1 ___________________ Preface 2 ___________________ Guide SIMATIC ET 200SP BusAdapter Manual 3 ___________________ Product overview 4 ___________________ BusAdapter BA 2xRJ45 5 ___________________ BusAdapter BA 2xFC 6 ___________________ BusAdapter BA 2xSCRJ 7 ___________________ BusAdapter BA SCRJ/RJ45 8 ___________________ BusAdapter BA SCRJ/FC 9 ___________________ BusAdapter BA 2xLC 10 ___________________ BusAdapter BA LC/RJ45 ___________________ 11 BusAdapter BA LC/FC ___________________ 12 Strain relief ___________________ A Dimension drawings ___________________ B Accessories 03/2018 A5E41449003-AA Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Digital Factory Postfach 48 48 90026 NURNBERG GERMANY A5E41449003-AA 02/2018 Subject to change Copyright (c) Siemens AG 2018. All rights reserved Table of contents 1 Preface ................................................................................................................................................... 5 2 Guide ...................................................................................................................................................... 8 2.1 BusAdapter guide ..................................................................................................................... 8 3 Product overview .................................................................................................................................. 11 4 BusAdapter BA 2xRJ45......................................................................................................................... 14 5 6 7 8 4.1 Product overview ....................................................................................................................14 4.2 Connecting ..............................................................................................................................15 4.3 Diagnostics .............................................................................................................................18 4.4 Technical specifications ..........................................................................................................19 BusAdapter BA 2xFC ............................................................................................................................ 20 5.1 Product overview ....................................................................................................................20 5.2 Connecting ..............................................................................................................................21 5.3 Diagnostics .............................................................................................................................25 5.4 Technical specifications ..........................................................................................................26 BusAdapter BA 2xSCRJ........................................................................................................................ 27 6.1 Product overview ....................................................................................................................27 6.2 Connecting ..............................................................................................................................28 6.3 Diagnostics .............................................................................................................................32 6.4 Technical specifications ..........................................................................................................34 BusAdapter BA SCRJ/RJ45 .................................................................................................................. 35 7.1 Product overview ....................................................................................................................35 7.2 Connecting ..............................................................................................................................36 7.3 Diagnostics .............................................................................................................................38 7.4 Technical specifications ..........................................................................................................40 BusAdapter BA SCRJ/FC...................................................................................................................... 41 8.1 Product overview ....................................................................................................................41 8.2 Connecting ..............................................................................................................................42 8.3 Diagnostics .............................................................................................................................44 8.4 Technical specifications ..........................................................................................................46 BusAdapter Manual, 03/2018, A5E41449003-AA 3 Table of contents 9 10 11 12 A B BusAdapter BA 2xLC ............................................................................................................................ 47 9.1 Product overview.................................................................................................................... 47 9.2 Connecting ............................................................................................................................. 48 9.3 Diagnostics ............................................................................................................................. 52 9.4 Technical specifications ......................................................................................................... 53 BusAdapter BA LC/RJ45 ....................................................................................................................... 54 10.1 Product overview.................................................................................................................... 54 10.2 Connecting ............................................................................................................................. 