Bussmann(R) Disconnect Switches Page Selection Guide Fusible Non-Fusible Handles Disconnect Switches Fusible (30-800A) Features Components Accessories Non-Fusible (16-3150A) Features Components Accessories Mounting Depths (Compact Disconnect) Technical Data Fusible Non-Fusible Auxiliary Contact Timing Diagrams Approximate Dimensions Fusible Non-Fusible Handles Transfer & Bypass Switches 2 3 4 5-6 7 8 9 10-14 15 16 17-18 19-20 21-27 28-29 30-34 35 36-40 Get the latest, most up-to-date specification data on products listed in this catalog by calling Bussmann Information Fax. Bussmann Information Fax ~ 314.527.1450 Bussmann Worldwide Web ~ BIF is a simple to use automated fax response system. No need to wait for normal business hours; BIF is available around the clock for your convenience. All you need is a touch-tone telephone and a fax machine to get specification data when you want it. A BIF document number is indicated with each product in this catalog. To get a detailed specification sheet simply call 314-527-1450 and follow the prompts. In a matter of minutes, a data sheet will be faxed to you. It's that simple! http://www.bussmann.com (c) 1997 Cooper Industries, Inc. Bussmann Division Printed in U.S.A. 1 Bussmann (R) Worldwide Circuit Protection Solutions North America's leading supplier of fuses and fusible protection systems, Bussmann continues its 80-year history of blazing new trails of innovative technologies. Maker of the industry's first truly global product line, each item is backed by an efficient worldwide network of distribution, customer service and technical support. Bussmann products include the most extensive circuit protection solutions approved for use in a variety of major standards: UL, CSA, IEC. . . Not to mention both European (DIN, British Standard) and North American styled fuses for a wide range of applications: industrial motor protection, power conversion, medium voltage, power distribution, telecommunications network equipment, electronics, and automotive. Manufacturing operations in the U.S., Denmark, and the United Kingdom have earned ISO 9000 certification. Bussmann customers are assured of only the utmost quality across every product line. Knowledgeable. Responsive. Customer focused. Bussmann continues to set the standard for circuit protection solutions around the world. This catalog is intended to present product data and provide technical information that will help the end user with design application. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this catalog. Once a product has been selected, it should be tested by the user in all possible applications. (c)1997 Cooper Industries, Bussmann Division Printed in the U.S.A. Headquarters Cooper Industries Bussmann Division P.O. Box 14460 St. Louis, Missouri 63178-4460, USA Telephone: 314 394 2877 Facsimile: 800 544 2570 Bussmann Circuit Components 7300 West Wilson Avenue Chicago, IL 60656-4793, USA Telephone: 708 867 4600 Facsimile: 708 867 2211 European Headquarters Bussmann Division Cooper (U.K.) Limited Burton-on-the-Wolds Leicestershire LE12 5th, England Telephone: 44 1509 882737 Facsimile: 44 1509 882786 Bussmann Asia Pacific 331 North Bridge Road #03-02 Odeon Towers Singapore 188720 Republic of Singapore Telephone: 65 336 3610 Facsimile: 65 336 4810 Bussmann Australia Dock 5, Block X 391 Park Road P.O. Box 257 Regents