1 Note: 1. Use 2-conductor shielded cable as connection wire (* 1). 2. Use as thick a wire as possible since high voltage drops on the load lines (* 2) may activate the overvoltage protection function. 3. Use when the voltage drop is 0.3 V or lower. 4. If the sensing line is too long, it is necessary to put an electrolytic capacitor across the load terminals. The electrolytic capacitor may generate heat due to the ripple current, depending on connected load. Therefore, the electrolytic capacitor must have a ripple current allowance higher than the output ripple current. 5. The stability and accuracy of the output will deteriorate if the +S or -S pins are open. Always connect the +S and -S pins. 6. Remove the standard supplied connector and prepare a connector separately. Switch Mode Power Supply S8VM 15 Remote Control Function This function turns outputs ON and OFF using an external signal while input voltage is applied, using the +RC pin (pin 7 on CN) and the -RC pin (pin 8 on CN). Connect a switch or transistor to the +RC and -RC pins to use the remote control function. When not using this function, the +RC and -RC pins are shorted by using the standard supplied connector. Inrush Current, Start Up Time, Output Hold Time Input OFF Input ON AC input voltage +RC S8VM SW CN Inrush current on input application TR -RC AC input current 95% 90% +RC Level for -RC Output Built-in Fan Motor Short or L (0 to 0.8 V) ON Rotate Open or H (2.4 to 12 V) OFF Stop Maximum input voltage: 12 V max. Maximum allowable reverse voltage: -1 V max. Sink Current: 3.5 mA Note: 1. Use 2-conductor shielded cable or twisted-pair cable as connection wire. 2. The remote control circuit is isolated from the input and output circuits of the power supply. 3. Remove the standard supplied connector and prepare a connector separately. Output voltage Start up time Input Current Waveform When Input Is Turned ON (The following examples show typical waveforms.) S8VM-300@@C 100 VAC, Load ratio: 100% 100 ms Power Failure Alarm Function The power failure alarm indicator will light red to indicate an output voltage error if overload, overvoltage, or overheat protection is activated, if a drop in the input voltage causes the output voltage to drop, if the built-in fan motor stops, and during remote control standby. The alarm is also output externally by a transistor. Transistor output: 30 VDC max., 50 mA max. AC input current (10 A/DIV) Output voltage AC input voltage Residual voltage when ON: 2 V max. Leakage current when OFF: 0.1 mA max. Alarm detection voltage: Approx. 80% of output voltage setting 200 VAC, Load ratio: 100% During detection, the transistor is OFF (with no continuity across pins 11 and 12 on CN), and the LED (red) lights. CN PF-E Vce max.: 30 VDC Ic max.: 50 mA Note: 1. This function monitors the voltage at the Power Supply output terminals. To check actual voltage, measure the voltage on the load side. 2. Outputs are forced OFF if the built-in fan motor stops (S8VM-15224C only). 3. Remove the standard supplied connector and prepare a connector separately. 16 100 ms PF-C S8VM Switch Mode Power Supply S8VM Hold time AC input current (10 A/DIV) Output voltage AC input voltage S8VM-600@@C Reference Values 100 VAC, Load ratio: 100% 100 ms AC input current (10 A/DIV) Value Definition Reliability (MTBF) Item 300 W: 135,000 hrs 600 W: 120,000 hrs 1,500 W: 100,000 hrs MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates the reliability of a device. Therefore, it does not necessarily represent the life of the Power Supply. Life expectancy 10 yrs. min. The life expectancy indicates average operating hours under the ambient temperature of 40C and a load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. Overload Protection Output voltage AC input voltage 200 VAC, Load ratio: 100% 100 ms The Power Supply is automatically protected from short-circuit or overcurrent damage by the overload protection function. Overload protection is activated if the output current rises above 105% of the rated current. S8VM-300@@C/600@@C When the output current returns within the rated range, overload protection is automatically cleared. AC input current (10 A/DIV) S8VM-15224C AC input voltage S8VM-15224C 100 VAC, Load ratio: 100% 300W/600W (5 V) 300W600W/1,500W (12 V, 15 V, 24 V) Output voltage (V) Output voltage Output voltage (V) Outputs are interrupted if an overload continues for 5 seconds or more. To reset the Power Supply, leave input power OFF for more than 3 minutes and then turn it ON again. Alternatively, turn OFF and ON the remote control signal. 