Product Description Ordering Key
Type: Dupline®
H4-housing
Transmitter
No. of channels
Input type
Power supply
Transmitter for Digital Signals
Type G 3420 5502
•8-channel transmitter
•8 opto-isolated voltage inputs:
6 to 265 VAC/DC
•H4-housing
•For mounting on DIN-rail (EN 50022)
•LED-indications for supply, input activated and
Dupline®carrier
•AC or DC power supply
•Channel coding by GAP 1605
Supply Ordering no.
8 channels
6 to 265 VAC/DC
24 VAC G 3420 5502 024
115 VAC G 3420 5502 115
230 VAC G 3420 5502 230
10 to 30 VDC G 3420 5502 800
Dupline®transmitter for exter-
nal supply. Detects the sig-
nals from 8 devices with volt-
age outputs of up to 265
VAC/DC, e.g. the presence of
mains supply to machinery.
Type Selection Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230 230 VAC, ±15%
115 115 VAC, ±15%
024 24 VAC, ±15%
Frequency 45 to 65 Hz
Voltage interruption ≤40 ms
Rated operational power Typ. 4.5 VA
Power dissipation ≤8 W
Rated impulse withstand
voltage 230 4 kV
115 2.5 kV
024 800 V
Dielectric voltage
Supply - Dupline®≥4 kVAC (rms)
Supply - Inputs ≥4 kVAC (rms)
Power supply DC type
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 800
10 to 30 VDC (ripple included)
Ripple ≤3 V
Reverse-polarity protection Yes
Power consumption < 1 W
Power dissipation ≤5.5 W
Inrush current ≤1 A
Rated impulse withstand
voltage 800 V
Dielectric voltage
Supply - Dupline®≥200 VAC (rms)
Supply - Inputs ≥4 kVAC (rms)
Input Specifications
Inputs
8 voltage-type
Input voltage range VBB 6 to 265 VAC/DC
Frequency range on AC 45 to 400 Hz
Input voltage for signal "0" ≤1 VAC/DC
Input voltage for signal "1" ≥6 VAC/DC
Input current for signal "1" Typ. 10 mA (VBB 10-18 VDC)
lower at other input voltages
Input current limiter Yes
Inrush current ≤450 mA
(at VBB = 265 VDC)
Operating time for signal "1" ≤1 pulse train + 3 ms
Operating time for signal "0" ≤1 pulse train + 50 ms
Cable length ≤25 m
Dielectric voltage
Inputs - Dupline®≥4 kVAC (rms)
G 3420 5502 024