Park, Sydney NSW 2143, Australia Telephone: 61 2 9743 8333 Facsimile: 61 2 9743 8070 Bussmann Brasil Bussmann do Brasil Ltda. Rodovia Santos Dumont, Km 23 Cruz das Almas Itu-Sao Paulo 13 300-000 Brasil Telephone: 55 11 7824 1856 Facsimile: 55 11 7824 1721 (c) Cooper Industries, Bussmann Division, Printed in U.S.A. Form No. BDS.1197 Bussmann Denmark 5 Literbuen DK-2740 Skovlunde Copenhagen, Denmark Telephone: 45 4485 0900 Facsimile: 45 4485 0901 Bussmann France Tour Mattei 207 Rue de Bercy 75587 Paris Cedex 12 France Telephone: 33 1 4475 0033 Facsimile: 33 1 4475 0420 Bussmann Germany Frankfurter Landstrasse 19 64546 Morfelden Germany Telephone: 49 6105 951509 Facsimile: 49 6105 951510 Bussmann India 2nd Floor, Unit #5 White House 23-29, St. Marks Road Bangalore - 560-001 India Telephone: 91 80 227 0893 Facsimile: 91 80 224 0124 Bussmann Mexico Arrow-Hart S.A. de C.V. Poniente 148, No. 933 02300 Mexico, D.F. Mexico Telephone: 52 5 587 0211 Facsimile: 52 5 567 4049 Bussmann (R) Disconnect Switches Contents Next Disconnect Switches Bussmann(R) Fusible Selection Guide 30 60 100 Poles available Ampere Rating 3, 4 2, 3, 4 2, 3, 4 400 600 800 2, 3, 4 3 Pole dimensions (inches) Width Height Depth 4.17 3.94 4.22 6.89 4.22 4.76 Fuse type Line & load fuse isolation J & CC X Auxiliary contacts Terminal shrouds Fuse covers 6 Pole kit Transfer kit Bypass kit Mechanical interlock 200 2, 3, 4 2, 3, 4 2, 3, 4 7.48 5.60 5.12 10.25 9.87 7.28 11.18 12.18 7.79 14.68 14.30 8.86 14.68 14.30 8.86 J X J&T X J&T X J&T X J&T X L X X STD STD X X -- X X STD X X X -- -- X X X X X -- -- X X STD X X X X X X STD X X X X X X STD X X X X X X STD X X X X NEMA 1, 3R, 12 handles Selector Pistol NEMA 4, 4X handles Pistol Metallic Flange-mounted operator X X -- X -- X -- X -- X -- X -- X X -- X X -- X X -- X X X -- X X -- X X -- X X -- U.L. Listed (3 pole) CSA Certified IEC Ratings Marked X X X X X X X X X X X X X X X X X X X X X X X X X X X X Includes terminals. X = Available -- = Not available STD = Standard + Basic Switch (fusible) + Shaft = Handle Complete Device Basic switch catalog numbering system -- fusible devices1, 2 BDCF 30J6 Fusible device BDCF--30A BDF -- 60-100A FD -- 200-800A 1 Shaft and handle must be ordered separately. Terminal lugs need to be ordered separately for 100A and above. 2 2 Fuse type Amp rating Contents Previous Next Bussmann(R) Disconnect Switches Non-Fusible Selection Guide Ampere Rating 16 Frame size Poles available 25 NF16 NF25 3, 4 3, 4 30 40 NF32 3, 4 NF45 3, 4 80 100 175 NF60 NF100 3 3 200 400 NF175 NF200A NF400 2, 3, 4 2, 3, 4 2, 3, 4 600 NF600A 2, 3, 4 800 1200 NF800A NF1200 2, 3, 4 2, 3, 4 1600 2000 3150 NF1600 NF2000 NF3150 2, 3, 4 2, 3, 4 2, 3, 4 3 Pole dimensions (inches) Width 1.4 Height 2.7 Depth 2.2 1.4 2.7 2.2 1.4 2.7 2.2 2.1 3.6 2.8 2.08 3.31 2.92 3.06 3.88 3.12 7.86 8.36 4.55 8.64 8.36 4.55 10.23 11.82 5.13 11.90 11.77 5.13 14.29 19.09 4.92 14.29 19.09 4.92 18.42 25.02 10.66 18.42 25.02 10.66 18.42 25.02 10.66 Visible blades Auxiliary contacts 6 Pole kit Transfer kit Bypass kit Mechanical interlock -- X X X X -- -- X X X X -- -- X X X X -- -- X X X X -- -- X X X X -- -- X X X X -- X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X -- -- -- X X X -- -- -- X X X -- -- -- X Terminal shrouds* X NEMA 1, 3R & 12 handles Selector X Pistol X NEMA 4 & 4X handles Pistol X Metallic -- Flange-mounted operator -- Door mounting kit X Toggle operator X X X X X X X X X X X -- -- -- X X X X X X X X X X -- X -- X -- X -- X -- X -- X -- -- -- -- -- -- X -- -- X X -- -- X X -- -- X X -- -- -- X X -- X -- X X -- -- -- -- X -- -- -- -- X X -- -- -- X X -- -- -- X X -- -- -- X X -- -- -- X -- -- -- X -- -- -- X -- -- X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X -- -- X U.L. Listed (3 pole) CSA Certified IEC Ratings Includes X X X terminals. *Compact switches (16-40A) are touch safe without terminal shrouds, but shrouds can be installed for extra protection. X = Available -- = Not available + Basic Switch + Shaft = Handle Complete Device Basic switch catalog numbering system -- non-fusible devices1, 2 CDNF 30 Non-fusible device CDNF - Compact Size (16-40A) BDNF - Standard Size (80-3150A) Frame size 1 Shaft and handle must be ordered separately. Terminal lugs need to be ordered separately for 100A and above. 2 3 Contents Previous Disconnect Switches Next Bussmann(R) Handles - Fusible and Non-Fusible Defeatable Catalog Number Off/On & O/l Off/On & O/l Off/On & O/l Off/On & O/l Off/On O/l Off/On O/l Off/On O/l Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes No No CDH3S CDH4S CDH5S CDH6S BDH47 BDH48 BDH99 BDH100 BDH102 BDH103 Off/On Off/On Off/On Yes Yes Yes Yes BDH20* Yes BDH50* No BDH57* Off/On Yes Yes BDH53 Grip Length Color (Inches) Style NEMA Type Blk R/Y Blk R/Y Blk R/Y Blk R/Y Blk R/Y Pistol Pistol Pistol Blk Blk Blk -- -- -- -- 3.15 3.15 2.36 2.36 2.36 2.36 3.15 2.36 2.36 200A Pistol 1, 3R, 12 Blk 4.72 200-800A Pistol Pistol Pistol Pistol Metallic 1, 3R, 12 1, 3R, 12 1, 3R, 4, 4X, 12 1, 3R, 4, 4X, 12 1, 3R, 4, 4X, 12 R/Y Blk Blk R/Y Blk 5.71 5.71 5.71 5.71 8.66 O/l Off/On Off/On O/l Off/On Yes Yes Yes Yes Yes Yes Yes No No No BDH11 BDH16 BDH35 BDH36 BDH8 Selector 1 Selector 1 Selector 1, 3R, 12 Selector 1, 3R, 12 Selector 1, 3R, 12 Selector 1, 3R, 12 Pistol 1, 12 Pistol 1, 12 Pistol 1, 3R, 12 Pistol 1, 3R, 12 Pistol 1, 3R, 4, 4X, 12 Pistol 1, 3R, 4, 4X, 12 Blk R/Y Blk R/Y Blk R/Y Blk R/Y Blk R/Y Blk R/Y Pistol Pistol 1, 3R, 12 1, 3R, 4, 4X, 12 Blk Blk -- -- -- -- -- -- 3.15 3.15 2.36 2.36 2.36 2.36 No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No Yes Yes Yes Yes Yes Yes No No CDH1S CDH2S CDH3S CDH4S CDH5S CDH6S BDH47 BDH48 BDH99 BDH100 BDH102 BDH103 3.15 3.15 Off/On Off/On Yes Yes Yes BDH64 No BDH67 Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53 Yes Yes Yes Yes Yes No Yes No BDH16 BDH35 BDH11 BDH36 Yes No BDH8 175-200A 400A 400-1200A Pistol Pistol Pistol Pistol 1, 3R, 12 1, 3R, 4, 4X, 12 1, 3R, 12 1, 3R, 4, 4X, 12 Blk Blk R/Y R/Y Metallic 1, 3R, 4, 4X, 12 Blk 5.71 5.71 5.71 5.71 Off/On Off/On O/l O/l 400-3150A *Consult factory for red, yellow, "O/l". 4 Off/On & O/l Off/On & O/l Off/On & O/l Off/On & O/l Off/On & O/l Off/On & O/l Off/On O/l Off/On O/l Off/On O/l 16-100A 60-100A 1, 12 1, 3R, 12 1, 3R, 4, 4X, 12 Catalog Number Grip Length Color (Inches) 30A Selector 1, 3R, 12 Selector 1, 3R, 12 Selector 1, 3R, 12 Selector 1, 3R, 12 Pistol 1, 12 Pistol 1, 12 Pistol 1, 3R, 12 Pistol 1, 3R, 12 Pistol 1, 3R, 4, 4X, 12 Pistol 1, 3R, 4, 4X, 12 Marking Defeatable Marking Padlockable Style NEMA Type Padlockable Handles for Non-Fusible Switches Handles for Fusible Switches 8.66 Off/On Contents Previous Next Bussmann(R) Disconnect Switches Fusible Disconnect Switches 30-800 Amps Features: * Compact, space