Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 9
Power Protection and Conditioning
1
9
Surge Protection and Active Tracking® Filtering
Introduction .........................................................................10
STV 200/400K Single and Three Phase Series ....................11
STV 100K Single and Three Phase Series ............................14
STV 25K DIN Rail Mount Series ...........................................16
STF Series Active Tracking® Filters .......................................18
STFV Plus Series Active Tracking® Filters with
Surge Protection ..................................................................21
STFE Elite Series Active Tracking® Filters with
Surge Protection ..................................................................24
STC Series of Data/Signal Line Surge Protection .................27
Power Conditioning
CVS Hardwired (± 1% Output Regulation) ...........................34
Design Styles ....................................................................... 35
MCR Hardwired (± 3% Output Regulation) ...........................36
Connection Diagrams .......................................................... 38
MCR Portable (± 3 Output Regulation) .................................40
Model Comparison/BTU Output Chart .................................42
Operating Characteristics ................................................... 43
SOLATRON™ Plus Three Phase Power Conditioners ......... 46
Frequently Asked Questions .............................................. 237
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
10
1Power Protection and Conditioning
Today's industries depend on their telecommunication,
networking, computing and production equipment for
optimized manufacturing performance. SolaHD's proven
surge protection and ltering devices protect these critical
operations across facilities from the continuous threat of
transient spikes, noise and harmonic distortion.
Employing an entire facility protection strategy will safeguard
the electrical system against most transients. Multi-stage
protection involves clamping the initial high energy surge,
ltering any remaining noise or transients to the protected
sensitive equipment and nally, protecting the data/signal
lines entering or leaving the control panel or the factory oor.
This coordination of devices provides the lowest possible
let through voltage to the equipment to ensure maximum
productivity.
Surge Protective Devices
High-energy transients either externally or internally
generated pose an immediate threat to the reliability and
performance of your sensitive electronic equipment.
Emerson Network Power Surge Protection recommends
placing high-energy Surge Protective Devices (SPDs) on
key panels throughout your facility. Within your facility,
motors, inductive loads and various equipment load
switching can cause damage or costly downtime.
Our surge protective devices focus on limiting high-voltage
spikes to a level that is acceptable to most electronic
equipment. Plus, they’re a great rst line of defense, us-
ing components that are placed in parallel with the line and
serve as clamping mechanisms for high-energy impulses.
Protection at this level is referred to in the industry as Sine
Wave Tracking or electronic grade. Surge Protective devices
are typically installed at service entrances, on larger distribu-
tion panels and at the point of use.
Active Tracking® Filtering with Surge Protection
Low-energy transients and high-frequency noise are the
primary causes for system disruption and long-term
degradation of microprocessor-based equipment within
your facility. For more than 30 years, our Active Tracking
Filters have proven to be the most effective solution in critical
equipment protection within harsh industrial environments.
Active Tracking Filters are built upon a unique multi-stage
hybrid design. This design creates a foundation for a family
of products that attenuate impulses that would normally go
untouched by standard, parallel clamping devices.
Surge Protective Devices and Active Tracking® Filtering
Changing technology and dependence on total automa-
tion processes within modern facilities create a critical need
for clean AC power at the equipment level. Active Tracking
Filters are a perfect solution for your microprocessor-based
products, including industrial PLCs, OEM applications and
motion control systems.
Data/Signal Line Surge Protection
The rapid development of automated controls, telecommu-
nications and re/alarm/security systems make it imperative
to have properly coordinated low-voltage surge protection.
Modern networked industrial facilities require error-free trans-
mission of information for maximum productivity and
integrity of data, but these areas are often overlooked when
it comes to power protection.
The need to protect all susceptible low-voltage cable routes
entering a facility and at key points within the building is
as critical as protecting the equipment from high-energy
impulses. The importance of protecting at this level grows
as your facility’s reliance on sensitive instrumentation,
networked automation, and uncorrupted data transmission
increases. Our Data/Signal Line products utilize high-speed,
high-energy components that come in a variety of voltage
levels and unique packaging congurations.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 11
1
Power Protection and Conditioning
STV 200/400K Series - Surge Protective Devices
SolaHD STV 200/400K Series offers continuous protection
from damaging voltage transients and electrical noise
commonly found at the service entrance or distribution
panel. The modular design of the STV 200/400K allows
for installation exibility and its’ robust design allows for
installation in the most severe exposure locations. They are
capable of handling the high-impulse, potentially damaging
transients commonly found at the service entrance or
distribution panels. The modular design of the STV
200/400K allows for installation exibility. Its robust design
allows for placement in the most severe exposure locations.
The STV 200/400K utilizes patented circuitry to monitor
the status of all protection modes, including neutral to
ground. Should protection be unavailable in any mode, the
Green LED will be extinguished, and the Red LED will be
illuminated. In addition, high isolation form C dry contacts
provide remote monitoring of suppression system failure,
under voltage, phase and power loss. The STV 200/400K
patented suppression integrity monitoring indicates failure
for both shorted or opened suppression components.
These devices are designed to meet UL 1449 (third
edition), UL 1283 and cUL Listed. These units are ANSI/IEEE
C62.11, C62.41, C62.45 Categories A, B, and C3 tested.
They are built to meet your unique requirements, and are
available in hardwire, three phase conguration. They are
designed for years of trouble free operation and require little
or no operator intervention after installation.
Features
Modular design allows for exibility
Surge current capacity of 200 to 400 kA per phase
Industry’s highest surge current repeatability
All modes transient protection (L-N, L-G, and N-G)
Form C contact and audible alarm status indications
Internal/external monitoring, including neutral to ground
UL rated 200 kAIC with component level fusing
for safe operation
EMI/RFI Filtering
UL 1449 (third edition), UL 1283, and cUL Listed
ANSI/IEEE C62.11, C62.41, C62.45
Categories A, B, and C3 tested
Tested to NEMA LS1, ISO 9001
NEMA 12 enclosure, available options
NEMA 3R, 4, and 4X
Optional rotary disconnect, transient counter,
and remote monitor panel
5 Year Limited Warranty
Applications
The STV 200/400K Series can be a facility-wide product
family and may be installed from service entrances to distri-
bution panels to branch panels.
Industrial Plants
Commercial Buildings
Institutional Facilities
Any facility that has an environment with
electronics based equipment
Related Products
Power Conditioners
Uninterruptible Power System
Transformers
STV 25K, STV 100K, STF, STFV and STC Series
Selection Table
Catalog
Number Input Voltage
STV 400K-10Y 120/208 V Three Phase Wye 4 wire + Ground
STV 200K-10Y 120/208V Three Phase Wye 4 wire + Ground
STV 400K-27Y 277/480 V Three Phase Wye 4 wire + Ground
STV 200K-27Y 277/480 V Three Phase Wye 4 wire + Ground
STV 400K-48D 480 V Three Phase 3 wire + Ground
STV 200K-48D 480 V Three Phase 3wire + Ground
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
12
1Power Protection and Conditioning
STV 200/400K Specifications
Description Catalog Number
STV 200K-10Y STV 200K-27Y STV 200K-48D STV 400K-10Y STV 400K-27Y STV 400K-48D
Input Vac
120Y/208 V 277Y/480 V 480 V 120Y/208 V 277Y/480 V 480 V
Three Phase Wye,
4 W + G
Three Phase Wye,
4 W + G
Three Phase Delta,
3 W + G
Three Phase Wye,
4 W + G
Three Phase Wye,
4 W + G
Three Phase Delta,
3 W + G
Maximum Continous
Operating Voltage (MCOV) 120 V = 125%, All others voltages 115%
Line Frequency 47–63 Hz
Connection/
Mounting Type Internally connected/Wall Mounted (Mounting hardware 1/4 in.)
Enclosure NEMA 12 (NEMA 3R, 4, 4x optional)
Modes of Protection All Modes: L-N, L-L, L-G, N-G
Saftey Agency Approvals UL 1449 3rd Edition, UL 1283, cUL
UL 1449 (2nd Edition) Suppressor Classification
L-N 400 V 700 V N/A 400 V 700 V N/A
L-L 700 V 1,500 V 1,500 V 700 V 1,500 V 1,500 V
L-G 400 V 700 V 1,500 V 400 V 700 V 1,500 V
N-G 400 V 700 V N/A 400 V 700 V N/A
AIG Rating 200 kAIC
Status Indication LED’s status indicator, Audible alarm, and Form ‘C’ contact only relay
Response Time < 0.5 nsec.
Operating Temperature -40°C to +50°C
Operating Humidity 0% to 95% Non-condensing
Noise Attenuation 50 dB Maximum
Circuit Ampacity Limitations
Per Phase 200 kA 200 kA 200 kA 400 kA 400 kA 400 kA
Line to Neutral 100 kA 100 kA N/A 200 kA 200 kA N/A
Line to Line 100 kA 100 kA 100 kA 200 kA 200 kA 200 kA
Line to Ground 100 kA 100 kA 100 kA 200 kA 200 kA 200 kA
Neutral to Ground 100 kA 100 kA N/A 200 kA 200 kA N/A
Warranty 5 year limited warranty
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 13
1
Power Protection and Conditioning
Dimensional Drawings
C
1.30 Max
E
B
AD
F
Phase L1/A
Phase L2/B
Phase L3/C
Service Panel for
Loads to be Protected
Disconnect/Main
Neutral Bus
Ground Bus
Panel
Breaker for
Recommended Wire
Entrance
Dedicated
(Optional)
Disconnect
Dimensional & Wiring Specifications
STV 200/400K Series
Catalog
Number
Dimensions (in/mm) Weight
lbs (kg)
Suggested
Breaker Size
Suggested Wire
Size (AWG)
Allowable Breaker
Range
Allowable
Wire Range
A B C D E F
STV 200K 16.25 14.25 8.25 16.75 12 .31 35 (15.88) 40 A #8 15 A–100 A #14–#2
STV 400K 16.25 14.25 8.25 16.75 12 .31 42 (19.05) 100 A #2 15 A–100 A #14–#2
STV 200/400K Series with Rotary Disconnect
Catalog
Number
Dimensions (inches) Weight
lbs (kg)
Suggested
Breaker Size
Suggested Wire
Size (AWG)
Allowable Breaker
Range
Allowable
Wire Range
A B C D E F
STV 200K 16.25 14.25 8.25 16.75 12 .31 38 (17.23) 40 A #8 15 A–175 A #14–2/0
STV 400K 16.25 14.25 8.25 16.75 12 .31 45 (20.41) 100 A #2 15 A–175 A #14–2/0
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
14
1Power Protection and Conditioning
The STV 100K Series - Surge Protective Devices
SolaHD’s STV 100K series is a hardwired surge
protective devices are designed for installation at the service
entrance, branch panel or a dedicated sensitive electronic
load. These units feature all mode protection, LED and au-
dible alarm status indication, sinewave tracking and form “C”
dry contacts. The STV 100K series also contains the highest
levels of safety built into the product including thermal fusing
and a fault current fusing level of 65 kAIC.