55 10.3 Diagnostics ............................................................................................................................. 57 10.4 Technical specifications ......................................................................................................... 58 BusAdapter BA LC/FC .......................................................................................................................... 59 11.1 Product overview.................................................................................................................... 59 11.2 Connecting ............................................................................................................................. 60 11.3 Diagnostics ............................................................................................................................. 62 11.4 Technical specifications ......................................................................................................... 63 Strain relief ........................................................................................................................................... 64 12.1 Product overview.................................................................................................................... 64 12.2 Installing ................................................................................................................................. 65 Dimension drawings .............................................................................................................................. 67 A.1 BusAdapter dimension drawings ........................................................................................... 67 A.2 Strain relief dimension drawings ............................................................................................ 67 Accessories .......................................................................................................................................... 68 B.1 Accessories ............................................................................................................................ 68 BusAdapter 4 Manual, 03/2018, A5E41449003-AA 1 Preface Purpose of the manual This manual provides all the necessary information for configuring, installing, connecting and commissioning the BusAdapter. Basic knowledge required The following knowledge is required in order to understand the manual: General knowledge in the field of automation technology Knowledge of the use of computers or PC -like tools (e.g. programming devices) under the Windows operating system. Knowledge of working with STEP 7. You can find information on this topic in the STEP 7 online help. Range of validity of this manual The manual describes the components based on the data valid at the time of its release. We reserve the right to include up-to-date Product Information with new components and new versions of components. BusAdapter Manual, 03/2018, A5E41449003-AA 5 Preface Recycling and disposal The BusAdapter can be recycled due to their low pollutant content. For environmentally sustainable recycling and disposal of your old device, please contact a company certified for the disposal of electronic waste. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial security concept. Siemens' products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial security measures that may be implemented, please visit (https://www.siemens.com/industrialsecurity). Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under (https://www.siemens.com/industrialsecurity). BusAdapter 6 Manual, 03/2018, A5E41449003-AA Preface Siemens Industry Online Support You can find current information on the following topics quickly and easily here: Product support All the information and extensive know-how on your product, technical specifications, FAQs, certificates, downloads, and manuals. Application examples Tools and examples to solve your automation tasks - as well as function blocks, performance information and videos. Services Information about Industry Services, Field Services, Technical Support, spare parts and training offers. Forums For answers and solutions concerning automation technology. mySupport Your personal work area in Industry Online Support for messages, support queries, and configurable documents. This information is provided by the Siemens Industry Online Support on the Internet (http://www.siemens.com/automation/service&support). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP). You can find catalogs for all automation and drive products on the Internet (https://mall.industry.siemens.com). BusAdapter Manual, 03/2018, A5E41449003-AA 7 2 Guide 2.1 BusAdapter guide Device information The BusAdapter manual contains information, for example, on properties, assembling, connecting, configuring and parameter assignment, alarms and diagnostics and technical specifications of the BusAdapter. General information The function manuals contain detailed descriptions on general topics such as PROFINET and communication. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/de/view/109742709). "mySupport" With "mySupport", your personal work area, you make the most of your Industry Online Support. In "mySupport" you can store filters, favorites and tags, request CAx data and put together your personal library in the Documentation area. Furthermore, your data is automatically filled into support requests and you always have an overview of your current requests. You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/de/). BusAdapter 8 Manual, 03/2018, A5E41449003-AA Guide 2.1 BusAdapter guide "mySupport" - Documentation In the Documentation area of "mySupport", you have the possibility to combine complete manuals or parts of them to make your own manual. You can export the manual in PDF format or in an editable format. Your documentation is available in My Documentation Manager (http://support.industry.siemens.com/My/ww/de/documentation). "mySupport" - CAx data In the CAx data area in "mySupport", you can access the current product data for your CAx or CAe system. You configure your own download package with a few clicks. In doing so you can select: Product images, 2D dimension drawings, 3D models, internal