saving design * Complete line of fusible disconnect switches 30A through 800A * J fusible switches (30-600A) * T fusible switches (100-600A) * L fusible switch (800A) * Rotary and variable-depth handle mechanisms for throughthe-door operation * NEMA rated handles 1, 3R, 4, 4X & 12 * Handles are lockable with three padlocks * NEMA 1, 3R, 4 & 12 flange-mounted operators (30-100A) * Type 1, 3R, 4 & 12 flange-mounted operators include interlock defeater for emergency maintenance purpose * NEMA 1, 3R & 12 handles are defeatable in "ON" position * 30-800A double break contacts * Auxiliary contacts * Terminal shrouds and fuse covers available for "touch-safe" protection More about the Compact 30A: * Compact size (2 narrower than present 30A fusible switch) * J & CC class fuse clips * DIN rail mounting * Fuseholder cannot be removed under load * Finger-protected fuse holder * Rotary and variable depth handle mechanism for throughthe-door operation * NEMA rated handles 1, 3R, 4, 4X & 12 * Test position handle permits the operation of the auxiliary contacts without main contacts being closed. The door can be opened in handle test position * Auxiliary contacts (up to eight auxiliary contacts, including two auxiliary contacts/test contacts which are mounted in the body of the switch) Agency Approvals: U.L. Listed & CSA Certified (2 Pole & 3 Pole): U.L. 98 (CSA 22.2 No. 4): Suitable for use on service equipment, panel boards, switchboards, industrial control equipment, motor control centers, etc. (30-800A) U.L. File E155129 (30-100A), E155130 (200-800A) CSA File 58077M9 IEC 947-1 5 Contents Previous Disconnect Switches Next Bussmann(R) Fusible Disconnect Switches - 30-800A, 600V Rotary Type Switches (30-800 Amps, 600V)* Maximum Horsepower Rating Amp Fuse Certification/ Catalog* Rating Type 200V 208V 240V 480V 600V Listing Number 3 pole 30 CC 5 7.5 7.5 15 20 CSA, U.L. BDCF30CC6 30 J 5 7.5 7.5 15 20 CSA, U.L. BDCF30J6 15 15 15 30 40 CSA, U.L. BDF60J6 60A J1 100A J1 25 25 30 60 60 CSA, U.L. BDF100JT6 50 50 60 125 150 CSA, U.L. FD200J3 200 J1 1 400 J 100 125 125 250 350 CSA, U.L. FD400J3 600 J1 150 150 200 400 500 CSA, U.L. FD600J3 800 L 200 200 250 500 600 CSA, U.L. FD800L3 Other pole configurations 2 pole 60 J1 15 15 15 30 40 CSA, U.L. BDF60J62 25 25 30 40 50 CSA, U.L. BDF100JT62 100 J1 200 J1 50 50 60 125 150 CSA, U.L. FD200J2 1 100 125 125 250 350 CSA, U.L. FD400J2 400 J 600 J1 150 150 200 400 500 CSA, U.L. FD600J2 800 L 200 200 250 500 600 CSA, U.L. FD800L2 4 pole 30 J 5 7.5 7.5 15 20 IEC BDCF30J64 30 CC 5 7.5 7.5 15 20 IEC BDCF30CC64 1 15 15 15 30 40 IEC BDF60J64 60 J 25 25 30 40 50 IEC BDF100JT64 100 J1 200 J1 50 50 60 125 150 IEC FD200J4 1 400 J 100 125 125 250 350 IEC FD400J4 600 J1 150 150 200 400 500 IEC FD600J4 800 L 200 200 250 500 600 IEC FD800L4 *Catalog number includes switch only. Order handle, shaft and terminal lugs from tables on next page. 1Class J fuses are standard. If a 600V Class T fuse is desired, select the necessary fuse adaptor from the Class T Fuse Adaptor Kit chart below. U.L. Listed & CSA Certified: U.L. 98 (CSA 22.2 No. 4): Suitable for use on service equipment, panel boards, switchboards, industrial control equipment, motor control centers, etc. (30-800A), U.L. File E155129; (30-100A), E155130; (200-800A), Guide WPZX; CSA File 58077M9; IEC 947-1. Description Bussmann fusible disconnect