100 ms Intermittent operation 0 AC input current (25 A/DIV) 50 100 Output current (%) 0 50 100 Output current (%) The values shown in the above diagrams are for reference only. Note: 1. If the Power Supply has been short-circuited or supplied with an overcurrent longer than 30 seconds, the internal parts of the Power Supply may occasionally be deteriorated or damaged. 2. The internal parts may possibly be deteriorated or damaged. Do not use the Power Supply for applications where the load causes frequent inrush current and overload. Output voltage AC input voltage 200 VAC, Load ratio: 100% 100 ms AC input current (10 A/DIV) Output voltage AC input voltage Switch Mode Power Supply S8VM 17 Overvoltage Protection Output voltage (V) Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the Power Supply fails. When an excessive voltage that is approximately 140% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again. Alternatively, turn OFF and ON the remote control signal. Overvoltage protection operating Approx. 40% +20% Rated output voltage Variable range -20% 0V The values shown in the above diagram are for reference only. Note: 1. Do not turn ON the input power again until the cause of the overvoltage has been removed. 2. The overvoltage protection function may be activated when the output voltage adjuster (V.ADJ) is set to a value that exceeds +20% of the rated output voltage. Overheat Protection The overheat protection circuit will operate and outputs will be shut OFF to protect the Power Supply if the ambient temperature rises, the fan stops, or other errors cause the Power Supply's internal temperature to rise. To reset the Power Supply, leave the input power OFF long enough for the Power Supply to cool sufficiently and then turn it ON again. Alternatively turn OFF the remote control signal long enough to cool sufficiently and then turn it ON again. Peak Output Current (S8VM-30024C/60024C/15224C Only) The peak current must satisfy the following conditions. Reduce the peak current according to the load rate of the derating curve. Input voltage range: 180 to 240 VAC Peak current pulse width: 10 s max. Duty: 35% max. Peak current value: Within the rated peak current Effective current: Within the rated current Ip Irms Ia 0A T Ip: Irms: lav: la: D: : T: 18 Peak current (A) Effective current (A) Rated current (A) Continuous load current (A) Duty Peak current pulse width (s) Cycle (s) Irms= lp2 x D + la2x (1-D) lav D= T Switch Mode Power Supply S8VM Dimensions Note: All units are in millimeters unless otherwise indicated. Bottom Mounting Models (15-W, 30-W, 50-W, 100-W, 150-W Models) S8VM-015@@ S8VM-015@@C S8VM-01524A 80.5 17.6 max. 27 81.5 680.5 8.50.5 Mounting Holes 620.5 Two, M3 (depth: 8 max.) 8.50.5 Bottom View Side Mounting 15.50.5 670.3 Two, 4 dia. Two, M3 (depth: 8 max.) 8.50.5 Note: The image is the S8VM-01524 Model. 680.5 84.5 13.6 max. 33.5 620.5 84.5 680.5 Bottom Mounting Two, 4 dia. 8.50.5 Two, M3 (depth: 8 max.) 670.3 620.5 8.50.5 15.50.5 Note: The image is the S8VM-01524A Model. 670.3 Two, M3 (depth: 8 max.) 8.50.5 S8VM-030@@ S8VM-030@@C S8VM-03024A 95.5 17.6 max. 27 82.5 680.5 Mounting Holes 8.50.5 770.5 Two, M3 (depth: 8 max.) Bottom View 8.50.5 Side Mounting 15.50.5 Two, 4 dia. Two, M3 (depth: 8 max.) 820.3 Note: The image is the S8VM-03024 Model. 8.50.5 680.5 99.5 13.6 max. 33.5 770.5 84.5 680.5 Bottom Mounting Two, 4 dia. 820.3 8.50.5 Two, M3 (depth: 8 max.) 8.50.5 770.5 15.50.5 Note: The image is the S8VM-03024A Model. 8.50.5 820.3 Two, M3 (depth: 8 max.) Switch Mode Power Supply S8VM 19 S8VM-050@@ S8VM-050@@C S8VM-05024A S8VM-05024P 120.5 17.6 max. 27 82.5 680.5 Mounting Holes Bottom View 8.50.5 23.50.3 Side Mounting 970.5 Two, M3 (depth: 8 max.) 8.50.5 Two, 4 dia. 150.2 830.5 80.2 680.5 Three, M3 (depth: 4 max.) 32.50.5 Note: The image is the S8VM-05024 Model. 124.5 13.6 max. 970.5 33.5 Bottom Mounting Three, 4 dia. 150.2 84.5 680.5 830.5 80.2 8.50.5 Two, M3 (depth: 8 max.) 23.50.3 970.5 8.50.5 150.2 Three, M3 (depth: 4 max.) 80.2 830.5 32.50.5 Note: The image is the S8VM-05024A Model. S8VM-100@@ S8VM-100@@C S8VM-10024A S8VM-10024P 160.5 17.6 max. 28.5 680.5 82.5 8.50.5 Two, M3 (depth: 8 max.) 1350.5 8.50.5 Mounting Holes 250.2 Bottom View 150.2 7.50.2 Three, M3 (depth: 4 max.) 1200.5 300.5 Side Mounting Two, 4 dia. Note: The image is the S8VM-10024 Model. 