circuit diagrams, EPLAN macro files Manuals, characteristics, operating manuals, certificates Product master data You can find "mySupport" - CAx data on the Internet (http://support.industry.siemens.com/my/ww/de/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system separated from the focus on individual products. Additional information can be found on the Internet under Application examples (https://support.industry.siemens.com/sc/ww/de/sc/2054). BusAdapter Manual, 03/2018, A5E41449003-AA 9 Guide 2.1 BusAdapter guide SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities simultaneously on various SIMATIC S7 stations as a bulk operation independent of the TIA Portal. The SIMATIC Automation Tool provides a multitude of functions: Scanning of a PROFINET/Ethernet system network and identification of all connected CPUs Address assignment (IP, subnet, gateway) and station name (PROFINET device) to a CPU Transfer of the date and the programming device/PC time converted to UTC time to the module Program download to CPU RUN/STOP mode switchover CPU localization by means of LED flashing Reading out of CPU error information Reading of the CPU diagnostic buffer Reset to factory settings Firmware update of the CPU and connected modules You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/de/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: The topology overview independently scans PROFINET and all connected components. PRONETA also scans: configuration of the station name, IP subnet mask and identification and maintenance data (I&M1..3) For more information, refer to SIEMENS PRONETA (https://support.industry.siemens.com/cs/ww/de/view/67460624). BusAdapter 10 Manual, 03/2018, A5E41449003-AA 3 Product overview Introduction The SIMATIC BusAdapters connect PROFINET IO to their ET 200SP system. You select the required connection technology and connection method for your process from the different versions of SIMATIC BusAdapter. Supported PROFINET devices The SIMATIC BusAdapters are used for: ET 200SP interface module and central processing unit (CPU and Open Controller) PN/PN Coupler Switches Overview The SIMATIC BusAdapters can be ordered in the following versions: BusAdapter Article number Property BA 2xRJ45 6ES7193-6AR000AA0 PROFINET BusAdapter with standard Ethernet socket for standard RJ45 connector BA 2xFC 6ES7193-6AF000AA0 PROFINET BusAdapter with FastConnect Ethernet connection for direct connection of the bus cable for applications with increased EMC and vibration/shock load Figure BusAdapter Manual, 03/2018, A5E41449003-AA 11 Product overview BusAdapter Article number Property BA 2xSCRJ 6ES7193-6AP000AA0 PROFINET BusAdapter with fiberoptic cable connection POF/PCF for SCRJ connector for applications with increased EMC and vibration/shock load as well as electrical potential differences between two stations Figure BA SCRJ/RJ45 6ES7193-6AP200AA0 Media converter, PROFINET BusAdapter with POF/PCF fiberoptic cable standard RJ45 connector BA SCRJ/FC 6ES7 193-6AP400AA0 Media converter, PROFINET BusAdapter with POF/PCF fiberoptic cable direct connection of bus cable BA 2xLC 6ES7193-6AG000AA0 PROFINET BusAdapter with glass fiber-optic cable connection for LC connector for applications with increased EMC and vibration/shock load as well as electrical potential differences between two stations BusAdapter 12 Manual, 03/2018, A5E41449003-AA Product overview BusAdapter Article number Property BA LC/RJ45 6ES7193-6AG200AA0 Media converter, PROFINET BusAdapter with glass fiber-optic cable standard RJ45 connector BA LC/FC 6ES7193-6AG400AA0 Media converter, PROFINET BusAdapter with glass fiber-optic cable direct connection of bus cable Figure See also Strain relief (Page 64) BusAdapter Manual, 03/2018, A5E41449003-AA 13 4 BusAdapter BA 2xRJ45 4.1 Product overview Article number 6ES7193-6AR00-0AA0 View Figure 4-1 BusAdapter BA 2xRJ45 Properties You connect PROFINET IO cable with RJ45 connector to the PROFINET device via the BusAdapter BA 2xRJ45. To do this, screw the BusAdapter BA 2xRJ45 to the PROFINET device and insert the PROFINET connecting cable. You loop through the PROFINET via the integrated 2-port switch. BusAdapter 14 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xRJ45 4.2 Connecting 4.2 Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required Connector: - IE FC RJ45 plug 180 2X2 (6GK1901-1BB10-2A) - IE FC RJ45 plug 180 4X2 (6GK1901-1BB12-2A) Cables: - IE FC TP standard cable (6XV1840-2A) - IE FC TP trailing cable (6XV1840-3AH10) - IE FC TP marine cable (6XV1840-4AH10) - IE FC TP robust cable (6XV1841-2) - IE TP torsion cable (6XV1870-2F) Please observe the specifications in the PROFINET Installation Guide (http://www.profibus.com/). BusAdapter Manual, 03/2018, A5E41449003-AA 15 BusAdapter BA 2xRJ45 4.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2xRJ45. Table 4- 1 PROFINET IO pin assignment with BusAdapter BA 2xRJ45 View Signal name Description 1 TD Transmit Data + 2 TD_N Transmit Data - 3 RD Receive Data + 4 TERM1 Termination Network 1 5 TERM1 Termination Network 1 6 RD_N Receive Data - 7 TERM2 Termination Network 2 8 TERM2 Termination Network 1 Procedure Watch video sequence "Connect BusAdapter BA 2xRJ45 to the ET 200SP interface module" (https://support.industry.siemens.com/cs/ww/de/view/95886218) To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xRJ45, follow these steps: 1. Plug the BusAdapter BA 2xRJ45 into the PROFINET device. 2. Screw the BusAdapter BA 2xRJ45 to the PROFINET device (1 screw with 0.2 Nm tightening torque). 3. Plug the RJ45 bus connector into the PROFINET port on the BusAdapter BA 2xRJ45. You can also swap steps 2 and 3. BusAdapter 16 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xRJ45 4.2 Connecting BusAdapter BA 2xRJ45 installed CPU BusAdapter BA 2xRJ45 PROFINET connecting cable Interface module Figure 4-2 BusAdapter BA 2xRJ45 installed (using an ET 200SP CPU/interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter Manual, 03/2018, A5E41449003-AA 17 BusAdapter BA 2xRJ45 4.3 Diagnostics 4.