switches allow the user to select the appropriate fuse which best suits the tripping characteristic for the application. The various classes of fuses are described below. Changing the fuse is convenient as the fuse links are isolated on both the line and load side of the fuse. Fuse Classes Class J (LPS) This fuse provides both time-delay for motor loads and a high degree of current-limitation. Suitable for the protection of service entrance equipment, feeder circuits, and branch circuits serving both motor and non-motor loads. Class T (JJS) Suitable for the protection of service entrance equipment, feeder circuits, and branch circuits serving both motor and non-motor loads. Class CC (LP-CC) The Class CC fuse was developed specifically for a growing need in the industry: a compact, space saving branch circuit fuse for motor circuits. CC fuses can be used for protection of motors from to 10HP. A major feature of the CC fuse is that they are current-limiting. 6 BIF Document 1120 1121 1122 -- -- This provides the benefit of protecting downstream components against the damaging thermal and magnetic effects of short-circuit currents. Class CC fuses are branch circuit rated and can be used on branch circuits of electrical distribution systems. Class L (KRP-C) This 100% rated fuse is a high interrupting rating, current-limiting device for the protection of service entrance equipment, feeder circuits and circuit breakers. It may be applied at continuous currents up to its ampere rating. The 4 second minimum time-delay provided allows this fuse to pass normal surges and to coordinate with ground fault relays. Class T Fuse Adaptor Kits for 600V Class J Switches Amp Rating Catalog Number Amp Rating 30A, 600V N/A 200A, 600V Catalog Number 60A, 600V Contact Factory 400A, 600V BDTA4 100A, 600V BDTA1 600A, 600V BDTA6 BDTA2 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. Contents Previous Next Bussmann(R) Disconnect Switches Fusible Disconnect Switch Components Handles - 30A Fusible Style NEMA Type Color Grip Length (Inches) Marking Padlockable Defeatable Catalog Number Yes Yes Yes Yes No No Yes Yes CDH3S CDH4S CDH5S CDH6S Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No BDH47 BDH48 BDH99 BDH100 BDH102 BDH103 BDH4 BDH79* 30 Amps ( 0.20 0.20) Selector Selector Selector Selector 1, 1, 1, 1, Pistol Pistol Pistol Pistol Pistol Pistol Pistol Pistol* 3R, 3R, 3R, 3R, 12 12 12 12 1, 12 1, 12 1, 3R, 12 1, 3R, 12 1, 3R, 4, 4X, 12 1, 3R, 4, 4X, 12 1 1 Blk Red/Yel Blk Red/Yel -- -- -- -- Blk Red/Yel Blk Red/Yel Blk Red/Yel Blk Blk 3.15 3.15 2.36 2.36 2.36 2.36 2.36 2.00 O/l O/l O/l O/l and and and and Off/On Off/On Off/On Off/On Off/On O/l Off/On O/l Off/On O/l Off/On/Test O/I/Test *Mounts directly to switch. No shaft required. Shafts Type Pistol Pistol Pistol 1, 12 1, 3R, 12 1, 3R, 4X, 12 Pistol 1, 3R, 12 Color Marking Mounting Depth** Defeatable NEMA Style Grip Length (Inches) Padlockable Handles - 60-800A Fusible Catalog Number Yes Yes Yes Yes Yes No BDH20 BDH50 BDH57 Yes Yes BDH53 BDH16 60-100 Amps ( 0.24 0.24) Blk Blk Blk 3.15 2.36 2.36 Off/On Off/On Off/On 200 Amps ( 0.47 0.47) Blk 4.72 Off/On 200-800 Amps ( 0.47 0.47) Pistol 1, 3R, 12 Blk 5.71 Off/On Yes Yes Pistol 1, 3R, 4, 4X, 12 Blk 5.71 Off/On Yes No BDH35 Pistol 1, 3R, 12 R/Y 5.71 O/l Yes Yes BDH11 1, 3R, 4, 4X, 12 R/Y 5.71 O/l Yes No BDH36 Metallic 1, 3R, 4, 4X, 12 