48 48 Series - Relay interface modules 8 A SERIES 48.12 2 Pole, forcibly guided contacts, relay interface modules,15.8 mm wide 48.12 - 2 Pole 8 A (screw terminal) * DC sensitive coils * Relay with forcibly guided contacts according to EN 50205 Type B * 35 mm rail (EN 60715) mounting B 48.12 Screw terminal * 2 pole, 8 A * Forcibly guided contacts relay * Screw terminal * 35 mm rail (EN 60715) mounting According to EN 50205 only 1 NO and 1 NC (11-14 and 21-22 or 11-12 and 21-24) shall be used as forcibly guided contacts. 48.12 For outline drawing see page 7 Contact specification Contact configuration 2 CO (DPDT) Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC 8/15 250/400 Rated load AC1 VA 2000 Rated load AC15 (230 V AC) VA 500 Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A 8/0.65/0.2 mW (V/mA) 500 (10/10) Minimum switching load Standard contact material 0.37 AgNi Coil specification Nominal voltage (UN) V AC (50/60 Hz) -- V DC 12 - 24 VA (50 Hz)/W --/0.7 Rated power AC/sens. DC Operating range AC sens. DC -- (0.75...1.2)UN Holding voltage AC/DC --/0.4 UN Must drop-out voltage AC/DC --/0.1 UN Mechanical life AC/DC cycles --/10 * 106 Electrical life at rated load AC1 cycles 100 * 103 Technical data IV-2015, www.findernet.com Operate/release time Insulation between coil and contacts (1.2/50 s) Dielectric strength between open contacts Ambient temperature range Protection category ms 10/4 kV 6 (8 mm) V AC C 1500 -40...+70 IP 20 Approvals relay (according to type) 1 48 SERIES 48 Series - Relay interface modules 8 - 10 - 16 A 48.31 1 & 2 Pole relay interface modules, 15.8 mm wide 48.52/72 Ideal interface for PLC and electronic systems 48.31 - 1 Pole 10 A (screw terminal) 48.52 - 2 Pole 8 A (screw terminal) 48.72 - 2 Pole 8 A (screwless terminal) clip * Supply status indication and EMC coil * 1 pole, 10 A * Screw terminal * 35 mm rail (EN 60715) mounting suppression module as standard * Identification label * UL Listing (certain relay/socket combinations) * 35 mm rail (EN 60715) mounting 48.31 / 48.52 Screw terminal * 2 pole, 8 A * Screw terminal and screwless terminal * 35 mm rail (EN 60715) mounting 48.72 Screwless terminal 48.52 / 72 For outline drawing see page 7 Contact specification Contact configuration Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC 1 CO (SPDT) 2 CO (DPDT) 10/20 8/15 250/400 250/250 Rated load AC1 VA 2500 2000 Rated load AC15 (230 V AC) VA 500 400 Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A Minimum switching load mW (V/mA) Standard contact material 0.37 0.3 10/0.3/0.12 8/0.3/0.12 300 (5/5) 300 (5/5) AgNi AgNi 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230 12 - 24 - 125 12 - 24 - 125 1.2/0.5 1.2/0.5 Coil specification Nominal voltage (UN) V AC (50/60 Hz) Rated power AC/sens. DC V DC VA (50 Hz)/W AC (0.8...1.1)UN (0.8...1.1)UN sens. DC (0.73...1.5)UN (0.73...1.5)UN Holding voltage AC/DC 0.8 UN / 0.4 UN 0.8 UN / 0.4 UN Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN Mechanical life cycles 10 * 106 10 * 106 Electrical life at rated load AC1 cycles 200 * 103 100 * 103 ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC) kV 6 (8 mm) 6 (8 mm) 1000 1000 -40...+70 -40...+70 IP 20 IP 20 Operating range Technical data Operate/release time Insulation between coil and contacts (1.2/50 s) Dielectric strength between open contacts Ambient temperature range Protection category Approvals relay (according to type) 2 V AC C IV-2015, www.findernet.com B * AC coils or DC sensitive coils * Instant ejection of relay using plastic retaining 48 48 Series - Relay interface modules 8 - 10 - 16 A 48.61/81 1 & 2 Pole relay interface modules, 15.8 mm wide SERIES 48.62/82 Ideal interface for PLC and electronic systems 48.61 - 1 Pole 16 A (screw terminal) 48.81 - 1 Pole 16 A (screwless terminal) 48.62 - 2 Pole 10 A (screw terminal) 48.82 - 2 Pole 10 A (screwless terminal) * AC coils or DC sensitive coils * Instant ejection of relay using plastic retaining B clip * Supply status indication and EMC coil * 1 pole, 16 A * Screw terminal and screwless