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xRJ45: LK1 (green) LK2 (green) Figure 4-3 LEDs on the BusAdapter BA 2xRJ45 LK1/LK2 LEDs on the BusAdapter Table 4- 2 Status and error displays LED Meaning Remedy LK1/LK2 off There is no Ethernet connection between the Check whether the bus cable to the switch or IO controller is disconnected. PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. on There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. flashes The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - BusAdapter 18 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xRJ45 4.4 Technical specifications 4.4 Technical specifications Technical specifications of the BusAdapter BA 2xRJ45 Article number 6ES7193-6AR00-0AA0 Interfaces Number of PROFINET interfaces 1 PROFINET IO * RJ 45 Yes; 2 x * FC (FastConnect) No * Number of SCRJ ports 0 * Number of LC ports 0 Cable length - Cu conductors 100 m Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 46 g BusAdapter Manual, 03/2018, A5E41449003-AA 19 5 BusAdapter BA 2xFC 5.1 Product overview Article number 6ES7193-6AF00-0AA0 View Figure 5-1 BusAdapter BA 2xFC Properties You connect PROFINET IO cable with FastConnect connection method to the PROFINET device via the BusAdapter BA 2xFC. To do this, screw the BusAdapter BA 2xFC with the connected PROFINET connection cable in place on the PROFINET device. You loop through the PROFINET via the integrated 2-port switch. BusAdapter 20 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xFC 5.2 Connecting 5.2 Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required If you use Fast Connect Cable, we recommend the Industrial Ethernet Fast Connect Stripping Tool (6GK1901-1GA00) with green knife cassette (6GK1901-1B). This guarantees fast and safe stripping. Fast Connect Cable (recommended types): - IE FC TP Standard Cable GP 2x2 (6XV1840-2AH10) - IE FC TP Trailing Cable 2x2 (6XV1840-3AH10) - IE FC TP Marine Cable (6XV1840-4AH10) - IE FC TP Flexible Cable GP 2x2 (6XV1870-2B) - IE FC TP Trailing Cable 2x2 (6XV1870-2D) - IE TP Torsion Cable 2x2 (6XV1870-2F) - FC TP FRNC Cable GP (6XV1871-2F) - IE FC TP Food Cable GP 2x2 (6XV1871-2L) - IE FC TP Festoon Cable 2x2 (6XV1871-2S) Please observe the specifications in the PROFINET Installation Guide (http://www.profibus.com/). BusAdapter Manual, 03/2018, A5E41449003-AA 21 BusAdapter BA 2xFC 5.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2xFC:. Table 5- 1 PROFINET IO pin assignment with BusAdapter BA 2xFC View Signal name Description 1 RD_N Receive Data - 2 TD_N Transmit Data - 3 RD Receive Data + 4 TD Transmit Data + Procedure Watch the video sequence "Connecting the BusAdapter BA 2xFC to the interface module" (https://support.industry.siemens.com/cs/ww/de/view/95886218) To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xFC, follow these steps: 1. Strip insulation from the sheath of the PROFINET connecting cable as follows: Figure 5-2 PROFINET connecting cable 2. Pull back the locking slide and fold up the cover of the connection element. 3. Pull up the wire guide as far as it will go. 4. Insert the unstripped single cores of the PROFINET connecting cable into the cable routing as far as it will go. Firmly press down the wire guide as far as it will go. Please refer to the color coding. BusAdapter 22 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xFC 5.2 Connecting 5. Close the cover of the connection element. Then push the locking slide forwards as far as it will go. 6. Screw the BusAdapter BA 2xFC to the PROFINET device (1 screw with 0.2 Nm tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10. Locking slide Wire guide Figure 5-3 Shield contact PROFINET connecting cable Connection of the PROFINET IO BusAdapter BA 2xFC BusAdapter Manual, 03/2018, A5E41449003-AA 23 BusAdapter BA 2xFC 5.2 Connecting BusAdapter BA 2xFC installed CPU BA 2xFC BusAdapter PROFINET connecting cable Connection element Figure 5-4 BusAdapter BA 2xFC installed (using an ET 200SP CPU/interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter 24 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xFC 5.3 Diagnostics 5.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xFC: LK1 (green) LK2 (green) Figure 5-5 LEDs on the BusAdapter BA 2xFC LK1/LK2 LEDs on the BusAdapter Table 5- 2 Status and error displays LED Meaning Remedy LK1/LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. - on The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - flashes BusAdapter Manual, 03/2018, A5E41449003-AA 25 BusAdapter BA 2xFC 5.4 Technical specifications 5.4 Technical specifications Technical specifications of the BusAdapters BA 2xFC Article number 6ES7193-6AF00-0AA0 Interfaces Number of PROFINET interfaces 1 PROFINET IO * FC (FastConnect) Yes; 2 x Cable length - Cu conductors 100 m Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 53 g BusAdapter 26 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xSCRJ 6.1 6 Product overview Article number 6ES7193-6AP00-0AA0 View Figure 6-1 BusAdapter BA 2xSCRJ Properties Using BusAdapter BA 2xSCRJ , you connect PROFINET IO to the PROFINET device optically with fiber-optic cables via an SCRJ connector. To do this, screw the BusAdapter BA 2xSCRJ to the PROFINET device and plug in the SCRJ connector. You loop through the PROFINET via the integrated 2-port switch. SCRJ connector is suitable for POF and PCF. BusAdapter Manual, 03/2018, A5E41449003-AA 27 BusAdapter BA 2xSCRJ 6.2 Connecting 6.2 Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required Connector for PROFINET connection: IE SCRJ POF Plug Fiber-optic cable: - IE POF standard cable (6XV1874-2A) - IE POF trailing cable (6XV1874-2B) - IE PCF standard cable (6XV1861-2A) - IE PCF trailing cable (6XV1861-2C) - IE PCF trailing cable, GI (6XV1861-2D) BusAdapter 28 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xSCRJ 6.2 Connecting Requirements Prepare the IE POF cables with the connectors IE SCRJ POF Plug or IE SC RJ PCF Plug. You will find more Instructions in the installation instructions: - POF fiber-optic cables with IE SCRJ POF plugs (A5E00351141). - PCF fiber-optic cables with IE SCRJ PCF plugs (A5E00835119). When installing the fiber-optic cable, make sure the bending radius is not less than permitted: - IE POF/PCF standard cable: 150 mm - IE POF/PCF trailing cable: 60 mm The maximum lengths of the fiber-optic cables are as follows: - IE POF standard cable: 50 m - IE POF trailing cable: 50 m - IE POF standard cable: 100 m - IE PCF trailing cable: 100 m - IE PCF trailing cable, GI: 250 m When the PROFINET device is the last device of the fiber-optic cable network, the unoccupied fiber-optic cable interface must be closed with a blanking plug. When the modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter. BusAdapter Manual, 03/2018, A5E41449003-AA 29 BusAdapter BA 2xSCRJ 6.