Pistol Blk 8.66 Off/On Yes No BDH8 Terminal Lug Kits - Kit Includes 6 Lugs Amp Rating 30 & 60 Wire Size Wire Type Kit Catalog Number Lugs come standard with switch 100 #14 - 2/0 Cu/Al BDTL24 200 #6 - 300 kcmil Cu/Al BDTL25 400 #2 - 600 kcmil Cu/Al BDTL26 600 & 800 (2) #2 - 600 kcmil Cu/Al BDTL27 5.5 - 5.7 5.5 - 6.5 5.5 - 7.1 5.5 - 7.5 6.3 - 9.4 9.1 - 12.2 12.2 - 15.4 Shaft Length (inches) Catalog Number 30 Amps ( 0.20 0.20) Selector 3.3 CDS85S 4.1 CDS105S 4.7 CDS120S 5.1 CDS130S 7.1 CDS180S 9.8 CDS250S 13.0 CDS330S 30 Amps ( 0.20 0.20) Pistol 6.89 - 7.48 7.67 - 8.27 11.42 - 12.00 16.72 - 17.32 5.91 6.69 10.43 15.75 BDS150P BDS170 BDS265 BDS400 60-100 Amps ( 0.24 0.24) 5.50 - 8.50 8.00 - 11.00 11.00 - 14.00 13.75 - 16.75 16.54 - 19.69 5.90 8.26 11.41 14.17 16.93 BDS150 BDS210 BDS290 BDS360 BDS430 200-400 Amps ( 0.47 0.47) 7.87 - 12.20 9.05 - 13.38 10.22 - 14.54 12.0 - 16.32 14.78 - 19.10 17.53 - 21.85 20.28 - 24.62 8.66 9.84 11.00 12.78 15.56 18.31 21.06 BDS220 BDS250 BDS280 BDS325 BDS395 BDS465 BDS535 600-800 Amps ( 0.47 0.47) CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 10.04 11.20 12.98 15.76 18.51 21.06 - 12.83 14.00 15.77 18.55 21.30 24.08 9.84 11.00 12.78 15.56 18.31 21.06 BDS250 BDS280 BDS325 BDS395 BDS465 BDS535 **Mounting depth is the distance from the outside of door to the disconnect switch mounting plate. Shaft can be cut to desired length. 7 Contents Previous Disconnect Switches Next Bussmann(R) Fusible Disconnect Switch Accessories & Flange-Mounted Operators Fuse Covers and Terminal Shrouds (line-side) Switch Type Amp Rating Fuse Class 60 100 200 400 600, 800 J J or T J or T J J or L Flange-Operated Switches Voltage Fuse Covers Catalog Number Terminal Shrouds Catalog Number 600V 600V 600V 600V 600V BDFC60J BDFC100 BDFC200* BDFC400* BDFC600* Not Required BDTSF1 BDTSF2 BDTSF4 BDTSF6 *3-pole 30, 200-800 amp fusible switches come with the fuse cover as standard. Terminal shrouds can also be used on the load side. Auxiliary Contacts - 30 Amps Type of Auxiliary Contact Amp Rating Voltage Form C 6 250 Aux. Contact Bracket Aux. Contact (NO) Aux. Contact (NC) Catalog Number BDAUX157 BDAUXB BDAUXCB10 BDAUXCB01 NEMA, A600, P600 Shaft Amp Rating Switch & Mechanism Catalog Number 30 60 100 BDFLCF30J6-F BDFLF60J6-F BDFLF100J6-F and handle must be ordered separately. Flange Switch Handles NEMA Rating Handle 4, 4X 12 BDFNHS4 BDFNHS12 Flange Switch Shafts Length (inches) Shaft Catalog Number 12 17 22.5 Auxiliary Contacts - 60-800 Amps Switch Amp Rating Aux. Contact Amp Rating Voltage 1 NO & 1 NC Catalog Number 2 NO & 2 NC Catalog Number 60 100 200-800 6 6 10 250 250 600 BDAUX7 BDAUX7 BDAUX1 BDAUX8 BDAUX8 BDAUX2 BDFHS12 BDFHS17 BDFHS22 Door Hardware - NEMA 12 Item Catalog Number Safety door latch, 2 point with 69 handle Roller for 3 point latch, add to FH-DHK BDDHK BD3RL Conversion Kits for Combination Switches** Description 30 Amp 60-100 Amp 200-800 Amp Catalog Number Catalog Number Catalog Number 6 Pole BDZW5 BDZW2 BDZW9 Transfer BDZW30 BDZW1 BDZW121 -- -- BDZW13 BDZW4 -- BDZW32 BDZW142 BDZW152 -- -- BDZW95 (2 switches with center OFF position) Bypass (3 switches with center OFF position) Mechanical Interlock (Mechanical interlock of two switches) Shaft Extension Coupler 1Includes metallic handle. 