680.5 164.5 13.6 max. 35 1350.5 680.5 84.5 Bottom Mounting Three, 4 dia. 150.2 7.50.2 8.50.5 Two, M3 (depth: 8 max.) 250.2 8.50.5 1350.5 150.2 7.50.2 300.5 1200.5 Note: The image is the S8VM-10024A Model. 20 Switch Mode Power Supply S8VM Three, M3 (depth: 4 max.) 1200.5 S8VM-150@@ S8VM-150@@C S8VM-15024A S8VM-15024P 160.5 17.6 max. 37.5 82.5 680.5 8.50.5 Two, M3 (depth: 8 max.) 1350.5 Mounting Holes 8.50.5 Bottom View 26.50.2 Side Mounting 150.2 7.50.2 1200.5 Two, 4 dia. Three, M3 (depth: 4 max.) 250.5 680.5 Note: The image is the S8VM-15024 Model. 1350.5 Bottom Mounting Three, 4 dia. 150.2 164.5 13.6 max. 7.50.2 44 1200.5 84.5 680.5 8.50.5 1350.5 Two, M3 (depth: 8 max.) 8.50.5 26.50.2 150.2 7.50.2 250.5 1200.5 Three, M3 (depth: 4 max.) Note: The image is the S8VM-15024A Model. Switch Mode Power Supply S8VM 21 DIN Rail Mounting Bracket Models (15-W, 30-W, 50-W, 100-W, 150-W Models) S8VM-015@@D S8VM-015@@CD S8VM-01524AD 14 17.6 max. 80.5 33 3.5 max. 81.5 90.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-01524D Model. 14 84.5 15 max. 3.5 max. 35.1 84.5 46.2 94.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-01524AD Model. S8VM-030@@D S8VM-030@@CD S8VM-03024AD 14 17.6 max. 95.5 3.5 max. 33 82 105.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-03024D Model. 14 99.5 84.5 46.2 5.4 (Sliding: 9 max.) Note: The image is the S8VM-03024AD Model. 22 Switch Mode Power Supply S8VM 109.4 15 max. 3.5 max. 35.1 14 S8VM-050@@D S8VM-050@@CD S8VM-05024AD S8VM-05024PD 17.6 max. 120.5 3.5 max. 33 82.5 130.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-05024D Model. 14 124.5 15 max. 3.5 max. 35.1 84.5 46.2 5.4 (Sliding: 9 max.) 134.4 Note: The image is the S8VM-05024AD Model. S8VM-100@@D S8VM-100@@CD S8VM-10024AD S8VM-10024PD 14 160.5 17.6 max. 3.5 max. 33 82.5 170.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-10024D Model. 14 15 max. 164.5 3.5 max. 36.6 84.5 46.2 5.4 (Sliding: 9 max.) 174.4 Note: The image is the S8VM-10024AD Model. Switch Mode Power Supply S8VM 23 S8VM-150@@D S8VM-150@@CD S8VM-15024AD S8VM-15024PD 14 160.5 17.6 max. 3.5 max. 39.1 82.5 170.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-15024D Model. 14 15 max. 164.5 84.5 46.2 174.4 5.4 (Sliding: 9 max.) Note: The image is the S8VM-15024AD Model. 24 Switch Mode Power Supply S8VM 3.5 max. 45.6 Bottom Mounting Models (300-W, 600-W, 1,500-W Models) S8VM-300@@C Mounting Holes Four, M4 (depth: 6 max.) 188 max. 22 max. 25 1050.5 Bottom View Standard Mounting Four, 4.5 dia. 83.5 600.5 400.5 1200.5 11 1200.5 25 22 max. Horizontal Mounting 62.5 10.5 400.5 Four, 4.5 dia. 600.5 1050.5 Four, M4 (depth: 6 max.) Note: The image is the S8VM-30024C Model. S8VM-600@@C Four, M4 (depth: 6 max.) Mounting Holes 192 max. Bottom View 1200.5 25 26 max. Standard Mounting 83.8 Four, 4.5 dia. 400.5 600.5 21 101.8 1100.5 20 Horizontal Mounting Four, 4.5 dia. 600.5 400.5 1200.5 46 max. 1100.5 Four, M4 (depth: 6 max.) Note: The image is the S8VM-60024C Model. S8VM-15224C Four, M4 (depth: 6 max.) 126.5 46 max.10 Mounting Holes 327 max. Bottom View 2600.5 82 Standard Mounting Four, 4.5 dia. 600.5 1120.5 11 M8 (See note.) 10 2600.5 2600.5 7.25 1120.5 Horizontal Mounting Four, 4.5 dia. 600.5 2600.5 Four, M4 (depth: 6 max.) Note: M8 bolts and nuts for the output terminals are not included. Switch Mode Power Supply S8VM 25 Mounting Brackets Name Model Mounting Bracket A (bottom mounting for 15-, 30-, and 50-W models) S82Y-VM10B Mounting Bracket B (bottom mounting for 100- and 150-W models) S82Y-VM20B Mounting Bracket C (front mounting for 15-, 30-, 50-, 100-, and 150-W models) S82Y-VM10F Mounting Bracket D (bottom mounting for 300-W models) S82Y-VM30B Mounting Bracket E (horizontal bottom mounting for 300-W models) S82Y-VM30S Mounting Bracket F (front mounting for 300-W models) S82Y-VM30F Mounting Bracket G (DIN Rail mounting for 300-W models) S82Y-VM30D Mounting Bracket H (bottom mounting for 600-W models) S82Y-VM60B Mounting Bracket I (horizontal bottom mounting for 600-W models) S82Y-VM60S Mounting Bracket J (front mounting for 600-W models) S82Y-VM60F Mounting Bracket K (DIN Rail mounting for 600-W models) S82Y-VM60D Mounting Bracket A (Bottom Mounting for 15-, 30-, and 50-W Models) S82Y-VM10B Using the Mounting Bracket a = Mounting holes for 15-W models b = Mounting holes for 30-W models c = Mounting holes for 