Motor reversing
Number of phases
Switching mode
Rated operational voltage
Control input type
Motor power rating
Specifications are subject to change without notice (05.06.2010) 1
Control voltage
D: 10 - 40 VDC
LA: 90 - 140 VAC
HA: 180 - 265 VAC
Rated operational
voltage, Ue
40: 400 VACrms
48: 480 VACrms
This family of 2-Phase Motor
Reversing Controller is de-
signed to control the directon
of 3-phase motors rated up to
5.5 kW. The built-in interlock-
ing circuitry prevents the relay
from switching both direc-
tions simultaneously and pro-
duce a short-circuit between
the 2 phases of the output. A
dual colour LED indicates di-
rection "forward" when green
and direction "reverse" when
red. The output is protected
from excessive voltage fluctu-
ations (transients) by built-in
varistors. Furthermore, opti-
mum reliability is achieved by
soldering the output thyristor
chips directly on to the
ceramic substrate (Direct
Copper Bonding).
The housing is designed to
incorporate a temperature
limit switch. It is recommend-
ed to install an appropriate
semiconductor fuse in series
with the relay.
Motor Controllers
Industrial, 2-Phase Motor Reversing
Type RR2A
Ordering Key
Product Description
Motor reversing
for 3-phase induction motors up to 5.5 kW
Rated operational voltage: Up to 480 VACrms
Built-in interlock function
DC or AC control voltage
Built-in voltage transient protection
LED indication for direction
Isolation: Optocoupler (input-output)
4000 VACrms
Direct copper bonding technology
10 to 40 VDC RR2A40D150 RR2A40D400
90 to 140 VAC RR2A40LA150 RR2A40LA400
180 to 265 VAC RR2A40HA150 RR2A40HA400
10 to 40 VDC RR2A48D220 RR2A48D550
90 to 140 VAC RR2A48LA220 RR2A48LA550
180 to 265 VAC RR2A48HA220 RR2A48HA550
Motor rating
150: 1.5 kW, 2 HP
220: 2.2 kW, 3 HP
400: 4.0 kW, 5 HP
550: 5.5 kW, 7.5 HP
Type Selection
Switching mode
A: Zero Switching
Selection Guide
Control
voltage
400 VACrms
Rated opera-
tional voltage
Motor rating
1.5 kW 2.2 kW 4.0 kW 5.5 kW
480 VACrms
RR 2 A 40 D 150
General Specifications
RR2 A 40. .... RR2 A 48 . 220 RR2 A 48 . 550
Operational voltage range 40 to 440 VACrms 40 to 530 VACrms 40 to 530 VACrms
Blocking voltage 1200 Vp1200 Vp1600 Vp
Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Power factor 0.5 @ 400 VACrms 0.5 @ 480 VACrms 0.5 @ 480 VACrms
LED on indication Yes (Green for Forward, Red for Reverse)
2Specifications are subject to change without notice (05.06.2010)
RR2A
Input Specifications
RR2A40.150 RR2A48.220 RR2A40.400 RR2A48.550
IEC and CCC
rated operational current Ie
(AC-53a) @ Ta = 40°C 5 A 5 A 11 A 11 A
IEC rated operational current
Ie (AC-51) @ Ta = 40°C 25 A** 25 A** 40 A** 40 A**
Assigned motor rating @ 40°C/
UL rating @ 40°C 1.5kW / 2HP 2.2kW / 3HP 4.0kW / 5HP 5.5kW / 7.5HP
Overload cycle according to
EN/IEC 60947-4-2 @ 4C 5A: AC53a: 6-6: 100-60 5A: AC53a: 6-6: 100-60 11A: AC53a: 8-3: 100-40** 11A: AC53a: 8-3: 100-40**
Number of starts/hr @ 40°C 60 60 40 40
Unlimited starts/hr @40˚C
4A: AC53a: 6-6: 100 4A: AC53a: 6-6: 100 5A: AC53a: 6-3: 100 5A: AC53a: 6-3: 100
- unlimited** - unlimited** - unlimited** - unlimited**
3.5A: AC53a: 5-6: 100 3.5A: AC53a: 5-6: 100 4A: AC53a: 5-3: 100 4A: AC53a: 5-3: 100
- unlimited* - unlimited* - unlimited* - unlimited*
1.5A: AC53a: 4-6: 100 1.5A: AC53a: 4-6: 100 2A: AC53a: 5-3: 100 2A: AC53a: 5-3: 100
- unlimited - unlimited - unlimited - unlimited
Minimum operational current
Ta = 25˚C V out = 40Vrms 150 mArms 150 mArms 250 mArms 250 mArms
Off-state leakage current 1 mArms 1 mArms 1 mArms 1 mArms
Non-rep. surge current t=10ms 300Ap350Ap350Ap350Ap
I2t for fusing t= 10ms 525 A2s 525 A2s 1800 A2s 1800 A2s
On-state voltage drop 1.6 Vrms 1.6 Vrms 1.6 Vrms 1.6 Vrms
Critical dv/dt off-state 500 V/us 500 V/us 1000 V/us 1000 V/us
* This overload cycle is applicable when device is mounted on heatsink type RHS300
** Applicable only when device is mounted on heatsink type RHS301
Output Specifications
RR2A..D... RR2A..LA... RR2A..HA...