terminal * 35 mm rail (EN 60715) mounting suppression module as standard * Identification label * UL Listing (certain relay/socket combinations) * 35 mm rail (EN 60715) mounting 48.61 / 48.62 Screw terminal * 2 pole, 10 A * Screw terminal and screwless terminal * 35 mm rail (EN 60715) mounting 48.81 / 48.82 Screwless terminal / 81 * For currents > 1048.61 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12). For outline drawing see page 7 48.62 / 82 Contact specification Contact configuration Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC 1 CO (SPDT) 2 CO (DPDT) 16*/30 10/20 250/400 250/400 Rated load AC1 VA 4000 2500 Rated load AC15 (230 V AC) VA 750 500 Single phase motor rating (230 V AC) kW 0.55 0.37 Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 10/0.3/0.12 mW (V/mA) 500 (10/5) 300 (5/5) AgCdO AgNi 12 - 24 - 110 - 120 - 230 -- 12 - 24 - 125 12 - 24 - 125 1.2/0.5 --/0.5 Minimum switching load Standard contact material Coil specification Nominal voltage (UN) V AC (50/60 Hz) Rated power AC/sens. DC Operating range V DC VA (50 Hz)/W AC (0.8...1.1)UN -- sens. DC (0.8...1.5)UN (0.8...1.5)UN Holding voltage AC/DC 0.8 UN / 0.4 UN --/0.4 UN Must drop-out voltage AC/DC 0.2 UN / 0.1 UN --/0.1 UN Mechanical life cycles 10 * 106 20 * 106 Electrical life at rated load AC1 cycles 100 * 103 100 * 103 ms 7/4 (AC) - 12/12 (DC) 12/12 (DC) kV 6 (8 mm) 6 (8 mm) 1000 1000 -40...+70 -40...+70 IP 20 IP 20 Technical data IV-2015, www.findernet.com Operate/release time Insulation between coil and contacts (1.2/50 s) Dielectric strength between open contacts Ambient temperature range Protection category V AC C Approvals relay (according to type) 3 48 SERIES 48 Series - Relay interface modules 8 - 10 - 16 A Ordering information Example: 48 series, 35 mm rail (EN 60715) mount, screw terminal relay interface module, 2 CO (DPDT) 8 A contacts, 24 V sensitive DC coil, green LED + diode, 99.02 coil indication. 4 8 . 5 B C D 2 . 7 . 0 2 4 . 0 0 5 0 Series A: Contact material 0 = Standard AgNi for 48.31/52/62/72/82 AgCdO, Standard for 48.61/81 1= AgNi, for 48.12 4 = AgSnO2, for 48.61/ 62/81/82 only 5 = AgNi + Au, for 48.31/52/72 only Type Screw terminal 1 = 35 mm rail (EN 60715) mount, forcibly guided contacts relay 3 = 35 mm rail (EN 60715) mount 5 = 35 mm rail (EN 60715) mount 6 = 35 mm rail (EN 60715) mount Screwless terminal 7 = 35 mm rail (EN 60715) mount 8 = 35 mm rail (EN 60715) mount D: Special versions 0 = Standard 2 = Standard (for 48.12 only) C: Options 0 = Standard (for 48.12 only) 5 = Standard for DC: green LED + diode (polarity +A1) 6 = Standard for AC: green LED + Varistor B: Contact circuit 0 = CO (nPDT) No. of poles 1 = 1 pole for 48.31, 10 A 48.61,48.81, 16 A 2 = 2 pole for 48.12, 48.52, 48.72, 8 A 48.62, 48.82, 10 A (48.62, 48.82 DC only) Coil version 7 = Sensitive DC 8 = AC (50/60 Hz) 9 = DC Selecting features and options: only combinations in the same row are possible. Preferred selections for best availability are shown in bold. Coil voltage See coil specifications Type Coil version A B C D 48.12 DC 1 0 0 2 0-5 0 6 0 48.31/52/72 Sensitive DC 0 - 5 0 5 0 48.31/52/72 AC 48.61/81 AC 0-4 0 6 0 48.61/81 Sensitive DC 0 - 4 0 5 0 48.62/82 Sensitive DC 0 - 4 0 5 0 Technical data Insulation Insulation according to EN 61810-1 48.12/31/61/62 48.52/72 insulation rated voltage rated impulse withstand voltage V 250 48.12/31/61/62/81/82 250 400 kV 4 4 4 pollution degree 3 2 2 overvoltage category III III III Insulation between coil and contacts (1.2/50 s) kV 6 (8 mm) Dielectric strength between open contacts V AC 1000; 1500 (48.12) Dielectric strength between adjacent contacts V AC 2000 (48.52); 2500 (48.12/62) Conducted disturbance immunity Burst (5...50)ns, 5 kHz, on A1 - A2 EN 61000-4-4 level 4 (4 kV) Surge (1.2/50 s) on A1 - A2 (differential mode) EN 61000-4-5 level 3 (2 kV) Other data Bounce time: NO/NC ms 2/5; 2/10 (48.12) Vibration resistance (10...200)Hz: NO/NC Power lost to the environment g 20/5 (for 1 pole) without contact current with rated current Wire strip length Screw