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2xSCRJ. Table 6- 1 PROFINET IO pin assignment with BusAdapter BA 2xSCRJ View Signal name Description Receive Data Transmit Data Procedure 1. Plug the BusAdapter BA 2xSCRJ into the PROFINET device. 2. Screw the BusAdapter BA 2xSCRJ to the PROFINET device (1 screw with 0.2 Nm tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10. 3. Remove the blanking plugs from the PROFINET sockets. 4. Hold the prepared connector by the housing. Insert it into the PROFINET socket on the BusAdapter BA 2xLC until you hear it click into place. The coding of the connectors ensures a safe connection. CAUTION Risk of damage to eyes Do not look directly into the opening of the optical transmitter diodes. The emitted light beam damages your eyes. You can swap steps 3 and 4. BusAdapter 30 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xSCRJ 6.2 Connecting BusAdapter BA 2xSCRJ installed Interface module BusAdapter BA 2xSCRJ PROFINET connecting cable (fiber-optic cable) Figure 6-2 BusAdapter BA 2xSCRJ connected to interface module (using ET 200SP interface module as an example) Reusing used fiber-optic cables Note Shorten both fiber-optic cores by the amount of the curved lengths and reassemble the connectors. This will prevent any attenuation losses caused by re-bent, heavily stressed portions of the fiber-optic cores. Reference For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC NET PROFIBUS Network Manual (https://support.industry.siemens.com/cs/de/de/view/1172302). BusAdapter Manual, 03/2018, A5E41449003-AA 31 BusAdapter BA 2xSCRJ 6.3 Diagnostics 6.3 Diagnostics LEDs The figure below shows the LED display on the BusAdapter BA 2xSCRJ: LK1 (green) MT1 (yellow) LK2 (green) MT2 (yellow) Figure 6-3 LEDs on the BusAdapter BA 2xSCRJ BusAdapter 32 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xSCRJ 6.3 Diagnostics LK1/LK2 and MT1/MT2 LEDs on the BusAdapter Table 6- 2 Status and error displays LED LK1/LK2 Meaning Remedy Not relevant There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. Not relevant There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. - Not relevant The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - No error - MT1/MT2 off on flashes Not relevant off Not relevant on Causes and measures for the transmission route: * Fiber-optic error * Maintenance demanded: attenua* tion through the fiber-optic cable is already so high that operation will soon no longer be possible. * Replace the fiber-optic cable if damaged or aged. Ensure correct installation of the PROFINET plugs or PROFINET connectors. * Adhere to maximum length of 50 m for POF cable or 100 m for PCF cable. * Ensure that the FOC connectors fit securely. BusAdapter Manual, 03/2018, A5E41449003-AA 33 BusAdapter BA 2xSCRJ 6.4 Technical specifications 6.4 Technical specifications Technical specifications of BusAdapter BA 2xSCRJ Article number 6ES7193-6AP00-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) SCRJ FO PROFINET IO * RJ 45 No * FC (FastConnect) No * Number of SCRJ ports 2 * Number of LC ports 0 Cable length - PCF 100 m - Plastic FOC (POF) 50 m - PCF-GI 250 m Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 50 g BusAdapter 34 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/RJ45 7.1 7 Product overview Article number 6ES7193-6AP20-0AA0 View Fiber-optic cable SCRJ RJ45 Figure 7-1 BusAdapter BA SCRJ/RJ45 Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA SCRJ/RJ45: Optically with fiber-optic cables (FOC) with an SCRJ connector to port 1 Electrically with a standard RJ45 connector to port 2 To do this, screw the BusAdapter BA SCRJ/RJ45 to the PROFINET device and plug in the SCRJ connector or the RJ45 connector. You can loop through PROFINET IO via the integrated 2-port switch. You can use any port of the BusAdapter for feeding or for looping through. The integrated media converter converts the signals automatically. BusAdapter Manual, 03/2018, A5E41449003-AA 35 BusAdapter BA SCRJ/RJ45 7.2 Connecting 7.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Connecting the SCRJ connector You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2xSCRJ (Page 28). Connecting the RJ45 connector You can find more information about the required tools, accessories and procedures in the section Connecting BusAdapter BA 2xRJ45 (Page 15). Pin assignment The following table shows the signal names and description of the pin assignment for the BusAdapter BA SCRJ/RJ45: Table 7- 1 PROFINET IO pin assignment with BusAdapter BA SCRJ/RJ45 View Signal name Description Receive Data Transmit Data 1 TD Transmit Data + 2 TD_N Transmit Data - 3 RD Receive Data + 4 TERM1 Termination Network 1 5 TERM1 Termination Network 1 6 RD_N Receive Data - 7 TERM2 Termination Network 2 8 TERM2 Termination Network 2 BusAdapter 36 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/RJ45 7.2 Connecting BA SCRJ/RJ45 BusAdapter mounted Interface module BusAdapter BA SCRJ/RJ45 PROFINET connecting cable Figure 7-2 Connecting the BusAdapter BA SCRJ/RJ45 to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter Manual, 03/2018, A5E41449003-AA 37 BusAdapter BA SCRJ/RJ45 7.3 Diagnostics 7.