Features
100,000 amp peak current rating provides all mode
protection against severe transients
Low clamping levels for more effective protection
65 kAIC fault current fusing level provides safety
and NEC conformance
LED status and audible alarms
Listed to UL 1449, 3rd Edition
Compact, rugged metal NEMA 12 enclosure
Applications
Distribution Panels (<1200 A)
Branch, Lighting and Control Panels
Factory Automation Installations
Dedicated Industrial Equipment
Related Products
Power Conditioners
UPS
Drive Isolation and K-Factor Transformers
Selection Table
Dimensions
Catalog
Number Input Voltage
STV 100K-10S 120/240 V Single Phase 3 wire + Ground
STV 100K-10Y 208Y/120 V Three Phase Wye 4 wire + Ground
STV 100K-10N 120 V Single Phase 2 wire + Ground
STV 100K-24L 240 V Single Phase 2 wire + Ground
STV 100K-23Y 380Y/220 V Three Phase Wye 4 wire + Ground
STV 100K-27Y 480Y/277 V Three Phase Wye 4 wire + Ground
STV 100K-24D 240 V Three Phase 3 wire + Ground
STV 100K-48D 480 V Three Phase 3 wire + Ground
STV 100K-10D4 240/120 CT Three Phase 4 wire + Ground
STV 100K-24D4 480/240 CT Three Phase 4 wire + Ground
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 15
1
Power Protection and Conditioning
STV 100K Specifications
Description
Catalog Number
STV 100K-10S STV 100K-10N STV 100K-24L STV 100K-10Y STV 100K-23Y STV 100K-27Y STV 100K-24D STV 100K-48D STV 100K-10D4 STV 100K-24D4
Input Vac
120/240 V 120 V 240 V 208Y/120 V 380Y/220 V 480Y/277 V 240 V 480 V 120/240 CT 240/480 CT
Single Phase
3 wire + Ground
Single Phase
2 wire + Ground
Three Phase Wye
4 wire + Ground
Three Phase
3 wire + Ground
Three Phase
4 wire + Ground
Maximum
Continuous
Operating
Voltage (MCOV)
125% of the nominal level for 120 V; 115% for all other input voltages
Line Frequency 47-63 Hz
Connection/
Mounting Type Parallel/Flange
Enclosure Metal, NEMA 12 Enclosure
Dimensions -
in (mm)
(H x W x D)
4 x 6 x 4
(101.6 x 152.4 x 101.6)
Weight (lbs/kg) 8 lb/3.63 kg max.
Modes of
Protection All Mode: L - N, L - L, L - G, N - G
Safety Agency
Approvals UL 1449 3rd Edition, cUL
UL 1449 (2nd Edition) Suppressor Classification
L - N 400 V 400 V N/A 400 V 800 V 800 V N/A N/A 400 V 800 V
L - L 800 V N/A 800 V 800 V 1500 V 1500 V 1500 V 1500 V 800 V 1500 V
L - G 400 V 400 V 800 V 400 V 800 V 800 V 1500 V 1500 V 400 V 800 V
N - G 400 V 400 V N/A 400 V 800 V 800 V N/A N/A 400 V 800 V
A/C Rating 65 kAIC
Status
Indication 3-Green LEDs, 1 per phase, 1-Red LED, Form C Contacts, Audible Alarm
Response Time < 0.5 nsec
Operating
Temperature -40°C to +60°C
Operating
Humidity 0% to 95% Non-condensing
Fusing Thermal and Fault Current
Noise
Attenuation 40 dB Max
Peak Surge Current Capability
Per Phase
Line to Neutral
Line to Line
Line to Ground
Neutral to
Ground
100 kA
50 kA
50 kA
50 kA
50 kA
100 kA
50 kA
N/A
50 kA
50 kA
100 kA
N/A
50 kA
50 kA
N/A
100 kA
50 kA
50 kA
50 kA
50 kA
100 kA
50 kA
50 kA
50 kA
50 kA
100 kA
50 kA
50 kA
50 kA
50 kA
100 kA
N/A
50 kA
50 kA
N/A
100 kA
N/A
50 kA
50 kA
N/A
100 kA
50 kA
50 kA
50 kA
50 kA
100 kA
50 kA
50 kA
50 kA
50 kA
Warranty 10 years
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
16
1Power Protection and Conditioning
Catalog Number Input Voltage
STV 25K-10S 120 V Single Phase (L - N)
STV 25K-24S 240 V Single Phase (L1 - L2)
Selection Table
The STV 25K DIN Rail Series - Surge Protective Devices
Dimensions
This series provides point-of-
use protection, at the dedi-
cated equipment level, against
damaging transients. Ideal for
installation in electronic control
cabinets found in harsh in-
dustrial environments such as
the factory oor or at remote
locations. These devices
provide 50,000 amps of surge
protection, sinewave tracking,
LED status indication and form
“C” dry contacts. This DIN Rail
series also provides protection
on all electrical paths and comes with a standard ten
year product warranty. The STV 25K DIN Rail series surge
protective devices are UL recognized to Standard 1449,
3rd Edition.
Applications (20 Amp Max)
Control Cabinets for Industrial Automation
Point-of-Use Industrial/Service Equipment
Remote Commercial or Industrial Equipment
Instrumentation and Large Test Equipment
Commercial and Building Automation Systems
Features
Compact and narrow design maximizes panel space.
Low clamping levels for more effective protection.
Easy access terminal screws for quick mounting
and installation.
50,000 amps of surge protection.
Sine wave tracking and all mode protection provide
consistent and reliable protection on all electrical paths.
Patented thermal fusing prevents MOV overheating
caused by excessive current levels.
Related Products
DIN Rail Power Supplies
DIN Rail AC UPS
Industrial Control Transformers
Line Reactors
Active Tracking® Filters
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 17
1
Power Protection and Conditioning
STV 25K Specifications
Description Catalog Number
STV 25K-10S STV 25K-24S
Input Voltage 120 Vac, Single Phase 0-135 VRMS 240 Vac, Single Phase 0-260 VRMS
Maximum Continuous
Operating Voltage (MCOV) 120 Vac - 150 VRMS 240 Vac - 275 VRMS
Line Frequency 47-63 Hz
Connection/Mounting Type DIN Rail Mount (Chassis Mount Bracket Optional order
SDN-PMBRK2) with screw terminals for #12 AWG.
Input Current Rating 20 Amps
Phase Configuration 2 wire + GND
Weight - lbs (kg) 3 lbs/1.36 kg
Dimensions (H x W x D) 4.87 x 2.5 x 4.375 (12.37 x 6.35 x 11.11)
includes mounting bracket
Modes of Protection All Mode: L - N, L - L, L - G, N-G
Safety Agency Approvals UL 1449 3rd Edition
UL 1449 (2nd Edition)
Suppressor Classification
120 Vac Normal/Common Mode
240 Vac Normal/Common Mode
400 Vac
800 Vac
Status Indication Green LED, Form C Contacts
Packaging Metal DIN Rail Mount Enclosure, IP20
Response Time < 0.5 nsec
Operating Temperature -40°C to +60°C
Operating Humidity 0% to 95% Non-condensing
Noise Attenuation
Normal Mode
Common Mode
50 dB Min
40 dB Min
Peak Surge Current Capability (8 x 20 µs)
Line to Neutral
Line to Ground
Neutral to Ground
25 kA
25 kA
25 kA
Warranty 10 Years
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
18
1Power Protection and Conditioning
STF Series – Active Tracking® Filters
Low voltage/high frequency noise is caused by everyday
events such as turning on machinery, motors, or equipment.
Although noise is less dramatic than high voltage transients,
the long term effects of these frequent disturbances can
be as damaging. Filtering systems such as SolaHD Active
Tracking® Filters provide clean AC power by eliminating
lower voltage noise.
The SolaHD STF Series offers the original active tracking
technology to guard against commonly occurring but very
damaging, lower energy transients. Offering excellent noise
reduction, the lter continuously tracks the input AC power
line and responds instantly upon detecting extraneous high
frequency noise.
The STF Series eliminates low voltage/high frequency noise
via a low-pass or L-C lter. These lters are used for low
energy, high frequency noise reduction and consist of a
series of inductors, capacitors and resistors. STFs are load
dependent which means that the series inductors located on
each phase and neutral conductors are sized to handle the
maximum current draw on the line. These inductors together
with the capacitors and resistors form a circuit capable of
absorbing a large bandwidth of noise.
These devices are designed to meet UL 1283, and CSA
C22.2 for Electromagnetic Interference Filters. STFs
attenuate or reduce the amplitude of noise to a minimum
of 40dB that occurs in a frequency range of 50 KHz to
50 MHz. They also provide the industry’s best IEEE Category
“A” protection, typically reducing normal mode transients
to +/- 5 volts.