50-W models c a b b a, c c R2 Three, M3.5 B 200.5 35 B 7.5 5 5 B 4 Screws Used A: Accessories (Use the enclosed screws in two places for 15-W and 30-W models and in three places for 50-W models.) B: M3 or M3.5 (three places) Mounting screw tightening torque (recommended): 0.49 N*m 4 dia. 1400.5 R2 150 A t = 2.3 A A Mounting Bracket B (Bottom Mounting for 100-, and 150-W Models) S82Y-VM20B Using the Mounting Bracket a = Mounting holes for 100-W models b = Mounting holes for 150-W models b a b a b a R2 4 B 150.2 Three, M3.5 5 200.5 40 4 dia. 1820.5 192 t = 2.3 B A 26 Switch Mode Power Supply S8VM A A B Screws Used A: Accessories (Use the enclosed screws in three places.) B: M3 or M3.5 (three places) Mounting screw tightening torque (recommended): 0.49 N*m Mounting Bracket C (Front Mounting for 15-, 30- 50-, 100-, and 150-W Models) S82Y-VM10F 58 15 33 4 dia. Using the Mounting Bracket 5 B A A 105 970.5 80 R2 A B B 4 8.3 a, b 13.4 c d, e d, e t = 1.6 a, b, c, d, e Screws Used A: Accessories (Use the enclosed screws in two places for 15-W, 30-W and 50W models and in three places for 100-W and 150-W models.) B: M3 or M3.5 (three places) Mounting screw tightening torque (recommended): 0.49 N*m a = Mounting holes for 15-W models b = Mounting holes for 30-W models c = Mounting holes for 50-W models d = Mounting holes for 100-W models e = Mounting holes for 150-W models Mounting Bracket D (Bottom Mounting for 300-W Models) S82Y-VM30B Using the Mounting Bracket Three, 4.5 dia. B 48 60 B 5 195 B A A A A Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m Switch Mode Power Supply S8VM 27 Mounting Bracket E (Horizontal Bottom Mounting for 300-W Models) S82Y-VM30S Using the Mounting Bracket B 52 84 B 16 8 6 202 215 B Three, 4.5 dia. A A A A Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m Mounting Bracket F (Front Mounting for 300-W Models) S82Y-VM30F Using the Mounting Bracket Two, 4.5 dia. B 60 48 5 B 102.3 105 B 13.5 4.5 67 215.3 A 243 max. A A A 28 Switch Mode Power Supply S8VM Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m Mounting Bracket G (DIN Rail Mounting for 300-W Models) S82Y-VM30D Using the Mounting Bracket 60 102.3 215.3 67 6.4 Screws Used A: Accessories (Use the enclosed screws in four places.) Mounting screw tightening torque (recommended): 1.27 N*m 243 max. 9.5 A A A A Mounting Bracket H (Bottom Mounting for 600-W Models) S82Y-VM60B Using the Mounting Bracket B 72 B 100 Three, 4.5 dia. 8 6 Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m 202 215 B A A A A Mounting Bracket I (Horizontal Bottom Mounting for 600-W Models) S82Y-VM60S Using the Mounting Bracket B B 52 84 Three, 4.5 dia. 16 8 6 202 215 B A A A A Switch Mode Power Supply Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m S8VM 29 Mounting Bracket J (Front Mounting for 600-W Models) S82Y-VM60F Using the Mounting Bracket Two, 4.5 dia. B 98 82 5 B 105 102.3 B 13.5 222.3 4.5 105 257 max. Screws Used A: Accessories (Use the enclosed screws in four places.) B: M4 (three places) Mounting screw tightening torque (recommended): 1.27 N*m A A A A Mounting Bracket K (DIN Rail Mounting for 600-W Models) S82Y-VM60D Using the Mounting Bracket 98 102.3 105 222.3 6.4 257 max. 9.5 A A A A 30 Switch Mode Power Supply S8VM Screws Used A: Accessories (Use the enclosed screws in four places.) Mounting screw tightening torque (recommended): 1.27 N*m Other Items Sold Separately Name Model Undervoltage Alarm Output Wiring Cable S82Y-VM10H Terminal and Housing S82Y-VM30C Replacement Fan Unit for 300-W Models S82Y-VM30FAN Replacement Fan Unit for 600-W Models S82Y-VM60FAN Replacement Fan Unit for a 1,500-W Model S82Y-VM15FAN Undervoltage Alarm Output Wiring Cable S82Y-VM60D (for S8VM-05024A@/05024P@/10024A@/10024P@/15024A@/15024P@ Only) Using the Undervoltage Alarm Output Wiring Cable : to XHP-3 (Manufactured by JST) : AWG24 3,00050 DIN Rail (Order Separately) Note: All units are in millimeters unless otherwise indicated. Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.30.15 4.5 350.3 15 25 10 25 25 10 25 270.15 1 15(5) * 1,000 (500) * *Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) 16 PFP-100N2 4.5 350.3 27 15 25 10 25 25 1,000 10 25 15 24 29.2 1 1.5 Switch Mode Power Supply S8VM 31 Safety Precautions Several Power Supplies cannot be connected. (Only S8VM100@@@@/150@@@@) Keep the Power Supply as far away from heating elements as possible when installing. As a reference value, allow at least 50 mm spacing on the right and left sides. If only 20 mm spacing is allowed, use the Power Supply at a load ratio of 80% or less. !CAUTION Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product or touch the interior of the Product. Minor burns may occasionally occur. Do not touch the Product while power is being supplied or immediately after power is turned OFF. S8VM-100@@@@/S8VM-150@@@@ Incorrect Fire may occasionally occur. Tighten terminal screws to the specified torque. 15-, 30-, 50-, 100-, and 150-W models (1.6 N*m) 300-, 600-, and 1,500-W models (M4; 1.27 N*m, M5; 2.50 N*m, M8 bolts and nuts; 10.8 N*m) 300/600/1,500-W Models A forced-air cooling method with a fan is used. To ensure sufficient cooling, do not cover the air holes located on the side the fan is mounted and the opposite side. Minor injury due to electric shock may occasionally occur. Do not touch the terminals while power is being supplied. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Do not use the Power Supply in any mounting direction other than those specified. Minor electric shock, fire, or Product failure may occasionally occur. Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to enter the Product. The internal parts may possibly be damaged if mounting screws are over inserted. The screws must not protrude more than 6 mm inside the Power Supply. Precautions for Safe Use Mounting (See note 4.) Ensure sufficient heat dissipation when installing the Power Supply to increase its long-term reliability. Use the metal plate as the mounting panel. When cutting out holes for mounting, make sure that cuttings do not enter the interior of the Power Supply. When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them, as shown in the illustrations below. 15/30/50/100/150-W Models Natural cooling is used, so mount the Power Supply so that there is airflow around it. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the Power Supply within the derating curve for the mounting direction that is used. The internal parts may possibly be damaged if mounting screws are over inserted. Refer to Dimensions on page 19 to 21 for maximum depth of insertion inside the Power Supply. Standard Mounting (DIN Rail Mounting Bracket Models) Standard Mounting (Front Mounting Models) (See note 1.) (See note 1.) (See note 1.) (See note 1.) (See note 3.) (See note 2.) (See note 2.) Horizontal Mounting Face-up Mounting (See note 1.) (See note 3.) (See note 3.) (See note 2.) Note: 1. Convection of air 2. 20 mm or more 3. Use a metal plate as the mounting panel. Switch Mode Power Supply S8VM (See note 2.) (See note 3.) (See note 1.) (See note 1.) (See note 5.) S8VM Note: 1. Convection of air 2. 50 mm or more 3. (S8VM-300@@C/600@@C): 50 mm or more (S8VM-15224C): 100 mm or more 4. 20 mm or more 5. Use a metal plate as the mounting panel. Wiring Connect the ground completely. A protective earthing connection stipulated in safety standards is used. Electric shock or malfunction may occur if the ground is not connected completely. Minor fire may possibly occur. Ensure that input and output terminals are wired correctly. Do not apply more than 100 N force to the terminal block when tightening it. Be sure to remove the sheet covering the Power Supply for machining before power-ON so that it does not interfere with heat dissipation. Use the following material for the wires to be connected to the S8VM to prevent smoking or ignition caused by abnormal loads. Over heating or fire can result from inadequately sized wiring materials when problems occur at the load. As a general rule, always select wire sizes suitable for at least 1.6 times the rated current. Refer to the wiring manufacturer's recommended allowable current and voltage drop specifications for information when selecting wiring materials. (See note 1.) 