2Distance between center line of shafts: BDZW3 = 11.819; BDZW14 = 9.849; BDZW15 = 19.689. **See page 14 for descriptions of conversion kits. 8 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. Contents Previous Next Bussmann(R) Disconnect Switches Non-Fusible Disconnect Switches 16-3150 Amps Features: * Compact, heavy-duty, space saving design * Complete line of non-fusible disconnect switches 16A through 3150A * Convenient through-the-door operation * Rotary and variable-depth handle mechanisms for throughthe-door operation * NEMA rated handles 1, 3R, 4, 4X & 12 * NEMA 1, 3R & 12 handles are defeatable in "ON" position * Handles available with interlock defeater for emergency maintenance purpose * Handles are lockable with three padlocks * DIN rail mountable switches (16-80A), base and door mountable switches * Snap-on auxiliary contacts, power poles and additional poles * Terminal shrouds available for "touch-safe" protection Agency Approvals: U.L. 508 (CSA 22.2 No. 14): Suitable for use in equipment, machinery, or industrial control panels as a motor controller; and are provided with horsepower and ampere ratings. (16-175A, 3 Pole), (16-40A, 4 Pole) U.L. 98 (CSA 22.2 No. 4): Suitable for use on service equipment, panel boards, switchboards, industrial control equipment, motor control centers, etc. (200-2000A, 2 & 3 Pole), (200-600A, 4 Pole) U.L. File 155129 (16-175A) U.L. File 155130 (200-2000A) CSA File 58077M9 IEC 947-1, 3 9 Contents Previous Disconnect Switches Next Bussmann(R) Compact Disconnect Switches - 16-40A, 600V Select one of each + + Shaft2 Switch Handle Non-Fusible, 16-40A, 600V Base & DIN Rail Mounted Switches (16-40A, 600V) 3 pole1 Maximum Horsepower Rating Amp Rating CDNF45 CDNF32 Terminal Lugs Single Phase Three Phase 120V 240V 200V 240V 480V 600V Wire Size Wire Type Certification/ Listing Catalog Number 16 25 TM 1.5 2 2 3 2 3 7.5 7.5 7.5 10 #18-#8 #18-#8 Cu Cu CSA/U.L. CSA/U.L. CDNF16 CDNF25 30 40 1 2 3 5 5 10 5 10 10 20 15 20 #18-#8 #14-#4 Cu Cu CSA/U.L. CSA/U.L. CDNF32 CDNF45 Selector Handles NEMA Ratings Color Padlockable Defeatable All marked both O/l and OFF/ON 1 Blk 1 R/Y CDH1S CDH6S 1, 1, 1, 1, 3R, 3R, 3R, 3R, 12 12 12 12 Blk R/Y Blk R/Y Catalog Number CDH1S CDH2S * * * * * * CDH3S CDH4S CDH5S CDH6S Pistol Handles BDH47 NEMA Ratings Color 1, 12 Blk 1, 12 R/Y 1, 3R, 12 Blk 1, 3R, 12 R/Y 1, 3R, 4, 4X, 12 Blk 1, 3R, 4, 4X, 12 R/Y Marking Off/On O/l Off/On O/l Off/On O/l Length mm 80 80 60 60 60 60 Padlockable * * * * * * Door Mounted Switches (16-30A, 600V) 3 pole1 Maximum Horsepower Rating Amp Rating 16 25 30 Defeatable * * * * Catalog Number BDH47 BDH48 BDH99 BDH100 BDH102 BDH103 Shafts for use with CDH Selector Handles2 ( M 5 5mm) Length3 inches/mm 3.3/85 4.1/105 4.7/120 5.1/130 7.1/180 9.8/250 13.0/330 Catalog Number CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS330S Shafts for use with Pistol Handles2 ( M 5 5mm) Length3 inches/mm 5.9/150 6.7/170 10.4/265 15.8/400 19.7/500 Catalog Number CDS48P CDS67P CDS49P CDS50P CDS99P Selector Handles for Door Mounted Switches Terminal Lugs Single Phase Three Phase Wire 120V 240V 200V 240V 480V 600V Size TM 1.5 2 2 7.5 7.5 #18-#8 2 3 3 7.5 10 #18-#8 1 3 5 5 10 15 #18-#8 Wire Catalog Type Number Cu CDNF16D Cu CDNF25D Cu CDNF32D NEMA Ratings Color Padlockable All marked both O/l and OFF/ON 1 Blk 1 R/Y 1, 3R, 12 Blk * 1, 3R, 12 R/Y * Defeatable Catalog Number CDH7S CDH8S CDH9S CDH10S Shafts not required with door mounted switches. 