Built to meet your unique requirements, these lters are
available in a multitude of voltage and phase congurations.
They are hardwired and designed for years of trouble free
operation requiring little or no operator intervention after
installation.
Active Tracking® Filters are one part of a total power
quality solution. They can be used alone or in conjunction
with other SolaHD products to solve more complex power
quality problems.
Applications
Branch and Control Panels
Factory Automation Installations
Point of Use Industrial Service Equipment
Dedicated Industrial and Machine Tools Equipment
Telecommunications Equipment
Features
Non degrading, series lter technology for
total durability
High Frequency Noise lter, RLC Low-Pass lter
Single Phase applications up to 30 Amp
Three Phase applications up to 200 Amp
Attenuates noise to 40 dB in frequency range
of 50 kHz to 50 MHz
Operating Temperature from -40°C to +45°C.
Hardwired connection
MTBF greater than 100,000 Hours, Mil Std. 217F
UL 1283 Listed or
Recognized (Single Phase models), CSA
10 Year Limited Warranty
Related Products
Single and Three Phase Power Conditioners
Uninterruptible Power System
Transient Voltage Surge Suppressors
Power Supplies
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 19
1
Power Protection and Conditioning
Catalog
Number Amps Min. Wire Size
(AWG Suggested)
Fuse/Circuit Breaker Ampacity Case Dim. (in)
A x B x C
Mounting Flange
Dim. (in) D x E x F
Weight
lbs (kg)
Design
Style
Suggest Max
Single-Phase Models (120 Vac)*
STF0025-10N 2.5 26 2.5A 3.125A 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 2.0 (.91) 1
STF0050-10N 5.0 22 5A 6.25A 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 2.0 (.91) 1
STF0075-10N 7.5 18 7.5A 9.375A 4.75 x 4.75 x 2.35 5.25 x 3.5 x 6.25 3.0 (1.36) 1
STF0150-10N 15.0 14 15A 18.75 6.25 x 4.75 x 2.35 6.75 x 3.5 x 7.75 5.0 (2.27) 1
STF0200-10N 20.0 12 20A 25A 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 7.0 (3.17) 1
STF0300-10N 30.0 10 30A 37.5A 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 8.0 (3.63) 1
Single-Phase Models (240 Vac)*
STF0025-24L 2.5 26 2.5A 3.125A 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 2.0 (.91) 1
STF0050-24L 5.0 22 5A 6.25A 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 2.0 (.91) 1
STF0075-24L 7.5 18 7.5A 9.375A 4.75 x 4.75 x 2.35 5.25 x 3.5 x 6.25 3.0 (1.36) 1
STF0150-24L 15.0 14 15A 18.75 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 5.0 (2.27) 1
STF0200-24L 20.0 12 20A 25A 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 7.0 (3.17) 1
STF0300-24L 30.0 10 30A 37.5A 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 8.0 (3.63) 1
Three-Phase Models (120/208 Vac WYE)**
STF0150-10Y 15.0 14 15A 18.75A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0300-10Y 30.0 10 30A 37.5A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0500-10Y 50.0 4 50A 62.5A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF1000-10Y 100.0 2 100A 125A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF2000-10Y 200.0 3/0 200A 250A 24 x 20 x 9 25.25 x 14.0 x 26.5 110.0 (49.89) 2
Three-Phase Models (240 Delta)**
STF0150-24D 15.0 14 15A 18.75A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0300-24D 30.0 10 30A 37.5A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0500-24D 50.0 4 50A 62.5A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF1000-24D 100.0 2 100A 125A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF2000-24D 200.0 3/0 200A 250A 24 x 20 x 9 25.25 x 14.0 x 26.5 110.0 (49.89) 2
Three-Phase Models (277/480 V WYE)**
STF0150-27Y 15.0 14 15A 18.75A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0300-27Y 30.0 10 30A 37.5A 14 x 12 x 6 14.75 x 10.0 x 15.5 38.0 (17.24) 4
STF0500-27Y 50.0 4 50A 62.5A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF1000-27Y 100.0 2 100A 125A 20 x 16 x 9 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF2000-27Y 200.0 3/0 200A 250A 24 x 20 x 9 25.25 x 14.0 x 26.5 110.0 (49.89) 2
Three-Phase Models (480 V Delta)**
STF0150-48D 15.0 14 15A 18.75A 10.0 x 8.0 x 6.0 10.75 x 6.0 x 11.5 38.0 (17.24) 4
STF0300-48D 30.0 10 30A 37.5A 10.0 x 8.0 x 6.0 10.75 x 6.0 x 11.5 38.0 (17.24) 4
STF0500-48D 50.0 4 50A 62.5A 14.0 x 12.0 x 6.0 14.75 x 10.0 x 15.5 85.0 (38.55) 4
STF1000-48D 100.0 2 100A 125A 20.0 x 16.0 x 9.0 21.25 x 10.0 x 22.5 85.0 (38.55) 2
STF2000-48D 200.0 3/0 200A 250A 24.0 x 20.0 x 9.0 25.25 x 14.0 x 26.5 110.0 (49.89) 2
Selection Table
* With barrier strip at input and output
**Units are standard in NEMA 12 hinged enclosures
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
20
1Power Protection and Conditioning
Dimensional Drawings
MOUNTING
DIMENSIONS
F
Design Style 1 Design Style 2
F
Design Style 3 Design Style 4
STF Specifications
Description 120 Vac Models 240 Vac Models 480 Vac Models
Input Voltage 0-150 VRMS 0-275 VRMS 0-520 VRMS
Line Frequency 50/60 Hz
Transient Attenuation Response Time Instantaneous
Mean Time Between Failure (MTBF) > 100,000 Hours (Mil Std. 217F)
Packaging
Single phase units through 30 Amps housed in black, high impact plastic case, Vacuum
impregnated magnetics, epoxy encapsulated; single phase greater than 30 Amps,
480 Vac, and three phase units housed in NEMA 12 enclosures
Operating Temperature -40°C to +45°C Derate Linearly to 60% at +70ºC
Load Surge Current Rating
10m sec: 5 x Nominal
1 sec : 3 x Nominal
5 sec: 2 x Nominal
Transient Reduction
Minimum of 40dB from 50 kHz through 50 MHz. Attenuation is greater than 50 dB to the surge withstand
capability Ringwave test IEEE C62.41, Category “A” (IEEE Category A Ringwave 6 kV, 200A, 100 kHz)
and “B” (IEEE Category B Ringwave 6 kV, 500 A, 100 kHz).
Safety ANSI / UL1283, CAN/CSA C22.2 No 8. Listed or Recognized “Electromagnetic Interference Filters”
Warranty 10 years
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 21
1
Power Protection and Conditioning
STFV Plus Series – Active Tracking® Filtering with Surge Protection
The SolaHD STFV Plus Series combines Active Tracking®
ltration for low energy noise and surge protection for high
energy transients. It continuously tracks the input AC power
line responding instantly into action upon detecting extrane-
ous high frequency noise and high voltage transients caused
by everyday events such as turning on machinery, motors,
or equipment.
These devices are designed to meet UL 1283 for
Electromagnetic Interference Filters. STFV Plus attenuates
or reduces the amplitude of high frequency noise to a
maximum of 90dB that occurs in a range of 100 kHz to
50 MHz. STFV Plus provides the industry’s best IEEE C62.41
Category “A & B” Ringwave protection.
They are built to meet your unique requirements, and are
available in hardwired, single phase conguration. They are
designed for years of trouble free operation and require little
or no operator intervention after installation.
Active Tracking® Filters Plus is one part of a total power
quality solution. They can be used alone or in conjunction
with other SolaHD products to solve more complex power
quality problems.
Features
Non degrading, series Filter/TVSS technology
for total durability
UL Listed surge current capacity – 25,000 Amps
High impact plastic case, epoxy encapsulated enclosure
Transient protection in all modes (L-N, L-G, and N-G)
Single Phase applications up to 30 Amp
Operating Temperature from -40°C to +60°C
Hardwired connection
LED power indication
UL 1283
10 Year Limited Warranty
Applications
Branch and Control Panels
Factory Automation Installations
Point of Use Industrial Service Equipment
Programmable Logic Controllers
Dedicated Industrial and Machine tools
Telecommunications and IT equipment
Related Products
Power Conditioners
Uninterruptible Power System
Power Supplies
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
22
1Power Protection and Conditioning
Catalog
Number Amps Case Dim. (in)
A x B x C
Mounting Flange Dim. (in)
D x E x F x G
Number Min.