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA SCRJ/RJ45: LK1 (green) MT (yellow) LK2 (green) Figure 7-3 LED displays on the BusAdapter BA SCRJ/RJ45 BusAdapter 38 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/RJ45 7.3 Diagnostics LK1/LK2 and MT LEDs on the BusAdapter Table 7- 2 Status and error displays LED LK1/LK2 Meaning Remedy Not relevant There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. Not relevant There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. - Not relevant The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - No error - MT off on flashes Not relevant off Not relevant on Causes and measures for the transmission route: * Fiber-optic error * Maintenance demanded: attenua* tion through the fiber-optic cable is already so high that operation will soon no longer be possible. * Replace the fiber-optic cable if damaged or aged. Ensure correct installation of the PROFINET plugs or PROFINET connectors. * Adhere to maximum length of 50 m for POF cable or 100 m for PCF cable. * Ensure that the FOC connectors fit securely. BusAdapter Manual, 03/2018, A5E41449003-AA 39 BusAdapter BA SCRJ/RJ45 7.4 Technical specifications 7.4 Technical specifications Technical specifications of BusAdapter BA SCRJ/RJ45 Article number 6ES7193-6AP20-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (SCRJ + RJ45) PROFINET IO * RJ 45 Yes; 1x * FC (FastConnect) No * Number of SCRJ ports 1 * Number of LC ports 0 Cable length - PCF 100 m - Plastic FOC (POF) 50 m - PCF-GI 250 m - Cu conductors 100 m Dimensions Width 20 mm Weights Weight, approx. 50 g BusAdapter 40 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/FC 8.1 8 Product overview Article number 6ES7193-6AP40-0AA0 View SCRJ fiber-optic cable FastConnect FC Figure 8-1 BusAdapter BA SCRJ/FC Properties You connect PROFINET IO to the PROFINET device via the BusAdapter BA SCRJ/FC . The BusAdapter BA SCRJ/FC has one port for connection of a copper cable and one port for connection of a fiber-optic cable. Screw the BusAdapter BA SCRJ/FC with the attached Fast Connect bus cable onto the interface module and plug in the SCRJ connector. You loop through the PROFINET IO via the integrated 2-port switch. You can use any port of the BusAdapter for feeding or for looping through. The integrated media converter converts the signals automatically. BusAdapter Manual, 03/2018, A5E41449003-AA 41 BusAdapter BA SCRJ/FC 8.2 Connecting 8.2 Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Connecting the SCRJ connector You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2xSCRJ (Page 28). Connecting the RJ45 connector You can find more information about the required tools, accessories and procedures in the section Connecting BusAdapter BA 2xFC (Page 21). Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA SCRJ/FC. Table 8- 1 PROFINET IO pin assignment with BusAdapter BA SCRJ/FC View Signal name Description Receive Data Transmit Data 1 RD_N Receive Data - 2 TD_N Transmit Data - 3 RD Receive Data + 4 TD Transmit Data + BusAdapter 42 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/FC 8.2 Connecting Procedure To connect PROFINET IO to the PROFINET device via the BusAdapter BA SCRJ/FC, follow these steps: 1. Plug the BusAdapter BA SCRJ/FC into the PROFINET device. 2. Screw the BusAdapter BA SCRJ/FC to the PROFINET device (1 screw with 0.2 Nm tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10. 3. Plug the RJ45 bus connector into the PROFINET port on the BusAdapter BA SCRJ/FC. BA SCRJ/FC BusAdapter mounted Interface module BusAdapter BA SCRJ/FC PROFINET connecting cable Figure 8-2 BusAdapter BA SCRJ/FC installed (using an ET 200SP interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter Manual, 03/2018, A5E41449003-AA 43 BusAdapter BA SCRJ/FC 8.3 Diagnostics 8.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA SCRJ/FC: LK1 (green) MT (yellow) LK2 (green) Figure 8-3 LEDs on the BusAdapter BA SCRJ/FC BusAdapter 44 Manual, 03/2018, A5E41449003-AA BusAdapter BA SCRJ/FC 8.3 Diagnostics LK1/LK2 and MT LEDs on the BusAdapter Table 8- 2 Status and error displays LED LK1/LK2 Meaning Remedy Not relevant There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. Not relevant There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. - Not relevant The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - No error - MT off on flashes Not relevant off Not relevant on * Fiber-optic error * Maintenance demanded: attenuation through the fiber-optic cable is already so high that operation will soon no longer be possible. Causes and measures for the transmission route: * Replace the fiber-optic cable if damaged or aged. * Ensure correct installation of the PROFINET plugs or PROFINET connectors. * Adhere to maximum length of 50 m for POF cable or 100 m for PCF cable. * Ensure that the FOC connectors fit securely. BusAdapter Manual, 03/2018, A5E41449003-AA 45 BusAdapter BA SCRJ/FC 8.4 Technical specifications 8.4 Technical specifications Technical specifications of BusAdapter BA SCRJ/FC Article number 6ES7193-6AP40-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (SCRJ + FC) PROFINET IO * RJ 45 No * FC (FastConnect) Yes; 1x * Number of SCRJ ports 1 * Number of LC ports 0 Cable length - PCF 100 m - Plastic FOC (POF) 50 m - PCF-GI 250 m - Cu conductors 100 m Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 50 g BusAdapter 46 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xLC 9.1 9 Product overview Article number 6ES7193-6AG00-0AA0 View Figure 9-1 BusAdapter BA 2xLC Properties You connect PROFINET IO fiber-optic cables to the PROFINET device via the BusAdapter BA 2xLC. To do this, screw the BusAdapter BA 2xLC to the PROFINET device and insert the PROFINET connection cable. You loop through the PROFINET via the integrated 2-port switch. BusAdapter Manual, 03/2018, A5E41449003-AA 47 BusAdapter BA 2xLC 9.2 Connecting 9.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required If you prepare the FC FO cables with the IE FC FO LC plug, we recommend the FC FO Termination Kit (LC) (6GK1900-0RL00-0AA0). You can cleave the glass fiber precisely using the FC FO Termination Kit (LC). CAUTION Cleaving the glass fiber * Wear protective glasses during the cleaving process. * Dispose of the remaining fibers in a suitable waste container. Connector for PROFINET fiber-optic cable connection: IE FC FO LC Plug (10 duplex plugs: 6GK1900-1RB00-2AB0) Fiber-optic cable: - IE FC FO Standard Cable GP (62.5/200/230) (6XV1847-2A) - IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C) - IE FC FO Robust Cable (6XV1873-5Rxx) - IE FC FO Standard Cable (6XV1873-3Axx) BusAdapter 48 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xLC 9.