32 Incorrect (See note 1.) Recommended Wire Sizes Terminal Input Output Model S8VM-015@@@@ S8VM-030@@@@ S8VM-050@@@@ S8VM-100@@@@ S8VM-150@@@@ S8VM-300@@C S8VM-600@@C S8VM-15224C S8VM-015@@@@ S8VM-030@@@ S8VM-050@@@@ S8VM-100@@@@ S8VM-150@@@@ S8VM-300@@C S8VM-600@@C S8VM-15224C (M4) AWG20 to AWG10 (0.52 to 5.27 mm2) * Use a YC Crimping Tool (manufactured by JST) to crimp the terminal and wire. * Applicable wire per barrel size is UL1007 (standard wire) and its equivalent standard wire can be used. Use UL1061 or its equivalent standard wire for AWG22 wires, because the wire insulation outer diameter of UL1061 is small. * Be sure to insert the crimped terminal wires into the housing fully until a click is heard. Also, make sure that the wires attached to the housing are securely locked in place. (M3.5) AWG24 to AWG14 (0.205 to 2.081 mm2) Installation Environment (M3.5) Recommended wire size AWG24 to AWG14 (0.205 to 2.081 mm2) AWG24 to AWG12 (0.205 to 3.309 mm2) AWG16 to AWG10 (M4) (1.32 to 5.27 mm2) AWG14 to AWG8 (M5) (2.08 to 8.3 mm2) (M8 AWG8 to AWG4 bolts and (8.3 to 21.09 mm2) nuts) (M4) The current rating for the output terminals on the S8VM-300@@C is 40 A per terminal. The current rating for the output terminals on the S8VM-600@@C is 60 A per terminal. Use two terminals together if a current exceeding the terminal rating is used. Do not use the Power Supply in locations subject to shocks or vibrations. In particular, install the Power Supply as far away as possible from contactors or other devices that are a vibration source. Install the Power Supply well away from any sources of strong, highfrequency noise and surge. Operating Life The life of a Power Supply is determined by the life of the electrolytic capacitors used inside. Here, Arrhenius Law applies, i.e., the life will be halved for each rise of 10C or the life will be doubled for each drop of 10C. The life of the Power Supply can thus be increased by reducing its internal temperature. Use min. 60C or 60/75C wire. Use copper conductors only. Undervoltage Alarm Output Connector Harness Manufacture Method Ambient Operating and Storage Environments Store the Power Supply at a temperature of -25 to 65C and a humidity of 25% to 90%. The following products are provided with the S8VM-05024A@/P@, S8VM-10024A@/P@ and S8VM-15024A@/P@ for the undervoltage alarm transistor output wiring. The Internal parts may occasionally be deteriorated or damaged. Do not use the Power Supply outside the derating range (i.e., under conditions indicated by the shaded area ( ) in the derating curve diagrams on pages 9 and 15.) Connector Use the Power Supply at a humidity of 30% to 85%. S8VMS8VM-10024A@/P@ Manu05024A@/P@ S8VM-15024A@/P@ factured by JST S3B-XH-A-1 BH3B-XH-2 Housing (provided) XHP-3 Terminal (provided) BXH-001T-P0.6 or SXH-001T-P0.6 Be sure to prepare the connector according to the following instructions to ensure correct wiring. For details, refer to the JST catalog. * Use a wire size of AWG28 to AWG22. * The guideline for the length of sheath to be stripped from the wire is 2.1 to 2.6 mm. * Use either a YC or YRS Crimping Tool (manufactured by JST) to crimp the terminal and wire. * Be sure to insert the crimped terminal wires into the housing fully until a click is heard. Also, make sure that the wires attached to the housing are securely locked in place. S12B-PHDSS Housing PHDR-12VS Terminal SPHD-001T-P0.5 or BPHD-001T-P0.5 Overcurrent Protection Internal parts may occasionally deteriorate or be damaged if a shortcircuited or other overcurrent state continues during operation. Eliminate the overcurrent state as soon as possible. Internal parts may possibly be deteriorated or damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. Charging the Battery Dielectric Strength Test The S8VM-300@@C/600@@C/15224C are using PHD connector (manufactured by JST). S8VM-300@@C/600@@C/15224C Do not use the Power Supply in locations where liquids, foreign matter, or corrosive gases may enter the interior of the Power Supply. If a battery is to be connected as the load, install an overcurrent limiting circuit and an overvoltage protection circuit. Signal I/O Connector Harness Manufacture Method Connector Do not use the Power Supply in locations subject to direct sunlight. Manufactured by JST Be sure to prepare the connector according to the following instructions to ensure correct wiring. For details, refer to the JST catalog. * Use a wire size of AWG26 to AWG22. * The guideline for the length of sheath to be stripped from the wire is 2.3 mm. If a high voltage is applied between an input and the case (PE/FG), it will pass though the LC of the built-in noise filter and energy will be stored. If the high voltages used for dielectric strength testing are turned ON and OFF with a switch, timer, or similar device, impulse voltage will be generated when the voltage is turned OFF and internal parts may possibly be damaged. To prevent the generation of impulse voltages, reduce the applied voltage slowly with a