Wire Size
(AWG Suggested)
Screw
Size
Fuse/Circuit Breaker
Ampacity Weight
lbs (kg)
Suggest Max
Single-Phase Models (120 Vac)
STFV025-10N 2.5 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 x 0.19 26 #6 2.5 3.125 1.0 (.45)
STFV050-10N 5.0 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 x 0.19 22 #6 5 6.25 1.3 (.59)
STFV075-10N 7.5 4.75 x 4.75 x 2.35 5.25 x 3.5 x 6.25 x 0.19 18 #6 7.5 6.25 2.0 (.91)
STFV150-10N 15.0 6.25 x 4.75 x 2.35 6.75 x 3.5 x 7.75 x 0.19 14 #8 15 18.75 3.5 (1.59)
STFV300-10N 30.0 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 x 0.19 10 #8 30 37.5 6.0 (2.72)
Single-Phase Models (240 Vac)
STFV025-24L 2.5 4.0 x 2.88 x 1.81 4.38 x 2.12 x 5.31 x 0.19 26 #6 2.5 3.125 1.3 (.59)
STFV050-24L 5.0 4.75 x 4.75 x 2.35 5.25 x 3.5 x 6.25 x 0.19 22 #6 5 6.25 2.0 (.91)
STFV075-24L 7.5 6.25 x 4.75 x 2.35 6.75 x 3.5 x 7.75 x 0.19 18 #6 7.5 9.375 3.5 (1.59)
STFV150-24L 15.0 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 x 0.19 14 #8 15 18.75 5.8 (2.63)
STFV300-24L 30.0 7.75 x 4.75 x 2.35 8.25 x 3.5 x 9.0 x 0.19 10 #8 30 37.5 6.0 (2.72)
Selection Table
MOUNTING
DIMENSIONS
Dimensions System Design
Series Blocking Inductors
smoothing inductors
Shunt Absorbing Components
sine wave tracking circuitry
MOV Transient Protection
high-energy transient protection
line to neutral, line to ground,
neutral to ground
Pulse Capacitor
high-frequency noise absorption
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 23
1
Power Protection and Conditioning
Description Value
Input Voltage 120 Vac Models 0-150 VRMS
240 Vac Models 0-275 VRMS
Line Frequency 50/60 Hz
Configuration Single Phase (2 wire + ground)
Response Time < 5 ns
Enclosure High impact plastic case, 94V0, Vacuum impregnated magnetics, epoxy encapsulated
Fusing External
Status Indication Green LED
Connection/Mounting Type Series/Panel Mount
Operating Temperature -40°C to +60°C at full load
Derate Linearly to 60% at +70ºC
Operating Humidity 0% to 95% Non-condensing
Mean Time Between Failure (MTBF) Greater than 100,000 hours (Mil. Std. 217F)
Packaging High impact plastic case, Vacuum impregnated magnetics, epoxy encapsulated
Peak Surge Current
Capability (8 x 20 µs)
Per Phase 25,000 Amps
Line to Neutral 12,500 Amps
Line to Ground 12,500 Amps
Neutral to Ground 12,500 Amps
Load Surge Current Rating
10m sec 5 x Nominal
1 sec 3 x Nominal
10 sec 2 x Nominal
Frequency Response
(Forward Reverse) 100 kHz to 50 MHz 90 dB Max
Transient Reduction*
(IEEE C62.41)
Typical Category A Ringwave
(6 kV, 200A, 100 kHz) < 10 volts peak
Typical Category B Ringwave
(6 kV, 500A, 100 kHz) < 50 volts peak
Safety ANSI / UL1283 Recognized “Electromagnetic Interference Filters”
Warranty 10 years
STFV Specifications
* All measurements in volts. IEEE test results with no AC applied.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
24
1Power Protection and Conditioning
STFE Elite Series - Active Tracking® Filters with Surge Protection
The SolaHD STF Elite DIN Rail Mount Series combines
Active Tracking® technology with UL Listed surge
protection to protect against the full spectrum of voltage
transients and surges. It continuously tracks the input AC
power line responding instantly into action upon detecting
extraneous high frequency noise and high voltage transients
caused by everyday events such as turning on machinery,
motors, or equipment.
These devices are designed to meet UL 1449 3rd Edition,
UL 1283, cUL recognized, and CE. STFE attenuates or
reduces the amplitude of normal mode noise to a minimum
of 90dB that occurs in a frequency range of 100KHz to
50MHz, and of common mode noise to a minimum of 60dB
that occurs in a frequency range of 5MHz to 50MHz. STFE
provides the industry’s best IEEE C62.41 Category “A & B”
Ringwave protection.
They are built to meet your unique requirements, and
are available in hardwired DIN Rail mount, single phase
conguration. They are designed for years of trouble free
operation and require little or no operator intervention after
installation.
Related Products
Power Conditioners
Uninterruptible Power System
Power Supplies
Selection Table
Catalog
Number Input Voltage
STFE030-10N 120 V Single Phase 2 Wire + Ground
STFE050-10N 120 V Single Phase 2 Wire + Ground
STFE100-10N 120 V Single Phase 2 Wire + Ground
STFE200-10N 120 V Single Phase 2 Wire + Ground
STFE030-24L 240 V Single Phase 2 Wire + Ground
STFE050-24L 240 V Single Phase 2 Wire + Ground
STFE100-24L 240 V Single Phase 2 Wire + Ground
STFE200-24L 240 V Single Phase 2 Wire + Ground
Features
Series connected DIN Rail mounted lter
Patented durable metal mount clip
UL Listed Surge current capacity – 45,000 Amps
Transient protection in all modes (L-N, L-G, and N-G)
Single Phase applications up to 20 Amp
Operating Temperature from -40°C to +50°C
Screw Terminal Connections
- Reliable and convenient screw clamp connections
- Accept 10-16 AWG wire
- Meet IP20 specications for ingress protection
LED status indication
Form C contact for remote monitoring
UL 1449 3rd Edition, UL 1283, cUL recognized
component, CE
5 Year Limited Warranty
Applications
Control Panels
Factory Automation Installations
Point of Use Industrial Equipment
Programmable Logic Controllers
Dedicated Industrial and Machine Tools Equipment
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 25
1
Power Protection and Conditioning
Description STFEXXX-10N STFEXXX-24L
Input Voltage 120 V (0-150 VRMS) 240 V (0-275 VRMS)
Line Frequency 47 - 63 Hz
Response Time < .5 ns normal mode, <5 ns common mode
Enclosure Fully Enclosed Metal Housing
Fusing Reference Fuse/Circuit Breaker Chart
Status Indication Green LED “OK”/Form C Contact/10 Amps @ 250 Vac or 5 Amps @ 100 Vdc
Connection/Mounting Type DIN Rail Mount
Operating Temperature -40°C to +50°C at full load Derate Linearly to 60% at +70ºC
Weight (Kg) 1.7 lbs (0.7kg)
Dimensions - in (mm)
(H x W x D)
4.88 x 2.56 x 4.56
(124 x 65 x 116)
Operating Humidity 0% to 95% Non-condensing
Peak Surge Current Capability
Per Phase 30,000 Amps
Line to Neutral 20,000 Amps
Line to Ground 10,000 Amps
Neutral to Ground 10,000 Amps
Load Surge Current Rating
10m Sec 5 x Nominal
1 sec 3 x Nominal
10 sec 2 x Nominal
Frequency Response
Normal Mode (Forward-Reverse) 100 kHz to 50 MHz 90 dB Max
Common Mode (Forward-Reverse) 5 MHz to 50 MHz 60 dB Max
Transient Reduction
(IEEE C62.41)
Typical Category A Ringwave
(6 kV, 200A, 100 kHz) < 60 V Peak
Typical Category B Ringwave
(6 kV, 500A, 100 kHz) <100 V Peak UL 1449
Safety UL 1449 3rd Edition, UL1283, cUL Recognized Component, CE
STFE Specifications
Connection Diagram
LINE LOAD
L/L1
N/L2
GND
L/L1
N/L2
GND
L/L1
TO
REMOTE INDICATION
IF NEEDED
TO LOAD OR
EQUIPMENT
PROTECT
RELAY
CONTACTS
NO COM NC
L/L1
N/L2
N/L2
GND
GND
LINE INPUT
FROM SOURCE
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
26
1Power Protection and Conditioning
Dimensional Diagram
Active Tracking Filter
STFE Elite Series
NO COM NC L/L1 N/12
L/L1 N/L2
2.560
4.560
4.880
Catalog Number Amps Min Wire Size*
(AWG Suggested)
Fuse/Circuit Breaker Ampacity
Suggest Max
Single-Phase Models (120 Vac)
STFE030-10N 3.0 24 3A 3.75A
STFE050-10N 5.0 22 5A 6.25A
STFE100-10N 10.0 20 10A 12.5A
STFE200-10N 20.0 12 20A 25A
Single-Phase Models (240 Vac)
STFE030-24L 3.0 24 3A 3.75A
STFE050-24L 5.0 22 5A 6.25A
STFE100-24L 10.0 20 10A 12.5A
STFE200-24L 20.0 12 20A 25A
Wiring Specifications
Internal View
of Components
MOV Array
provides high-energy
all mode protection
Series Blocking Inductor
blocks voltage, smooths current
Silicone Avalanche Diodes
fast responding surge suppressor
Finger Safe Terminals
Green LED Unit Status Indicator
Pulse Capacitor
high-frequency noise absorption
Form C Relay Contacts
DC OK signal
Rear View
DIN Connector
Strong all metal for
horizontal or vertical
mounting
Internal Diagram
*16 AWG wire or larger may be required by code dependent upon
the application.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 27
1
Power Protection and Conditioning
STC Series – Data/Signal Line Surge Protection Devices for Transient Data
The rapid development of automated controls, telecommu-
nications and re/security systems has made it imperative to
have properly coordinated low-voltage protection. Modern
networked industrial facilities require error free transmission
of information for maximum productivity and integrity of data.
The SolaHD STC series protects all susceptible low-voltage
cable routes entering a facility and at key points within the
building. These devices can be used as part of a multi-stage
protection strategy which involves clamping the initial high-
energy impulse, ltering any remaining noise or transients
to the PLC or sensitive equipment and nally, protecting
the Data/Signal lines entering and leaving the control panel.
Modern, networked industrial facilities require error free
transmission of information for maximum productivity and
data integrity.
The hybrid design of these Data/Signal Line surge
suppressors allows them to respond quickly with high
energy absorption. These units are available in a variety of
application specic voltage levels and packaging congura-
tions. The STC series is used to protect network signal lines
entering or leaving control panels including PLCs, universal
remote I/O, DeviceNetTM and Data Highway Plus.