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2xLC: Table 9- 1 PROFINET IO pin assignment with BusAdapter BA 2xLC View Signal name Description Receive Data Transmit Data Requirements Prepare the IE FC FO cable with the IE FC FO LC plug connectors. For detailed instructions, refer to the assembly instructions Preparing IE FC FO Cable with the plug-in connector IE FC FO LC Plug (A5E36312721). When installing the fiber-optic cable, make sure the bending radius is not less than permitted: - IE FC FO Standard Cable GP (62.5/200/230): 70 mm - IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C): 88 mm The maximum lengths of the fiber-optic cables are as follows: - IE FC FO Standard Cable GP (62.5/200/230): 2 km - IE FC FO Trailing Cable (62.5/200/230): 2 km When the interface module is the last device of the fiber-optic cable network, the unoccupied fiber-optic cable interface must be closed with a blanking plug. When the modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter. BusAdapter Manual, 03/2018, A5E41449003-AA 49 BusAdapter BA 2xLC 9.2 Connecting Procedure To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xLC, follow these steps: 1. Plug the BusAdapter BA 2xLC into the PROFINET device. 2. Screw the BusAdapter BA 2xLC to the PROFINET device (1 screw with 0.2 Nm tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10. 3. Remove the blanking plugs from the PROFINET sockets. 4. Hold the prepared connector by the housing. Insert it into the PROFINET socket on the BusAdapter BA 2xLC until you hear it click into place. The coding of the connectors ensures a safe connection. CAUTION Risk of damage to eyes Do not look directly into the opening of the optical transmitter diodes. The emitted light beam damages your eyes. BusAdapter 50 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xLC 9.2 Connecting BusAdapter BA 2xLC installed Interface module BusAdapter BA 2xLC PROFINET glass fiber connecting cable Figure 9-2 Connecting the BusAdapter BA 2xLC to the interface module Reusing used fiber-optic cables Note Shorten both fiber-optic cores by the amount of the curved lengths and reassemble the connectors. This will prevent any attenuation losses caused by re-bent, heavily stressed portions of the fiber-optic cores. Reference For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC NET PROFIBUS Network Manual (https://support.industry.siemens.com/cs/de/de/view/1172302). BusAdapter Manual, 03/2018, A5E41449003-AA 51 BusAdapter BA 2xLC 9.3 Diagnostics 9.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xLC: LK1 (green) LK2 (green) Figure 9-3 LEDs on the BusAdapter BA 2xLC LK1/LK2 LEDs on the BusAdapter Table 9- 2 Status and error displays LED Meaning Remedy LK1/LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. - on The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - flashes BusAdapter 52 Manual, 03/2018, A5E41449003-AA BusAdapter BA 2xLC 9.4 Technical specifications 9.4 Technical specifications Technical specifications of BusAdapter BA 2xLC Article number 6ES7193-6AG00-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) LC Multimode Glass Fibre PROFINET IO * RJ 45 No * FC (FastConnect) No * Number of SCRJ ports 0 * Number of LC ports 2; Wavelength of 1 270 ... 1 380 nm, corresponds to 100BASE-FX Cable length - Multimode graded-index fiber 50/125 m 3 km - Multimode graded-index fiber 62.5/125 m 3 km Ambient conditions Ambient temperature during operation * min. 0 C * max. 60 C Dimensions Width 20 mm Height 69.5 mm Depth 59 mm BusAdapter Manual, 03/2018, A5E41449003-AA 53 10 BusAdapter BA LC/RJ45 10.1 Product overview Article number 6ES7193-6AG20-0AA0 View Glass fiber-optic cable LC RJ45 Figure 10-1 BusAdapter BA LC/RJ45 Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA LC/RJ45: Optically with glass fiber-optic cables with an LC connector to port 1 Electrically with a standard RJ45 connector to port 2 To do this, screw the BusAdapter BA LC/RJ45 to the PROFINET device and plug in the LC connector or the RJ45 connector. You can loop through PROFINET IO via the integrated 2-port switch. You can use any port of the BusAdapter for feeding or for looping through. The integrated media converter converts the signals automatically. BusAdapter 54 Manual, 03/2018, A5E41449003-AA BusAdapter BA LC/RJ45 10.2 Connecting 10.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Attaching LC connectors You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2xLC (Page 48). Connecting the RJ45 connector You can find more information about the required tools, accessories and procedures in the section Connecting BusAdapter BA 2xRJ45 (Page 15). Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA LC/RJ45. Table 10- 1 PROFINET IO pin assignment with BusAdapter BA LC/RJ45 View Signal name Description Receive Data Transmit Data 1 TD Transmit Data + 2 TD_N Transmit Data - 3 RD Receive Data + 4 TERM1 Termination Network 1 5 TERM1 Termination Network 1 6 RD_N Receive Data - 7 TERM2 Termination Network 2 8 TERM2 Termination Network 2 BusAdapter Manual, 03/2018, A5E41449003-AA 55 BusAdapter BA LC/RJ45 10.2 Connecting BA LC/RJ45 BusAdapter mounted Interface module BA LC/RJ45 BusAdapter PROFINET connecting cable Figure 10-2 BusAdapter BA LC/RJ45 installed (using an ET 200SP interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter 56 Manual, 03/2018, A5E41449003-AA BusAdapter BA LC/RJ45 10.3 Diagnostics 10.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA LC/RJ45: LK1 (green) LK2 (green) Figure 10-3 LED displays on the BusAdapter BA LC/RJ45 LEDs LK1/LK2 on the BusAdapter Table 10- 2 Status and error displays LED Meaning Remedy LK1/LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. - on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - flashes BusAdapter Manual, 03/2018, A5E41449003-AA 57 BusAdapter BA LC/RJ45 10.4 Technical specifications 10.4 Technical specifications Technical specifications of the BusAdapters BA LC/RJ45 Article number 6ES7193-6AG20-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) LC / RJ45 PROFINET IO * RJ 45 Yes; 1x * FC (FastConnect) No * Number of SCRJ ports 0 * Number of LC ports 1 Cable length - Cu conductors 100 m - Multimode graded-index fiber 50/125 m 3 km - Multimode graded-index fiber 62.5/125 m 3 km Ambient conditions Ambient temperature during operation * min. 0 C * max. 60 C Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 32 g BusAdapter 58 Manual, 03/2018, A5E41449003-AA BusAdapter BA LC/FC 11.1 11 Product overview Article number 6ES7193-6AG40-0AA0 View Glass fiber-optic cable LC FastConnect FC Figure 11-1 BusAdapter BA LC/FC Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA LC/FC: Optically with glass fiber-optic cables with an LC connector to port 1 Electrically with direct connection of the Fast Connect bus cable to port 2 Screw the BusAdapter BA LC/FC with the attached Fast Connect bus cable onto the PROFINET device and plug in the LC connector. You loop through the PROFINET IO via the integrated 2-port switch. You can use any port of the BusAdapter for feeding or for looping through. The integrated media converter converts the signals automatically. BusAdapter Manual, 03/2018, A5E41449003-AA 59 BusAdapter BA LC/FC 11.2 Connecting 11.