Control voltage range 10 - 40 VDC 90 - 140 VAC 180 - 265 VAC
Pick-up voltage 8.5 VDC 70 VAC 170 VAC
Input current range 10 - 20 mADC 7 - 12.5 mAAC 6 - 9.5 mAAC
Drop-out voltage 3.5 VDC 20 VAC 50 VAC
Response time input to output 10 ms 70 ms 100 ms
Time delay
FR, R F Typical 80 ms 200 ms* 200 ms*
Minimum 50 ms 30 ms 30 ms
Maximum 90 ms 300 ms 300 ms
*300 ms for surrounding temperatures + 60˚C (140 ˚F)
Environmental Specifications
Operating temperature -2C to +80°C
(-4°F to +17F)
Storage temperature -40°C to +10C
(-40°F to +212°F)
Relative humidity <95% non-condensing @40°C
Pollution Degree 3
Degree of Protection IP10 (EN/IEC 60529)
Installation category III
Installation Altitude 1000m
Vibration
Sinusodial (IEC 60068-2-6) 13 to 25Hz: 2.0mm peak
25 to 150Hz: 20m/s2
Specifications are subject to change without notice (05.06.2010) 3
RR2A
Standards
Approvals UL, cUL (E172877), CCC
Markings CE, EN 60947-4-2, GB 14048.6
EMC (Electromagentic
compatability) accord. to EN 61000-6-2
Wire conducted emission Class A
Radiated emission Class B
ESD Immunity (EN 61000-4-2) 4kV contact, PC1
8kV air discharge, PC2
Radiated RF immunity
(EN 61000-4-3) 10V/m, PC1 (80-1000MHz)
Fast transient immunity
(EN 61000-4-4) Output 2kV, PC1
Input 2kV, PC1
Surge immunity (EN 61000-4-5)
Output: line to line 1kV, PC1
line to ground 2kV, PC1
Input: line to line 500V, PC1** (RR2AxxDxxx)
line to ground 500V, PC1** (RR2AxxDxxx)
line to line 1kV, PC1 (RR2AxxxAxxx)
line to ground 2kV, PC1 (RR2AxxxAxxx)
Conducted RF immunity
(EN 61000-4-6) 140dBuV, PC1*
(0.15-80MHz)
Voltage Dips & Interruptions EN 61000-4-11
* It is suggested that the input lines be installed together (such as a 3 core cable)
to enhance susceptibility.
** Surge immunity level with an external transient voltage suppressor (47V) meets
PC2 @ 1 kV between line to line and 2kV between line to ground.
Note: EMC tests were performed with representative motor loads of 1.1kW and
4.0kW. The above is just an indication of the EMC performance. The performance
of the controller would have to be evaluated with the device connected and fitted as
part of the complete system in the end application.
Short Circuit Protection (according to EN/IEC 60947-4-2 and UL 508)
RR2A40.150 RR2A40.400
RR2A48.220 RR2A48.550
Type of coordination: 1*
UL rated short circuit current 5kA when protected by RK5 fuses 10kA when protected by RK5 fuses
RK5 fuse TRS10R 10A TRS20R 20A
Type of coordination: 2**
Rated short circuit current 10kA when protected by 10kA when protected by
semiconductor fuses semiconductor fuses
Semiconductor fuse Ferraz Shawmut Ferraz Shawmut
25A, Class URC 50A, Class URC
Art. No. 6.9 CP gRC 14.51 25 Art. No. 6.9 CP gRC 14.51 50
* Applicable only for UL
** Applicable for IEC/ CCC
Isolation
Dielectric withstand voltage
Input to output 4000 VACrms
Input to case 4000 VACrms
Dielectric withstand voltage
Output to case 4000 VACrms
Applications
Reversing an Asynchronous single phase motor working
with a phase-shifting capacitor
1/L1
3/L2
5/L3
2/T1 4/T2
N
L
M
6/T3
C
Housing Specifications
Weight Approx. 430 g
Housing material Noryl, glass-reinforced
Colour Black
Base plate Aluminium, nickel-plated
Potting compound Polyurethane, black
Relay
Mounting screws M5
Mounting torque 1.5 Nm
Control terminal
Mounting screws M4
Mounting torque 0.5 Nm
Wire size Max. 2 x 2.5 mm2(AWG 14)
Min. 2 x 1.0 mm2
Power terminal
Mounting screws M5
Mounting torque 2.5 Nm
Wire size Max. 2 x 6 mm2(AWG 8)
Min. 2 x 1 mm2
4Specifications are subject to change without notice (05.06.2010)
Functional Diagram
Control
inputs
Mains
inputs
Load
outputs
(+)
(-)
(+)
ZC
Regulation
Regulation
(~)
/~
/~
(~)
(~)
Accessories
Heatsinks For further information refer
Fuses to “General Accessories”.
Temperature limit switch
Wiring Diagram
F3
F1
F2
Pilot
voltage
RF
1/L1
3/L2
5/L3
2/T1 4/T2
6/T3
(~)
(~)
Dimensions
73.5
47.6
4 x M4 6x M5
LED
12
5.3
41
103
92
Use heatsink
compound
Temperature limit switch
All dimensions in mm
RR2A