Series Application
STC-P0E Power-over-Ethernet, Category 5 and Category 6
STC-DRS DIN Rail mountable, single pair surge protection
STC-642 Two-Pair Data/Signal Protection
STC-CCTV High-Frequency Coaxial protection for head and camera ends
STC-TEL RJ11 Telephone Protection
Low Voltage - Data/Signal, STC Series
Related Products
Single and Three Phase Power Conditioners
Uninterruptible Power System
Transient Voltage Surge Suppressors
Active Tracking® Filters
Power Supplies
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
28
1Power Protection and Conditioning
STC-P0E Series, Category 5 and 6 Power-over-Ethernet Applications
The SolaHD STC Power-over-Ethernet (PoE) series is
designed to work on Category 5 P0E transmission lines as
well as Category 6 applications. They feature both female
to female and male to female RJ-45 connection options for
ease of installation.
Power-over-Ethernet is a technology for wired Ethernet
LANs (Local Area Networks) that allows the electrical current
to be carried by the data cables rather than power cords.
This minimizes the number of wires that must be strung in
order to install the network. The result is lower cost, less
downtime, easier maintenance and greater installation
exibility than with traditional wiring.
P0E allows users to power devices over Ethernet cabling.
Power and networking is provided over a single cable. PoE
has tremendous advantages in industrial applications. The
ease of combining signal and power in a single Ethernet
cable connection is contributing to the already rapid evolu-
tion of Ethernet-based industrial control systems. Category
5e and Category 6 commonly known as Cat5e and Cat6 are
the most widely used Ethernet connectivity methods on the
market today. Cat5e and Cat6 are dened in ANSI/TIA/EIA
568-B standard for Unshielded Twisted Pair Cabling.
Specifications
Description STC-P0E-65FF STC-P0E-65MF
Mode of Protection Normal Mode (L-L)
All Lines (1-8) Protected
DC Breakover Voltage 65 Vdc
Insertion Loss < .1 dB
Certified Transmission Speeds 10baseT, 100baseT, 1000baseT
Peak Surge Energy 300 Watt
Response Time <1 ns
Connectors RJ-45 (Female — Female) RJ-45 (Male — Female)
Dimensions - in (mm) 2.3 x 1.0 x .8
(5.84 x 2.54 x 2.032)
3.0 x 1.0 x .8
(7.62 x 2.54 x 2.032)
Warranty 3 years
The STC-P0E series is ideally suited to protect expensive
equipment and critical communication/data transfer from
internally generated transients and noise.
Features
Exceeds CAT 5 PoE & 6 Transmission Values
Applications up to 60 Vdc @ 300 mA
3 Year Limited Warranty
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 29
1
Power Protection and Conditioning
STC-DRS Series, DIN Rail Protection
Catalog
Number
Max Peak Signal
Voltage
Nominal
Breakdown
Voltage
Max Current
1p 10X1000 ms
(Occurrences)
Peak Current
8X20 ms
Typ. Cap
(PF)
Max
Continuous
Current
Nominal
Series
Resistance
STC-DRS-232 15 22 >100 10KA 1500 150ma 5 Ω
STC-DRS-036 30 36 >100 10KA 1500 150ma 5 Ω
STC-DRS-060 52 60 >100 10KA 1500 150ma 5 Ω
Notes:
These protectors are intended for indoor use on communication loop
circuits that have been isolated from the Public Switch Telephone
Network.
The communication loop circuits shall not be exposed to accidental
contact with the electric light or power conductors. The protectors
shall be installed per the applicable requirements of the National
Electric Code, ANSI/NFPA 70.
Using three-stage hybrid technology, this DIN Rail mount-
able, single pair, surge suppressor attenuates over-voltage
transients with gas tubes and silicon avalanche components
while resetable fuses (PTCs) mitigate sneak currents. The
PTC increases resistance by several orders of magnitude
when over-currents exceed safe levels. A normal state
resumes when over-currents are removed. The ability to
self-restore in this manner signicantly increases suppressor
performance and survivability.
The STC-DRS Series mounts onto a standard 35 mm
industrial DIN rail. There are three Field Side and three
Electronics Side screw terminals. One is reserved for a
shield. Three electrically tied ground terminals are provided
for grounding the unit to building-approved ground. The
shield is isolated from ground.
Features
Low-Voltage Data Surge Protection
Three-Stage Hybrid Technology
Sneak/Fault Current Protection With
Resetable Fuses (PTCs)
Low Prole Packaging
Easy Installation
Fits Standard 35 mm DIN Rail
Fast Response Time <1 Nanosecond
UL 497B Listed
• 5 Year Limited Warranty
Selection Table
Dimensions
497B
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
30
1Power Protection and Conditioning
STC-642 Series, Data/Signal Line Protection
The STC-642 series of surge suppressors are dual pair (four
wire) modules using three-stage hybrid technology. This
module addresses over voltage transients with gas tubes
and silicon avalanche components. In addition, sneak and
fault currents are mitigated with resetable fuses (PTCs). The
PTCs increase resistance several orders of magnitude when
over currents exceed safe levels. A normal state resumes
when over currents are removed. The ability to self restore in
this manner signicantly increases suppressor performance
and survivability.
The STC-642 card edge module is gold-plated, double
sided and is designed to mate with the STC-642 gold-plated
female terminal connector (sold separately). When snapped
together, the data circuits pass thru the protector in a serial
fashion from the four Field Side terminals to the four
Electronics Side terminals. Terminals 1 or 10 of the
STC-PCB1B must be attached to building approved ground.
Features
Lightning Protection for Low Voltage Data
Signal Lines
Three-Stage Protection
Sneak/Fault Current Protection
Resetable Solid-State Fuses - PTCs
Low Capacitance Option for High Speed Data
Plug-in Module / Requires PCB1B Base
Fast Response Time
UL Listed 497B
• 5 Year Limited Warranty
Specifications
Description STC642-020* STC642-036*
Peak Surge Current
(10 times)
8x20 s .. 10kA
10x700 s 500A per line
Life Expectancy 8x20 s (2000A) .. >100 occurrences
10x700 s (400A)
Response Time <1ns
Voltage Clamp 20 36
Technology SAD Hybrid
Resistance 5 (typical)
Capacitance (typical) 1500pf
Operating Temperature -40oC to +85oC
Weight 2 oz.
Dimensions H x W x L
(STC-642 & PCB1B) 2.05 x 1.0 x 2.4
Certifications UL 497B
Warranty 5 Years
Catalog Number Description
STC-PCB1B
Base for all STC-642 models. Designed to
accommodate up to 10 AWG wire. It offers Flat/
Phillips screws and can be mounted using 2 #6
size screws. Must be ordered separately.
STC-FM4-DRC Optional DIN Rail Mounting Clip for STC-PCB1B
497B
*Part number STC-PCBIB sold separately
Selection Table
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 31
1
Power Protection and Conditioning
STC-642 Series, Data/Signal Line Protection
Wiring Diagram (PIN Assignments)
The hybrid design of this product includes series
resistance. Do not place this product in service on any
signal line capable of supplying more than 150 milliamperes
continuously.
These protectors are intended for indoor use on communica-
tion loop circuits which have been isolated from the Public
Switch Telephone Network.
The communication loop circuits shall not be exposed to
accidental contact with the electric light or power conduc-
tors. The protectors shall be installed per the applicable
requirements of the National Electric Code, ANSI/NFPA 70.
Part Numbers by Application
STC642-036 & STC-PCB1B for 4-20 ma Signal
STC642-020 & STC-PCB1B for RS232
Ground Terminal 1 or 10 (internally tied together) to building approved ground. The STC-PCB1B accommodates 24 to 10 AWG wire.
Top View
Side View
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
32
1Power Protection and Conditioning
The STC-CCTV Series is tailored specically to CCTV, data,
audio and cable applications. These units are single Coax
Surge Protective Devices implementing three-stage hybrid
technology. They address overvoltage transients with
a primary gas tube, and secondary silicon avalanche
components. Over-currents (e.g. sneak and fault currents)
are mitigated with solid-state resetable fuses (PTCs). The
STC-CCTV units are designed in accordance with NFPA
780 (2004 Edition) requirements, with up to 20kA of surge
current capability. The STC-CCTV-75I model has an isolated
ground and is recommended for use at the camera end.
Features
• Hybrid, three-stage technology
• Sneak/Fault Current Protection
• Low Insertion Loss
• Shielded Case
• 5 Year Limited Warranty
Application Guide
• CCTV Head End
• CCTV Camera End
STC-CCTV Coax Series
Specifications
Description STC-CCTV-75 STC-CCTV-75I
Operating Voltage 5
Clamping Voltage 6
Frequency Range 0 to 20 MHz
Equipment Location IEEE Category C, and Category B
Rated Load Current 0.35 amperes
Topology 2-port Series
STC Technology
Primary Stage: Gas Tubes,
Secondary Stage: Silicon Avalanche Components
Third Stage: resetable fuses (PTCs)
Modes of Protection Signal to Ground
Nominal Discharge
Current per Mode 10.0 kA
Maximum Discharge
Current per Mode 20.0 kA
EMI Attenuation < 0.1 dB at 20 MHz
VSWR < 1.2
Continuous Power 0.72 Watts
Operating Humidity 0-95 % Non-condensing
Operating & Storage
Temperature -40oC to +85oC
Input & Output
Connection Type BNC, 50 Ohm
Mounting Flange
Enclosure Type Metal
Certifications UL 497B Pending, NFPA 780 (2004)
Compliant for Communication Protectors
Warranty 5 Years
497B
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 33
1
Power Protection and Conditioning
STC-TEL Series – RJ Connection Telephone Protection
The SolaHD STC-TEL series are single pair telephone or
Data Line Protectors that use an advanced two-stage hybrid
design. These units address over voltage transients with
silicon breakover devices, while sneak and fault currents are
mitigated with resetable fuses (PTCs).
These units use two screw terminals to connect a Telco line
to the protector. The equipment to be protected then plugs
into the female modular jack on the STC-TEL.
