Data sheet...
ConnectPower
CP-BBU 115-230VAC / 24VDC
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-2083
www.weidmueller.com
Technical data
Creation date January 20, 2012 3:41:50 PM CET
Catalogue status 24.11.2011 / We reserve the right to make technical changes. 2
Dimensions
Length 161 mm Width 72.5 mm
Height 127.5 mm Weight 950 g
Temperatures
Operating temperature -20 °C...+50 °C Storage temperature -20 °C...+85 °C
Input
Conductor connection system Screw connection Connection range AWG26-12 (0.1-4.0 mm²)
Input current 1 A @ 115 V AC; 0.6 A @
230 V AC
Input frequency
50/ 60 Hz
Input fuse
2 A time-lag fuse (internal)
Input voltage (voltage mode input) 85...265 V AC; 120...300 V
DC; typ.115–230 V AC ±10%
Surge protection Varistor Turn-on current limit Thermistor
output
Battery charging current 2 A Battery voltage 27.3 V
Conductor connection system Screw connection Connection range AWG26-12 (0.1-4.0 mm²)
Control at input voltage 0.2 % Mains failure bridge-over time for 115 V AC 24 ms
Mains failure bridge-over time for 230 V AC 190 ms Max. residual ripple < 50 mVeff
Output current Max. 15 A / max 9.0 A for
power supply unit
Output voltage
24 V DC
output power 360 W
General data
Degree of efficiency at max. load 72 % Depth 127.5 mm
EMC standards EN 55011, EN 55022, EN
55024, EN 61000-6-2, 3
Low Voltage Directive
73/ 23/ EWG
Operating temperature
-20 °C...+50 °C
Standards DIN EN 50178, DIN EN
60950, IEC950
Status indication Green LED (full charge):
battery voltage > 29.5 V DC,
Yellow LED (low battery):
battery voltage < 22 V DC,
Yellow LED (charging): BBU
is loading battery, Red LED
(error): no AC input voltage,
Red LED (reversed battery):
battery poles are reversed,
LED red (battery open): no
battery is connected
Switching frequency
100 kHz
Insulation coordination
Humidity at operating temperature 20 - 85% RH without
condensation
Humidity at storage temperature
20 to 90%
Protection degree IP 20 electrical isolation, I/O rail 3 kV
electrical isolation, input-earth 1.5 kV electrical isolation, input-output 3 kV