torque Max. wire size 4 15/3; 20/6 (48.12) for 2 pole W 0.7 W 1.2 (48.12/31) 1.3 (48.52/72) 1.2 (48.61/62/81/82) mm 8 Nm 0.5 Screw terminal Screwless terminal solid cable stranded cable solid cable stranded cable mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x (0.2...1.5) 2 x (0.2...1.5) AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x (24...18) 2 x (24...18) IV-2015, www.findernet.com B A 48 48 Series - Relay interface modules 8 - 10 - 16 A SERIES Contact specification F 48 - Electrical life (AC) v contact current Types 48.31/61/81 F 48 - Electrical life (AC) v contact current Types 48.62/82 Cycles Cycles Resistive load - cos = 1 Inductive load- cos = 0.4 B Resistive load - cos = 1 Inductive load- cos = 0.4 limit for 48.31 Resistive load - cos = 1 Inductive load- cos = 0.4 Cycles Resistive load - cos = 1 Inductive load- cos = 0.4 H 48 - Maximum DC1 breaking capacity Types 48.31/52/61/72/81 DC breaking current (A) F 48 - Electrical life (AC) v contact current Type 48.12 H 48 - Maximum DC1 breaking capacity Types 48.62/82 48.61/81 current limit 48.31 current limit 48.52/72 current limit DC breaking current (A) Cycles F 48 - Electrical life (AC) v contact current Types 48.52/72 2 contacts in series single contact DC voltage (V) 2 contacts in series single contact DC voltage (V) DC breaking current (A) IV-2015, www.findernet.com H 48 - Maximum DC1 breaking capacity Type 48.12 * When switching a resistive load (DC1) having voltage and current * DC voltage (V) values under the curve, an electrical life of 100 * 103 can be expected. In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load. Note: the release time for the load will be increased. 5 48 SERIES 48 Series - Relay interface modules 8 - 10 - 16 A Coil specifications DC coil data (0.5 W sensitive) Nominal voltage Coil code UN V B 12 AC coil data Operating range 7.012 Umin* Umax V V 8.8 24 7.024 17.5 125 7.125 91 Rated coil consumption I at UN Nominal voltage UN mA V 12 Coil code Operating range Umin V 8.012 Umax V mA 18 41 36 22.2 24 8.024 19.2 188 4 125 8.110 88 121 10.1 120 8.120 96 132 11.8 230 8.230 184 253 7.0 * Umin = 0.8 UN for 48.61, 48.62, 48.81 and 48.82 9.6 Rated coil consumption I at UN (50 Hz) 13.2 90.5 26.4 46 DC coil data, 2 pole relay - Type 48.12 Nominal voltage UN Coil code Operating range Umin V Umax V Resistance R Rated coil consumption I at UN V mA 12 9.012 9 14.4 205 58.5 24 9.024 18 28.8 820 29.3 R 48 - DC coil operating range v ambient temperature 48.31/52/72 48.61/62/81/82 R 48 - AC coil operating range v ambient temperature 1 1 48.61/62/81/82 48.31/52/72 2 1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature. 2 1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature. R 48 - DC coil operating range v ambient temperature Type 48.12 IV-2015, www.findernet.com 1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature. 6 48 SERIES 48 Series - Relay interface modules 8 - 10 - 16 A Combinations Code Type of socket Type of relay Module Retaining clip 48.12 95.05.0 50.12 -- 095.71 48.31 48.52 95.03 40.31 99.02 095.01 95.05 40.52 99.02 095.01 48.61 95.05 40.61 99.02 095.01 48.62 95.05 44.62 99.02 095.01 48.72 95.55 40.52 99.02 095.91.3 48.81 95.55 40.61 99.02 095.91.3 48.82 95.55 44.62 99.02 095.91.3 Outline drawing B 73.7 24.6 4 4 21 COM 11 24 NO 14 22 NC 12 34.7 30.3 95.6 30.6 A2 COIL A1 15.8 48.31 48.52 / 48.61 / 48.62 Screw terminal 22.6 32.5 48.72 / 48.81 / 48.82 Screw terminals 64.5 25.9 17.5 17.5 35.4 25.5 78.6 21.6 15.8 32 IV-2015, www.findernet.com 48.12 Screw terminal 7 48 SERIES 48 Series - Relay interface modules 8 - 10 - 16 A P A N T E PEAN 095.18 PEAN O O T EUR EUR Accessories B 8-way jumper link for screw terminal version 095.18 (blue) Rated values 10 A - 250 V Sheet of marker tags, plastic, 72 tags, 6 x 12 mm 060.72 095.18.0 (black) 060.72 Packaging codes How to code and identify retaining clip and packaging options for sockets. Example: 4 8 . 5 2 . 7 . 0 2 4 . 0 0 5 0 S P A A Standard packaging B Blister packaging IV-2015, www.findernet.com SP Plastic retaining clip 8