Features
<1 Nanosecond Response Time
Solid State Silicon Breakover Technology
Low Capacitance
Over current Protection
UL 497A Listed
Line-to-Line, Line-to-Ground Protection
Resetable Fuses PTCs
• 5 Year Limited Warranty
Catalog
Number
Max Peak Signal
Voltage
Nominal
Breakdown
Voltage
Max Current
1p (10X1000ms)
(Occurrences)
Max Clamp*
Voltage @Ip
Typ. Cap
(PF)
Max
Continuous
Current
Nominal
Series
Resistance
STC-TEL-200T 220 270 100 (T-G)(R-G) 10 50 150ma 8 Ω
Specifications
Installation
497A
* Forward voltage after breakover.
Applications
Telephone Lines
Data Lines
To Phone or Computer
TELCO
Building
A
pproved
Ground
To Pho
ne or Computer
Protected
Side
Un
p
rotected
Side
FAS-TE
L
R1
T1
R
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
34
1Power Protection and Conditioning
Superior voltage regulation of ±1% sets the CVS series apart
from other power conditioning technologies on the market.
Extremely tight regulation is accomplished by SolaHD’s pat-
ented ferroresonant transformer technology. The CVS recre-
ates a well regulated sinusoidal waveform that is well isolated
from input disturbances including:
Impulses Swells
Brownouts Sags
Severe waveform distortion
No other power conditioning technology provides as
complete a solution against these power quality
disturbances. The CVS series is ideal for applications
where even a small change in voltage level can lead to
unscheduled downtime, misoperation, incorrect data or
scrapped production.
Features
• Superior voltage regulation of ±1%
• Surge protection tested to ANSI/IEEE C62.41,
Class A & B Waveform
• Harmonic ltering
• Hardwired
• Acts as a Step-up/Step-down Transformer
• Galvanic isolation provides exceptional
circuit protection.
• 25 year typical Mean Time Between Failure
• No maintenance required
Selection Tables: Single Phase
Group 1 – CVS Series, 60 Hz
CVS Hardwired Series – Constant Voltage Transformers
* This unit is not CSA Certied.
Applications
Industrial automation and control equipment PLCs
Analytical laboratory and factory automating
equipment
• Photo processing equipment
Sound/recording systems
Photographic enlargers
Broadcast equipment
Related Products
On-line UPS (S4K Industrial)
Surge Protection
Three Phase Power Conditioners
Active Tracking® Filters
VA Catalog
Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship Weight
(lbs)
Design
Style
Elec
Conn
30 23-13-030-2 120 120 7 4 5 9 1 J
60 23-13-060-2 120 120 7 4 5 9 1 J
120 23-22-112-2 120, 240 120 8 4 5 13 1 J
250 23-23-125-8 120, 240, 480 120 11 6 8 29 1 G
500 23-23-150-8 120, 208, 240, 480 120, 240 13 9 7 42 1 H
1000 23-23-210-8 120, 208, 240, 480 120, 240 17 9 7 65 1 H
2000 23-23-220-8 120, 208, 240, 480 120, 240 18 13 10 111 1 H
3000 23-23-230-8 120, 208, 240, 480 120, 240 19 13 10 142 1 H
5000 23-23-250-8 120, 208, 240, 480 120, 240 28 13 10 222 1 H
7500* 23-28-275-6 240, 480 120, 240 27 25 9 365 2 J
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 35
1
Power Protection and Conditioning
Design Styles (CVS and MCR Hardwired)
Style 1 Style 2 Style 3
Specifications
Parameter Condition Value
Input
Voltage
Continuous at full load
(lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current1at Full Load & 80% of nominal input voltage Iin (VA/.87)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 60 Hz
Output
Line Regulation Vin >80% and <110% of nominal ±1%
Overload Protection At Nominal Input Voltage Current limited at 1.65 times
rated current
Output Harmonic Distortion At Full Load within Input Range 3% total RMS content
Noise Attenuation -Common Mode
-Transverse Mode
40 dB
40 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to 80°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 32 dBA to 65 dBA
Approvals 60 Hz Models UL1012, CSA2
Warranty See General Information section for details 10 Years
These styles are single phase only.
Notes:
1 - Consult user manual for fuse sizing.
2 - Applies to all models except 23-28-275-6.
3 - It is recommended that the unit run at a minimum of 40-50% load.
See the Operating Characteristics section of this chapter for more information.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
36
1Power Protection and Conditioning
The MCR Hardwired Series provides excellent noise
ltering and surge protection to safeguard connected
equipment from damage, degradation or misoperation.
Combined with the excellent voltage regulation inherent
to SolaHD’s patented ferroresonant design, the MCR can
increase the actual Mean Time Between Failure (MTBF)
of protected equipment. The MCR is a perfect choice where
dirty power, caused by impulses, swell, sags, brownouts and
waveform distortion can lead to costly downtime because of
damaged equipment.
Features
±3% output voltage regulation
Noise attenuation
- 120 dB common mode
- 60 dB transverse mode
Surge protection tested to ANSI/IEEE
C62.41 Class A & B Waveform:
- <10 V let through typical
Acts as a step-up or step-down transformer
Harmonic ltering
Hardwired
Galvanic isolation provides exceptional
circuit protection.
25 year typical MTBF
No maintenance required
Applications
• Industrial automation and control equipment PLCs
• Machine tools
• Computer loads and electronic equipment
• Robotics
• Semiconductor fabrication equipment
MCR Hardwired Series – Power Line Conditioning with Voltage Regulation
Selection Tables: Single Phase
Group 2 – MCR Series, 60 Hz Only
* Canadian option: cULus certied units must be ordered by changing “-8” (UL only) to “-C8”.
** UL Listed Only. Use Group 3 for cULus.
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship Weight
(lbs)
Design
Style
Elec
Conn
120 63-23-112-4 120, 208, 240, 480 120 9 4 5 15 1 D
250 63-23-125-4 120, 208, 240, 480 120 10 6 8 27 1 D
500 63-23-150-8 120, 208, 240, 480 120, 208, 240 13 9 7 37 1 E
750 63-23-175-8 120, 208, 240, 480 120, 208, 240 14 9 7 52 1 E
1000* 63-23-210-8 120, 208, 240, 480 120, 208, 240 17 9 7 62 1 E
1500* 63-23-215-8 120, 208, 240, 480 120, 208, 240 17 13 9 95 1 E
2000* 63-23-220-8 120, 208, 240, 480 120, 208, 240 18 13 9 109 1 E
3000* 63-23-230-8 120, 208, 240, 480 120, 208, 240 19 13 9 142 1 E
5000* 63-23-250-8 120, 208, 240, 480 120, 208, 240 28 13 9 222 1 E
7500** 63-28-275-8 208, 240, 480 120, 208, 240 27 26 9 362 2 F
10000** 63-28-310-8 208, 240, 480 120, 208, 240 28 26 9 446 2 F
15000** 63-28-315-8 208, 240, 480 120, 208, 240 28 38 10 710 3 F
Related Products
On-line UPS (S4K Industrial)
Surge Protection
Three Phase Power Conditioners
Active Tracking® Filters
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 37
1
Power Protection and Conditioning
Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation)
Selection Tables: Single Phase
Group 3 – MCR Series, 60 Hz Only
Specifications
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
500 63-31-150-8 600 120, 208, 240 13 9 7 38 1 B
1000 63-32-210-8 600 120, 208, 240 17 9 7 62 1 B
2000 63-32-220-8 600 120, 208, 240 18 13 10 109 1 B
3000 63-32-230-8 600 120, 208, 240 19 13 10 142 1 B
5000 63-29-250-8 208, 240, 480, 600 120, 208, 240 28 13 10 221 1 A
7500 63-29-275-8 208, 240, 480, 600 120, 208, 240 27 25 10 360 2 A
10000 63-29-310-8 208, 240, 480, 600 120, 208, 240 28 25 10 441 2 A
15000 63-29-315-8 208, 240, 480, 600 120, 208, 240 28 38 10 706 3 A
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
120 63-23-612-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9 6 8 24 1 C
250 63-23-625-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11 6 8 27 1 C
500 63-23-650-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13 9 7 40 1 C
1000 63-23-710-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 9 7 64 1 C
2000 63-23-720-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 13 10 113 1 C
3000 63-23-730-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27 13 10 162 1 C
5000 63-23-750-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30 13 10 266 1 C
7500 63-28-775-8 220, 240, 380, 415 110, 120, 220, 240 28 26 10 393 2 C1
10000 63-28-810-8 220, 240, 380, 415 110, 120, 220, 240 30 26 10 490 2 C2
15000 63-28-815-8 220, 240, 380, 415 110, 120, 220, 240 30 38 10 776 3 C2
Parameter Condition Value
Input
Voltage
Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current1at Full Load & 80% of nominal input voltage Iin (VA/.89)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Output
Line Regulation Vin >80% and <110% of nominal ± 5% for 50 Hz units, ± 3% for 60 Hz units
Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current
Output Harmonic Distortion At full load within input range 3% total RMS content
Noise Attenuation Common Mode
Transverse Mode
120 dB
60 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to +85°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 35 dBA to 65 dBA
Approvals
60 Hz Models UL1012, CSA evaluated by UL
50 Hz Models CE (EMC & LVD)
Warranty See General Information section for details 10 + 2 Years
Notes: 1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
38
1Power Protection and Conditioning
Primary Voltage Interconnect Connect Lines To
208 H1 to H4
H2 to H5 H1 & H5
240 H1 to H4
H3 to H6 H1 & H6
480 H3 to H4 H1 & H6
600 H3 to H4 H1 & H7
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
Primary
Voltage Interconnect Connect Lines To
600 H1 & H2
Secondary
Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
Primary Voltage Interconnect Connect Lines To
110-120 H1 to H3
H2 to H4 H1 & H4
220-240 H2 to H3 H1 & H4
380-415 H2 to H3 H1 & H5
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X3 & X2
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
220-240 H1 to H3
H2 to H5 H1 & H5
380-415 H2 to H3 H1 & H4
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X2 & X3
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
220-240 H2 to H3 H1 & H4
380-415 H2 to H3 H1 & H5
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X3 & X2
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
120 H1 & H2
208 H1 & H3
240 H1 & H4
480 H1 & H5
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2
Electrical Connections
MCR 60 Hz 5000–15000 VA MCR 60 Hz 500–3000 VA MCR 50 Hz 120–5000 VA
MCR 50 Hz 7500 VA MCR 50 Hz 10000–15000 VA
MCR 60 Hz 120–250 VA
BC
C1 C2 D
A
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 39
1
Power Protection and Conditioning
Primary Voltage Interconnect Connect Lines To
120 H1 to H3 to H6 to H8
H2 to H5 to H7 to H10 H1 & H2
208 H2 to H3 H7 to H8
H1 to H6 H4 to H9 H1 & H4
240 H2 to H3 H7 to H8
H1 to H6 H5 to H10 H1 & H5
480 H2 to H3 H5 to H6
H7 to H8 H1 & H10
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
240 X1 & X3
30 & 60 VA
Primary Voltage
120 VA
Primary Voltage
7500 VA
Primary Voltage Interconnect Connect
Lines To
120 N/A N/A Note: H3 & H4
are not used H1 & H2
N/A 120 240 H1 to H3
H2 to H4 H1 & H4
N/A 240 480 H2 to H3 H1 & H4
30 & 60 VA
Secondary Voltage
120 VA
Secondary Voltage
7500 VA
Secondary Voltage Interconnect Connect
Lines To
120 120 N/A X1 & X2
N/A N/A 120 X1 & X2 or
X3 & X2
N/A N/A 240 X1 & X3
Primary Voltage Interconnect Connect Lines To
120 H1 to H3 to H5 to H7
H2 to H4 to H6 to H8 H1 & H2
240 H2 to H3 H6 to H7
H1 to H5 H4 to H8 H1 & H4
480 H2 to H3 H4 to H5
H6 to H7 H1 & H8
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2
Primary Voltage Interconnect Connect Lines To
120 H1 & H2
208 H1 & H3
240 H1 & H4
480 H1 & H5
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
MCR 60 Hz 500–5000 VA MCR 60 Hz 7500, 10000 and 15000 VA CVS 60 Hz 250 VA only
CVS 60 Hz 500–5000 VA
EFG
HJ
Series-Multiple Primary
with Tap for two input voltages
Electrical Connections
CVS 60 Hz 30–120 VA & 7500 VA
Note:
Secondaries are
not grounded.
