3
74
Interface Modules
JUMPFLEX® Transducers
Isolation amplifiers, fixed setting for voltage or current signals
OUTIN
POWER
5
6
1
2
3
4
7
8
OUT+
GND 2
Us+
GND 3
IN+
GND 1
Us+
GND 3
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
Short description:
The configurable isolation amplifiers convert, amplify, filter and electrically
isolate analog standard signals. The devices have a 3-way isolation with a
2.5kV test voltage. The 857-411 Isolation Amplifier provides electrical isolation
between the 0(4) - 20mA input and the 0(4) - 20mA output analog current
signals. The 857-412 Isolation Amplifier provides electrical isolation between
the 0(2) - 10V input and the 0(2) - 10V output analog voltage signals.
The device is supplied with 24VDC, which can be quickly and cost-effectively
commoned via lateral, push-in type jumper bars.
A green LED on the front panel indicates normal operation. The isolation
amplifiers meet the requirements for safe isolation of input, output and supply
circuits with 2.5kV test voltage according to EN 61140.
Description Input signal Output signal Item No. Pack.
Unit
Isolation amplifier 0(4) ... 20 mA 0(4) ... 20 mA 857-411 1
Isolation amplifier 0(2) ... 10 V 0(2) ... 10 V 857-412 1
Isolation amplifier 0 ... 10 V 0 ... 20 mA 857-413 1
Isolation amplifier 0 ... 10 V 4 ... 20 mA 857-414 1
Isolation amplifier 0 ... 20 mA 0 ... 10 V 857-415 1
Isolation amplifier 4 ... 20 mA 0 ... 10 V 857-416 1
Accessories
General accessories see Full Line Catalog 2010/2011
Interface Modules
Approvals
Shipbuilding g
4 r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Conformity marking 1
General Specifications
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP®S
Cross sections solid: 0.08 mm² ... 2.5 mm² /
AWG 28 ... 14
fine-stranded: 0.34 mm² ... 2.5 mm² /
AWG 22 ... 14
Stripped lengths 9 ... 10 mm / 0.37 in
Dimensions (mm) W x H x L 6 x 96 x 94
Technical Data
Input signal 857-411: 0(4) ... 20 mA
857-412: 0(2) ... 10 V
857-413: 0 ... 10 V
857-414: 0 ... 10 V
857-415: 0 ... 20 mA
857-416: 4 ... 20 mA
Input resistance ≤ 50 Ω (I input)
≥ 100 kΩ (U input)
Output signal 857-411: 0(4) ... 20 mA
857-411: 0(2) ... 10 V
857-411: 0 ... 20 mA
857-411: 4 ... 20 mA
857-411: 0 ... 10 V
857-411: 0 ... 10 V
Load impedance 600 Ω (I output)
2 kΩ (U output)
Max. operating frequency 100 Hz
Response time (T10-90) < 3.5 ms
Voltage supply VN DC 24 V
Supply voltage range 16.8 V ... 31.2 V
Current consumption at 24 V DC < 25 mA
Transmission error < 0.1 % of the full scale value
Temperature coefficient 0.01 % /K
Test voltage (input/output/supply)
2.5 kV AC, 50 Hz, 1 min
Ambient operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
857-411, 857-412, 857-413, 857-414, 857-415, 857-416
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.04.2011
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com