variable resistor on the test device or turn the voltage ON and OFF at the zero-cross point. When performing the test, be sure to short-circuit all the output terminals to protect them from damage. Check the waveform of the applied voltage while testing. High voltage due to distortions of the applied voltage may be produced depending on the type of testing equipment. Switch Mode Power Supply S8VM 33 Insulation Test Series Operation When performing the test, be sure to short-circuit all the output terminals to protect them from damage. Two Power Supplies can be connected in series. The () voltage output can be accomplished with two Power Supplies. Inrush Current Series Operation When two or more Power Supplies are connected to the same input, inrush current is added to the total current. Select fuses and circuit breakers giving sufficient consideration to the fusing or operating characteristics so that fuses will not burn and breakers will not break due to inrush current. Output Voltage Adjuster (V.ADJ) Default Setting: Set at the rated voltage Adjustable Range: Adjustable with output voltage adjuster (V.ADJ) on the front panel of the Power Supply from -20% to 20% of the rated output voltage (-10% to 20% of the rated voltage for S8VM@@@24A@/P@) Turning clockwise increases the output voltage and turning counterclockwise decreases the output voltage. The output voltage adjuster (V.ADJ) may possibly be damaged if it is turned with unnecessary force. Do not turn the adjuster with excessive force. After completing output voltage adjustment, be sure that the output capacity or output current does not exceed the rated output capacity or rated output current. The output voltage may increase beyond the allowable voltage range (up to +20% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged. When increasing the output voltage to more than +20% of the rated value using the output voltage adjuster (V. ADJ), the overvoltage protection function may operate. (S8VM-@@@24A@/P@ Only) Turn the output voltage adjuster (V.ADJ) slowly. When decreasing the output voltage quickly, or when adjusting the output voltage to less than -10% of the rated value, the undervoltage alarm function may operate. (S8VM-15224C Only) The rated ripple noise voltage was measured using a measuring circuit that conforms to the JEITA standard RC-9131A. CN AC (L) +V AC (L) +V AC (N) -V AC (N) -V AC (L) +V AC (L) +V AC (N) -V AC (N) -V Output Voltage () Correct AC (L) +V AC (N) -V AC (L) +V AC (N) -V Note: 1. If the load is short-circuited, a reverse voltage may be applied inside the Power Supply unit, and this may possibly cause the deterioration or damage of the Power Supply unit. Connect the diode as shown in the figure. Use the following guidelines to select the diode to be connected. Type Schottky Barrier diode Dielectric strength Twice the rated output voltage or (VRRM) above Forward current (IF) Twice the rated output current or above Parallel Operation 15/30/50/100/150-W Models +V S8VM 50W/100W/150W/300W/600W/ 1,500W Correct 2. Though Power Supplies having different specifications can be connected in series, the current flowing through the load must not exceed the smaller rated output current. Ripple + C1 -V 15W/30W Correct C2 Incorrect Coaxial cable 1.5 m 50 +V +S -V -S The Power Supply is not designed for parallel operation. Load R: 50 C1: 4700 pF C2: 22 uF C3: 0.47 uF R C3 Oscilloscope Frequency band 100 MHz Remote Sensing Function AC (L) +V AC (N) -V AC (L) +V AC (N) -V 100/150-W Models If the +S and -S terminals are opened by removing the short bar, the overvoltage protection function will be activated and the output voltage will be cut off. 300/600/1,500-W Models The stability and accuracy of the output will deteriorate if the +S or - S pins are open. Always connect the +S and -S pins. 34 Switch Mode Power Supply S8VM 300/600/1,500-W Models If the CB pin (pin 5 on CN) and the CBG pin (pin 6 on CN) are connected, the current balance function will operate and parallel operation will be possible at 80% or less of the total output capacity. Up to 2 Power Supplies can be connected. Check the overheat protected status. Correct AC (L) AC (N) AC (L) AC (N) +V S8VM CN CB CBG *1 CB CBG S8VM CN -V Turn OFF the input power and leave it OFF until the Power Supply cools sufficiently. Turn it ON again to see if this clears the condition. Check if the built-in fan motor has stopped. Check if the built-in fan motor has stopped. The fan is a consumable part. +V -V Check the remote control function. Use 2-conductor shielded cable as connection wire (* 1). Check if the +RC and -RC pins are open. Make the correct connections as specified. Adjust the output voltage of each Power Supply to the same value within 1% or 100 mV, whichever is smaller, using the output voltage adjuster (V. ADJ). Fan Replacement Parallel operation is used to increase static capacity. The output voltage may drop with sudden load fluctuations. 