Ground X2 per
Code.
Open MCR/CVS terminal
Primary Voltage Interconnect Connect Lines To
208 H2 & H3
240 H2 & H4
480 H1 & H4
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
40
1Power Protection and Conditioning
The MCR provides excellent noise ltering and surge
protection to protect connected equipment from damage,
degradation or misoperation. Combined with the excellent
voltage regulation inherent to SolaHD’s patented ferroreso-
nant design, they can
increase the actual
Mean Time Between
Failure (MTBF) of
protected equipment.
These units are a
perfect choice where
dirty power caused by
impulses, swell, sags,
brownouts and wave-
form distortion can lead to
costly downtime because
of damaged equipment.
Applications
Computers/ Printers Telephone/FAX systems
POS terminals Security systems
Laboratory equipment LAN networks
Features
±3% output voltage regulation
Noise attenuation
- 120 dB common mode
- 60 dB transverse mode
Surge protection tested to ANSI/IEEE C62.41
Class A & B Waveform (<10 V let-through typical)
Harmonic ltering
Galvanic isolation provides exceptional
circuit protection.
Point-of-use Protection (cord & plug connected)
- Easy & Flexible Installation
25 year typical MTBF
No maintenance required
Related Products
DIN Rail AC UPS (SDU)
Off-Line UPS (S1K Mini-Tower)
Line-Interactive UPS (S3K Mini-Tower)
Specifications
MCR Portable Series
MCR Portable Series – Power Line Conditioning with Voltage Regulation
Parameter Condition Value
Input
Voltage Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current At Full Load & 80% of nominal input voltage Iin (VA/.89)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 60 Hz depending on model
Output
Line Regulation Vin >80% and <110% of nominal ± 3% for 60 Hz units
Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current
Output Harmonic Distortion At full load within input range 3% total RMS content
Noise Attenuation -Common Mode
-Transverse Mode
120 dB
60 dB
Let-Through ANSI/IEEE C62.41 Class A & B Waveform <10V typical
General
Efficiency At Full Load 92% Typical
Storage Temperature Humidity <95% non-condensing -20° to +85°C
Operating Temperature Humidity <95% non-condensing -20° to 40°C
Audible Noise Full Resistive Noise 35 dBA to 65 dBA
Approvals 60 Hz Models UL10121 ,CSA (or cUL)1
Warranty See General Information section for details 10 + 2 Years
Notes: 1 - Depending on model, see selection tables to conrm agency approvals for specic model numbers.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 41
1
Power Protection and Conditioning
Plug & Receptacle Reference Chart
5-15R
5-15P L5-30P
Selection Tables: Single Phase
Group A – MCR Portable Series, 60 Hz Only
* This unit is CULUS certied.
** This unit is not CSA certied.
VA Catalog
Number
Voltage
Input/Output
Height
(inch)
Width
(inch)
Depth
(inch)
Ship Weight
(lbs)
Receptacle (No.)
Type (NEMA)
Plug
(NEMA)
70 63-13-070-6 120 6 7 9 18 (4) 5-15R 5-15P
150 63-13-115-6 120 6 7 9 21 (4) 5-15R 5-15P
250 63-13-125-6 120 6 7 9 26 (4) 5-15R 5-15P
500 63-13-150-6 120 9 9 16 32 (4) 5-15R 5-15P
750 63-13-175-6 120 9 9 16 64 (4) 5-15R 5-15P
1000 63-13-210-6 120 9 9 16 69 (4) 5-15R 5-15P
1500* 63-13-215-6 120 11 11 17 95 (6) 5-15R 5-20P
2000** 63-13-220-6 120 11 11 17 115 (4) 5-15R, (1) L5-30R L5-30P
3000** 63-13-230-6 120 11 11 17 143 (4) 5-15R, (1) L5-30R 5-50P
Back Panels
60 Hz, 2000–3000 VA,
(4) 5-15R and (1)
L5-30R Receptacle
60 Hz, 70 – 1000 VA,
(4) 5-15R Receptacles
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
42
1Power Protection and Conditioning
Model Comparison
BTU Output Chart for CVS and MCR Series
Note: Ratings are for a 40oC ambient temperature.
Description Hardwired CVS Hardwired MCR Portable MCR
VA Ratings 30 to 7500 VA 120 to 15000 VA 70 to 3000 VA
Input Voltage Range +10/-20% of nominal
Voltage Regulation ±1% for an input line variation of +10/-20%.
No loss of output for line loss of 3 msec.
±3% for an input line variation of +10/-20% (50 Hz hardwired units ±5%.)
No loss of output for complete line loss of 3 msec.
Overload Limits output current to 1.65 x rated current at nominal input.
Output Harmonic
Distortion 3% total RMS content at full load.
Noise Isolation 40 dB common and normal code. 120 dB common mode and 60 dB normal mode.
Surge Protection
Up to 6000 Volt surges are suppressed to a
let through of less than 1% per ANSI/IEEE
C62.41 Class A & B waveforms.
ANSI/IEEE C62.41 Class A & B 6000 waveforms are
suppressed to a let-through of less than 0.2%.
Efficiency Up to 92% at full load Up to 90% at full load
Operating
Temperature -20oC to 50oC -20oC to 40oC
Audible Noise 32 dB to 65 dB 35 dB to 65 dB 34 dB to 49 dB
Conformance Listed to UL 1012. CSA Certied
UL Listed and CSA Certied. 50 Hz
models in compliance with Low Voltage
Directive Specication EN60950.
Listed to UL 1012. CSA Certied on
all models except 3000 VA.
Warranty 10 years
VA Ratings 120 250 500 750 1000 1500 2000 3000 5000 7500 10000 15000
Total BTU’s 136 225 280 444 519 686 1229 1331 2117 2407 3209 4813
Note: All values are typical and may vary based on VA ratings of actual units.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 43
1
Power Protection and Conditioning
Operating Characteristics of the CVS & MCR Series
Regulation
SolaHD’s CVS power conditioners will hold output voltages
to ±1.0% or less with input variations as great as ±15%
(115V ±15% or 120 V +10%/-20%). Units operated at less
than rated load will maintain approximately ±1% regulation
over a wider input line voltage variation. Output meets NEMA
voltage specications even when input voltage drops to 65%
of nominal. The output versus input voltage relationship for a
typical CVS is show in Figure A.
Figure A: Load Variation
Note: MCR line regulations: ±3% for 60 Hz; ±5% for 50 Hz.
The typical performances shown in Figure B indicate that
most of the residual changes take place near the lower
(95 V) and upper (130 V) ends of the input range. It is
possible to improve output regulation if line variations remain
within a restricted range near the center of the nameplate
range (for example, 100-120 V).
Figure B: Line Regulation
Except as noted, all characteristics of Sola/HD’s CVS products
also apply to the MCR series.
Normally, the output voltage will rise as the load is
decreased. Typical percentages for changes in resistive
load from full to zero load as shown below.
Input Characteristics
SolaHD power conditioners include a resonant circuit that
is energized whether or not it is serving load. The input
current at no load or light load may run 50% or more of the
full primary current. As a result, the temperature of the unit
may rise to substantially full-load level, even at light or no
load. Input power factor will average 90-100% at full load,
but may drop to about 75% at half load and 25% at no load.
In any case, the current is always leading. The input no load
watts are about 12.5% of the VA rating.