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Attaching LC connectors You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2xLC (Page 48). Connecting FastConnect bus cable You can find more information about the required tools, accessories and procedures in the section Connecting BusAdapter BA 2xFC (Page 21). Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA LC/FC. Table 11- 1 PROFINET IO pin assignment with BusAdapter BA LC/FC View Signal name Description Receive Data Transmit Data 1 RD_N Receive Data - 2 TD_N Transmit Data - 3 RD Receive Data + 4 TD Transmit Data + BusAdapter 60 Manual, 03/2018, A5E41449003-AA BusAdapter BA LC/FC 11.2 Connecting BusAdapter BA LC/FC installed Interface module BA LC/FC BusAdapter PROFINET connecting cable Figure 11-2 Connecting the BusAdapter BA LC/FC to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks (Local Area Networks). A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN (Wide Area Network). BusAdapter Manual, 03/2018, A5E41449003-AA 61 BusAdapter BA LC/FC 11.3 Diagnostics 11.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA LC/FC: LK1 (green) LK2 (green) Figure 11-3 LEDs on the BusAdapter BA LC/FC LK1/LK2 LEDs on the BusAdapter Table 11- 2 Status and error displays LED Meaning Remedy LK1/LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. Check whether the bus cable to the switch or IO controller is disconnected. - on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner, e.g. IO controller. The "Node flash test" is running. The RN/ER/MT LEDs are also flashing. - flashes BusAdapter 62 Manual, 03/2018, A5E41449003-AA BusAdapter BA LC/FC 11.4 Technical specifications 11.4 Technical specifications Technical specifications of the BusAdapters BA LC/FC Article number 6ES7193-6AG40-0AA0 Interfaces Number of PROFINET interfaces 1 PROFINET IO * RJ 45 No * FC (FastConnect) Yes; 1x * Number of SCRJ ports 0 * Number of LC ports 1 Cable length - Cu conductors 100 m - Multimode graded-index fiber 50/125 m 3 km - Multimode graded-index fiber 62.5/125 m 3 km Ambient conditions Ambient temperature during operation * min. 0 C * max. 60 C Dimensions Width 20 mm Height 69.5 mm Depth 59 mm Weights Weight, approx. 50 g BusAdapter Manual, 03/2018, A5E41449003-AA 63 12 Strain relief 12.1 Product overview Article number 6ES7193-6RA00-1AN0 (VPE: 5 strain relief units incl. screws) View Figure 12-1 Strain relief Properties The strain relief is a mechanical protective device for the electrical PROFINET cables on the BusAdapter. The strain relief is suitable for all optical and electrical PROFINET cables of the BusAdapter. The strain relief is an optional accessories. The cable ties are not included in the delivery. We recommend cable ties with a width of 4.8 mm. The maximum width is 7.0 mm. The length of the cable tie is min. 60 mm. BusAdapter 64 Manual, 03/2018, A5E41449003-AA Strain relief 12.2 Installing 12.2 Installing Requirement The PROFINET cables are not inserted on the BusAdapter. The inserted PROFINET cables hamper the mounting of the strain relief. BusAdapter and strain relief can be mounted separately. Tools required Screwdriver TX10 (torx). Procedure To install the strain relief, follow these steps: 1. Press the strain relief below the BusAdapter seat of the PROFINET device. Figure 12-2 Strain relief before mounting 2. Fasten the strain relief (1 screw with 0.7 to 0.8 Nm tightening torque). 3. Plug the BusAdapter into the PROFINET device. BusAdapter Manual, 03/2018, A5E41449003-AA 65 Strain relief 12.2 Installing 4. Screw the BusAdapter to the PROFINET device (1 screw with 0.2 Nm tightening torque). 5. Attach the PROFINET cables with the cable ties to the strain relief. Figure 12-3 Strain relief installed BusAdapter 66 Manual, 03/2018, A5E41449003-AA Dimension drawings A.1 A BusAdapter dimension drawings The figure below shows the dimension drawing of the BusAdapter BA 2xRJ45 as an example. Figure A-1 A.2 Dimensional drawing of BusAdapter BA 2xRJ45 Strain relief dimension drawings The figure below shows the dimension drawing of the strain relief. Figure A-2 Strain relief dimension drawing BusAdapter Manual, 03/2018, A5E41449003-AA 67 B Accessories B.1 Accessories Additional accessories are available for the SIMATIC BusAdapters: Accessories Article number Property Figure Strain relief 6ES7193-6RA001AN0 The strain relief is a mechanical protective device for the electrical PROFINET cables on the BusAdapter. The strain relief can be ordered as optional accessories. You install the strain relief on the PROFINET device (e.g.: interface module) before you install the BusAdapter. You can find additional information in section Strain relief (Page 64). Reference identification label (10 mats with 16 labels each) 6ES7193-6LF300AW0 The labels enable the reference identification labeling of the BusAdapter. The labels can be ordered on a mat for thermal transfer and inkjet printers as optional accessories. You insert the reference identification label into the opening on the top of the BusAdapter. Cables and connectors You can find the recommended cables and connectors with the respective BusAdapters. Assembly tools Tool MLFB Description Industrial Ethernet FastConnect Stripping Tool 6GK1901-1GA00 Stripping tool for the fast stripping of IE FastConnect cables with green blade cassette FC FO Termination Kit 6GK1900-0RL00-0AA0 Stripping tool for FC FO cable with the IE FC FO LC plug (cleaving of the glass fiber). BusAdapter 68 Manual, 03/2018, A5E41449003-AA