300/600/1,500-W Models Remove the standard supplied connector and prepare a connector separately. In Case There Is No Output Voltage 15/30/50/100/150-W Models The possible cause for no output voltage may be that the overcurrent protection or overvoltage protection has operated. The internal protection circuit may operate if a large amount of surge voltage such as a lightening surge occurs while turning ON the input power. Consult with OMRON regarding fan replacement. OMRON will replace fans for a fee. A replacement Fan Unit (S82Y-VM@@FAN) is available. Use the curve in the graph below as a rough measure of replacement timing. Expected service life (years) There may be steps in the rising waveform of the output voltage during parallel operation. 10 7 5 3 2 If there is no output voltage even after checking the following points please contact your OMRON representative. Check the overload protected status. Check whether the load is in overload status or is short-circuited. Remove the load wires when checking. Attempt to clear the overvoltage or internal protection function. Turn OFF the input power once and leave it OFF for at least 3 minutes. Then turn it ON again to see if this clears the condition. Check whether the +S terminal or -S terminal is open, i.e., if the short bar has been removed. (S8VM-100@@@@/S8VM-150@@@@ only) Check if the output voltage has been adjusted to more than +20% of the rated value using the output voltage adjuster (V. ADJ). 300/600/1,500-W Models The possible cause for no output voltage may be that the overcurrent protection, overvoltage protection, or overheat protection has operated. Alternatively, the built-in fan may have stopped or the remote control function may be OFF. If there is no output voltage even after checking the following points, please contact your OMRON representative. Check the overload protected status. Check whether the load is in overload status or is short-circuited. Remove the load wires when checking. Attempt to clear the overvoltage protection function. Turn OFF the input power once and leave it OFF for at least 3 minutes. Then turn it ON again to see if this clears the condition. Check whether the +S terminal or -S terminal is open, i.e., if the short bar has been removed. Check if the output voltage has been adjusted to more than +20% of the rated value using the output voltage adjuster (V. ADJ). 1 0 40 50 60 70 80 100 Exhaust temperature: C Note: Expected fan service life Exhaust temperature 45C: 45,000 hours Exhaust temperature 80C: 11,000 hours The Power Supply will not conform to safety standards if the customer replaces the fan. Buzzing Noise when the Input Is Turned ON 50/100/150/300/600/1,500-W Models A harmonic current suppression circuit is built into the input power. This circuit can create noise when the input is turned ON, but it will last only until internal operation stabilizes and does not indicate any problem in the Power Supply. DIN Rail Mounting 15/30/50/100/150/300/600-W Models When mounting to a DIN Rail, lower the S8VM onto the Rail until the Rail stopper clicks into place, hook section A over the edge of the Rail and push in the direction of B. To remove the S8VM from the DIN Rail, insert a screwdriver into section C and pull the S8VM away from the Rail. 30 mm min. Rail stopper Switch Mode Power Supply S8VM 35 Warranty and Application Considerations Read and Understand this Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. Replacement fans, however, are available for a fee. Contact OMRON to replace fans. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Disclaimers PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. T031-E1-02 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company Control Devices Division H.Q. Power Electronics Department Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7108/Fax: (81)75-344-7189 Printed in Japan 0506-1.5M (0705) (C)