Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (28.09.2005) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description Ordering Key
Type: Dupline®
H4-housing
Receiver
Number of channels
Output type
Power supply
Output Module
Type G 3430 4445
• 4-channel receiver
• Relay load: 16 A
• Module load: 64 A (16 A per relay)
• Galvanically separated SPST relay outputs
• H4-housing
• For mounting on DIN-rail (EN 50022)
• LED-indications for supply, Dupline®carrier and outputs
• AC power supply
• Address coding by GAP 1605
Dupline receiver®designed to
be a part of the Dupline®
concept for Building Auto-
Type Selection
Supply Ordering no.
24 VAC G3430 4445 024
115 VAC G3430 4445 115
230 VAC G3430 4445 230
mation. SPST relay outputs
for control of 4 loads of up to
250 VAC/16 A.
Output Specifications
Outputs 4 SPST relays
Contact ratings (AgSn02) µ (micro gap)
Resistive loads AC1 16 A
Mechanical lifetime 5x106operations
Electrical lifetime
1x105operations/250 V, 12 A
Minimum load 100 mA/12 V
Operating frequency 60 operations/min.
Dielectric voltage
Outputs – Dupline®4 kVAC (rms)
Response time 1 pulse train
G 3430 4445 024
Supply Specifications
Power Supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through term. 21 & 22
230 VAC, +/- 10% (IEC 60038)
115 VAC, +/- 10% (IEC 60038)
24 VAC, +/- 10%
Frequency 45 to 65 Hz
Rated operational power Typ. 2,5 VA
Max. power dissipation 7 W
General Specifications
Fail polarity state delay
Upon loss of Dupline®carrier 20 ms
Power ON delay typ. 2s
Indication for:
Supply ON LED, Green
Dupline®carrier LED, Yellow
Output ON
LED, red (one per output)
Environment
Degree of protection IP 20
Pollution degree 3 (IEC 60664)
Operating temperature
-5 to +50°C (+23° to +122°F)
Storage temperature
-50 to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 5 G (11ms)
Vibration 2 G (6 to 55Hz)
Housing H4-housing
Weight 400 g
Supply Specifications (cont.)
Power supply (cont.)
Rated impulse withstand volt.
230 4 kV
115 2,5 kV
024 800 V
Dielectric voltage
Supply – Dupline®4 kVAC (rms)
Supply – Outputs 2 kVAC (rms)
21 22 23 24 25 26 27 28
1 2 3 4 5 6 7 8
34
1
Supply
D+
N
N
LN
2
L1/L2/L3
L1/L2/L3
D-
L1/L2/L3
L1/L2/L3
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (28.09.2005)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Wiring Diagram
Accessories
DIN-rail FMD 411
For further information, see "Accessories".
4 channels G 3430 4445 ...
SPST relay output
G 3430 4445 ...
Operation Diagram
Dupline®carrier
Transmission on channel for output 1
Output 1 (term. 24 & 25)
Transmission on channel for output 2
Power supply
Output 2 (term. 27 & 28)
Default setting (fail polarity): OFF
Mode of Operation
4-channel receiver with 4
normally open contact out-
puts. Each output is individu-
ally coded by means of the
code programmer GAP 1605.
For changing the default set-
ting, please refer to the
datasheet on GAP 1605.
The outputs are normally OFF.
When a transmitter coded
to
the selected channel is acti-
vated, the output turns ON
and remains ON until the
respective channel becomes
deactivated. The default set-
ting is such that upon loss of
Dupline®carrier all the out-
puts go OFF.
Note: At delivery some of the
relays might be ON due to
transportation bumps. To be
sure that the relays are OFF,
connect the module to power
and Dupline and transmit on
channels A1-4 once.
Note: Due to the construc-
tion with bistable relays, the
module is intended for heat-
ing and light control only.
Dimensions (mm)
H4-housing
Output Specifications, Relay Data
Load Test conditions Typical number
of operations
250 V, 12 A, cos ϕ =1 1800/h, 50% DC, +70°C 1.0 x 105
250 V, 8 A, cos ϕ =1 1800/h, 50% DC, +70°C 3.5 x 105
250 V, 4 A, cos ϕ =1 1800/h, 50% DC, +70°C 5.0 x 105
250 V, 3 A, cos ϕ =1 1800/h, 50% DC, +70°C 7.5 x 105
230 V, 550 W
filament lamps
Iin 40 Apeak
Ioff = 2.5 A 60/h, 8% DC, +22°C 2.0 x 105
230 V, 1000 W
filament lamps
Iin 71.5 Apeak
Ioff = 4.5 A 60/h, 8% DC, +25°C 7.0 x 104
230 V, 900 W
fluorescent tubes
(25 x 36 W)
parallel compensated,
30 µF 360/h, 50% DC, +25°C 1.0 x 104
230 V, compressor
Iin 21 Apeak
Ioff =3.5 A
cos ϕ = 0.5 500/h, 20% DC, +25°C 1.7 x 105
250 V, 8 A, cos ϕ = 0.3 360/h, 50% DC, +25°C 1.0 x 105