Frequency
Output voltage varies linearly with a change of frequency of
the input voltage. This change is about 1.5% of the
output voltage for each 1% change in input frequency and in
the same direction as the frequency change.
Power Factor
SolaHD power conditioners regulate any power factor load.
Output voltage is a function of load current and load power
factor (see Figure C). If lower voltage under lagging power
factor is objectionable, correction may be made with capaci-
tors at the load. “Median” value of output voltage will vary
from the nameplate rating if the load has a power
factor other than that for which the transformer was
designed. Load regulation will also be relatively greater as
the inductive load power factor is decreased (see Figure C).
However, the resulting median values of output voltage will
be regulated against supply line changes at any reasonable
load or load power factor.
CVS Conditioner
Rating - VA
Increase in Output Voltage due to
Load Removal
30 3%
60 & 120 2%
250 & over 1%
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
44
1Power Protection and Conditioning
Motor Loads
Because of the fast response time of the SolaHD circuit, any
current-limiting characteristic must be taken into account
for transient overloads such as motor starting and solenoid
operation. In general, the SolaHD constant voltage regulator
must have a capacity nearly equal to the maximum demand
made on it, even for an instant. To determine the power
rating of the regulator, peak motor-starting current or
solenoid inrush current should be measured or power factor
correcting capacitors should be used to reduce the starting
VA of the load.
Response Time
An important advantage of SolaHD’s ferroresonant trans-
former is its fast response time compared with other types of
AC regulators. Transient changes in supply voltage are
usually corrected within 1½ cycles or less; the output
voltage will not uctuate more than a few percent, even
during this interval.
Figure D: Overload Performance
Figure C: Power Factor
Efficiency
The copper magnet wire and lamination material used in
SolaHD ferroresonant products are selected to achieve
efciencies of 90% or higher. Whether or not an external load
is being served, current will be drawn from the line whenever
the primary is energized, since the capacitor remains con-
nected in the circuit.
Overload and Short Circuits
When the load is increased beyond the regulator’s rated
value, a point is reached where the output voltage suddenly
collapses and will not regain its normal value until the load is
partially released. Under direct short circuit, the load current
is limited to approximately 150-200% of the rated full load
value and the input watts to less than 10% of normal.
A constant voltage regulator will protect both itself and its
load against damage from excessive fault currents. Fusing
of load currents may not be necessary. The actual value of
short-circuit current varies with the specic design and
rating. Units may be operated indenitely at short-circuit.
This characteristic protects the unit itself as well as the load
and load circuit being served. Typical overload
performance is shown in Figure D.
Operating Characteristics of the CVS & MCR Series
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 45
1
Power Protection and Conditioning
Temperature
SolaHD’s ferroresonant power conditioners are very stable
with respect to temperature. The change in output voltage
is only 0.025%/°C. Units are factory adjusted to +2%/-0%
of nominal, with full load and nominal input voltage. This
adjustment to the high side of nominal is to compensate for
the natural temperature drift of about 1% that takes place
during initial turn-on or warm-up. When the unit warms up to
operating temperature, the voltage typically falls about 1%.
At a stable operating temperature, the output voltage will
change slightly with varying ambient temperatures. This shift
is equal to approximately 1% for each 40°C of temperature
change. The normal maximum temperature rise of a SolaHD
power conditioner may fall anywhere in the range of 40°C
to 110°C depending on the type and rating. The nominal
design ambient range is between -20°C and +50°C (-20°C
to +40°C for 70 - 1000 VA, 60 Hz portable models).
External Magnetic Field
In almost all applications, this effect may be disregarded.
The exclusive SolaHD “wide outside leg” construction (U.S.
Patent 2,806,199) reduces stray magnetic elds to a practi-
cal minimum. On critical applications, care should be taken
in orientation of the core with respect to critical circuits to
minimize the effect of the eld.
Phase Shift
The phase difference which exists between input and
output voltages is in the range of 120 degrees to 140
degrees at full load. This phase difference varies with the
magnitude and power factor of the load, and to a lesser
extent, with changes in line voltage and load power factor.
Transient Protection
Ferroresonant power conditioners protect input transients
(caused by lightning and load switching) from damaging the
sensitive electronic load. A typical surge protective device
(SPD) tries to ‘clamp’ a transient by diverting it to ground.
A ferroresonant power conditioner “blocks” the transient.
This ‘blocking’ action is achieved by total physical separation
from input (primary) to output (secondary). Because of
this difference in operation, it is difcult to apply the same
specications to a ferroresonant power conditioner. Some
parallels can be made however.
One, is that under load, the let-through voltage of a
ferroresonant power conditioner (SPD refers to "clamping
voltage”) is less than 10 V above the point where the sine
wave would normally be at any given time. The ferroreso-
nant power conditioner is an ‘active tracking’ suppressor
with several advantages. The Ferro power conditioner will
not shunt the transient to the ground line as SPD devices
typically do. Shunting the transient to ground can cause the
disturbance to be transmitted to other sensitive loads within
a facility. This can pose serious problems with electronic or
microprocessor-based equipment, especially if there is poor
grounding within a facility. Other advantages provided by fer-
roresonant power conditioners include noise ltering, ltering
of harmonic distortion and protection against voltage uctua-
tions such as sags or swells. These features are not provided
by standard surge protection devices but are often
misrepresented or misused by SPD manufacturers trying to
market their product as a “Do All” power quality device.
Operating Characteristics of the CVS & MCR Series
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
46
1Power Protection and Conditioning
SOLATRON™ Plus Series - Three Phase Power Conditioners
Features
Rugged, industrial design
High overload capability
High MTBF - No fans used
No power factor restriction on loads
Tight regulation for protection against
sag (-25%) and swell (+15%) conditions
Fail-safe, no-break, auto-bypass
Status indicating lights
Shielded, copper wound isolation transformer
Surge protection to ANSI/IEEE and IEC Standards
High efciency (96%) microprocessor controlled
tap switcher
Automatic under voltage protection
• UL1012, UL1449-2, CULUS Listed
• Two Year Limited Warranty
Related Products
STV 100K
• Isolation Transformers
Applications
Automatic Packaging Machinery
• Large Machine Tool Equipment
UPS Bypass Circuits
Retail Store
Process Equipment
Mechanical Specifications
Environmental Specifications
Indicators Indicating Lamps: 2 amber (over temperature and
bypass mode), 1 green (regulated output present)
Connections Field wired, terminal blocks
Size
H W D
in 42 28 26
mm 1016 712 661
Safety Agency
Approvals
UL1012 and UL1449-2
cUL (Canadian Standard C22.2 No 125)
Complies with Part 15 Subpart J of
FCC rules for a Class A computing device.
Audible Noise Less than 50 dBA at 3 feet
Ambient Temperature 0° to 40°C Operating,
0° to 80°C Storage
Operating Altitude 10,000 feet without derating
Operating Humidity 95% relative (non-condensing)
Design Style
Electrical Specifications
Power Ratings 20, 30, 50, 75 kVA, Three Phase*
Nominal Voltages See Selection Table
Input Voltage Range -25% to +15% of nominal rated voltage
Output Voltage
Range
Regulated to a max of ± 5% (3% typical) of nominal
voltage with an input voltage range of –25% to +15%.
Response Time Responds to any line variation in <1.5 cycles typical.
Technology
Enhance Voltage Regulation (EVR), Microprocessor
controlled electronic tap switching. 6 taps switched at
zero current crossing with no output interruption.
Operating Frequency 57-63 Hz
Load Power Factor No Restriction
Insulation
Resistance
100 megohms from winding to core
measured at 500 Vdc
Efficiency 96% typical
Overload Capability 1000% of rated load for 1 second
200% of rated load for 1 minute
EMI Less than 0.2 gauss at a distance of 3 ft.
* Contact Technical Services for other ratings.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 47
1
Power Protection and Conditioning
Noise Suppression Performance Specifications
Selection Table
Protection Specifications
Under Voltage
Output voltage will switch to bypass mode
when input is less than 50% of nominal.
Regulated output voltage will be
re-established once input voltage is with
specications.
Short Circuit Protection Input circuit breaker
Over Temperature Protection
Amber lamp indication of over temperature
at approximately 180°C. Unit switches to
by-pass mode until internal temperature is
reduced to specied values.
Common Mode Noise
Attenuation 150 dB at 100 kHz
Normal Mode Noise
Attenuation 65 dB at 100 kHz
Surge Protection Tested to ANSI/IEEE standard C62.41 A&B
Output kVA Catalog Number Vac Input Vac Output Ship Weight (lbs/kg)
208 Vac Input, 208Y/120 Vac Output, 60 Hz
20 63TAA320 208 208Y/120 600/273
30 63TAA330 208 208Y/120 750/341
50 63TAA350 208 208Y/120 950/432
75 63TAA375 208 208Y/120 1200/545
480 Vac Input, 208Y/120 Vac Output, 60 Hz
20 63TCA320 480 208Y/120 600/273
30 63TCA330 480 208Y/120 750/341
50 63TCA350 480 208Y/120 950/432
75 63TCA375 480 208Y/120 1200/545
480 Vac Input, 480Y/277 Vac Output, 60 Hz
20 63TCC320 480 480Y/277 600/273
30 63TCC330 480 480Y/277 750/341
50 63TCC350 480 480Y/277 950/432
75 63TCC375 480 480Y/277 1200/545
600 Vac Input, 208Y/120 Vac Output, 60 Hz
20 63TDA320 600 208Y/120 600/273
30 63TDA330 600 208Y/120 750/341
50 63TDA350 600 208Y/120 950/432
75 63TDA375 600 208Y/120 1200/545
Custom Voltages
240 Vac Input, 240Y/139 Vac Output, 60 Hz
480 Vac Input, 240Y/139 Vac Output, 60 Hz
600 Vac Input, 240Y/139 Vac Output, 60 Hz
Contact Technical Services for custom voltages.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
48
1Notes