SST Series Soft-start modules 120/240 V AC models 3.5-10 V DC control range Used with Series 1 random-fire solid-state relays PRODUCT SELECTION Description 10 A 120 Vrms Line Voltage 240 Vrms Line Voltage 10SST120 10SST240 OUTPUT SPECIFICATIONS (voltage) (1) 120 VAC 25 A 50 A 75 A 90A 25SST120 25SST240 40SST120 50SST240 75SST240 90SST240 240 VAC ol e Description te * * * * Operating Voltage (47-63Hz) [Vrms] Transient Overvoltage [Vpk] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/sec] (2) 90-140 400 10 500 180-280 600 10 500 OUTPUT SPECIFICATIONS (current) (1) Description 10 A 25 A 50 A 75 A 90 A 10 0.04 120 1.6 1.48 60 0.5 25 0.04 250 1.6 1.02 260 0.5 50 0.04 625 1.6 0.63 1620 0.5 75 0.04 1000 1.6 0.31 4150 0.5 90 0.04 1200 1.6 0.28 6000 0.5 bs Maximum Load Current (3) [Arms] Minimum Load Current (3) [Arms] Maximum Surge Current (16.6ms) [Apk] Maximum On-State Voltage Drop @ Rated Current [Vpk] Thermal Resistance Junction to Case (Rjc) [C/W] Maximum It for Fusing (8.3 msec) [Asec] Minimum Power Factor (with Maximum Load) CONTROL MODULE INPUT SPECIFICATIONS (1) Description Control Voltage Range Maximum Off-State Voltage Typical Input Current Nominal Turn-On Delay time @ 60Hz Nominal Swell (Ramp) Time @ 60Hz Maximum Reset Time Maximum Turn-Off Time [msec] DC Control 3.5-10 VDC 1.0 VDC 1.6 mA @ 5 VDC 150 msec 180 msec 0.1 msec 1/2 Cycle O CONTROL MODULE OUTPUT SPECIFICATIONS (1) Description Maximum Off-State Operating Voltage Maximum Load Current Maximum Turn-On Voltage@ 3mA Maximum Off-State Leakage@ 10 VDC DC Control 36 VDC 3 mADC 0.5 VDC 1.0 ADC GENERAL SPECIFICATIONS Description Parameters Dielectric Strength, signal to load Dielectric Strength, signal to Base Ambient Operating Temperature Range Ambient Storage Temperature Range Weight (typical) Encapsulation 4000 Vrms 4000 Vrms -30 to 80 C -40 to 125 C 3.0 oz. (43g) Thermally Conductive Epoxy GENERAL NOTES te 1) All parameters at 25C unless otherwise specified. 2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 3) Heat sinking required (Relay Only). bs ol e WIRING DIAGRAM NOTES O 1. Following pins may be interchanged: 1A & 1B, 2A & 2B, 3A & 3B. 2. Pin 4A & 4B may not be interchanged 3. The line and load may be interchanged. AGENCY APPROVALS O bs UL E116949 ol e te THERMAL DERATE INFORMATION Rev. 122010 O te ol e bs O bs ol e te ANNEX - ENVIROMENTAL INFORMATION