1A snap-on fourth pole may be added. See Accessories. mounted switches do not require shafts. 3 For mounting depth please see page 16. 2Door 10 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. Contents Previous Next Bussmann(R) Disconnect Switches Non-Fusible Disconnect Switches - 80-100A, 600V Rotary Type Switches (80-100 Amps, 600V) Maximum Horsepower Rating Single Phase Wire Size For Terminal Lugs Three Phase Amp Rating 120V 200V 240V 200V 208V 240V 480V 600V 80 100 3 5 7.5 10 10 15 15 20 15 20 20 25 40 50 50 60 #14 - #1 #6 - 2/0 Certification/ Listing 3 Pole Catalog Number CSA, U.L. CSA, U.L. BDNF60 BDNF100 Cu Cu Catalog number & price includes switch and lugs only. Order handles and shafts from tables below. Handles 80-100 Amps ( 0.20 0.20) Style NEMA Type Selector Selector Selector Selector Pistol Pistol Pistol Pistol Pistol Pistol 1, 1, 1, 1, 3R, 3R, 3R, 3R, 12 12 12 12 1, 12 1, 12 1, 3R, 12 1, 3R, 12 1, 3R, 4, 4X, 12 1, 3R, 4, 4X, 12 Color Grip Length (Inches) Blk Red/Yel Blk Red/Yel -- -- -- -- Marking Blk Red/Yel Blk Red/Yel Blk Red/Yel 3.15 3.15 2.36 2.36 2.36 2.36 Off/On O/l Off/On O/l Off/On O/l O/l O/l O/l O/l and and and and Padlockable Defeatable Yes Yes Yes Yes No No Yes Yes CDH3S CDH4S CDH5S CDH6S Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No BDH47 BDH48 BDH99 BDH100 BDH102 BDH103 Defeatable Catalog Number No BDH127 Off/On Off/On Off/On Off/On Catalog Number Rotary Handles - Mounted Directly to Switch Switch Type Poles NEMA Type Color Marking 3 1 Blk O/l BDNF60 No Padlockable Yes shaft required Toggle Type Switch (80-100 Amps, 600V) Maximum Horsepower Rating Single Phase Wire Size For Terminal Lugs Three Phase 3 Pole Catalog Number Amp Rating 120V 200V 240V 200V 208V 240V 480V 80 3 7.5 10 15 15 20 40 50 #14 - #1 Cu CSA, U.L. BDNF60T 100 5 10 15 20 20 25 50 60 #6 -2/0 Cu CSA, U.L. BDNF100T Extended Shafts ( 0.20 0.20) For Handle Type NEMA 1, 3R & 12 Selector NEMA 1, 3R, 4, 4X & 12 Pistol Mounting Depth* 4.61 5.39 5.98 6.38 8.35 11.10 14.25 - 5.39 6.18 6.77 7.17 9.13 11.89 15.04 6.89 7.67 11.42 16.72 - 7.48 - 8.27 - 12.00 - 17.32 600V Certification/ Listing Accessories - 80-100 Amps Shaft Length Catalog Number 3.3 4.1 4.7 5.1 7.1 9.8 13 CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS350S 5.91 6.69 10.43 15.75 BDS150P BDS170 BDS265 BDS400 *Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length. Agency Approvals: 40-175 Amps: U.L. 508, File 155129, CSA 22.2 No. 14; 200-800 Amps: U.L. 98, File 155130, CSA 22.2 No. 4, Guide WPZX: CSA File 58077M9; IEC 947-1 Auxiliary Contacts - 80A Switch Amp Rating Auxiliary Contact Amp Rating 80 80 80 Aux. contact base Aux. contact (NO) Aux. contact (NC) Voltage -- NEMA A600, P600 NEMA A600, P600 Catalog Number BDAUXB80 BDAUXCA10 BDAUXCA01 Auxiliary Contacts - 80-100A Switch Amp Rating Aux. Contact Amp Rating Voltage 1 NO & 1 NC Catalog Number 2 NO & 2 NC Catalog Number 80 100 6 6 250 250 BDAUX79 BDAUX52 BDAUX80 BDAUX53 Terminal Shrouds (Line side) Amp Rating Catalog Number 100 BDTS1 Note: Terminal shrouds can also be used on the load side. 11 Contents Previous Disconnect Switches Next Bussmann(R) Non-Fusible Disconnect Switches - 175 -600A, 600V Rotary Type Switches (175-600 Amps, 600V) Maximum Horsepower Rating Amp Rating 200V 208V 240V 480V 600V Certification/ Listing Catalog Number 3 Pole 175 200 400 600 30 60 100 150 30 60 100 150 40 75 125 200 75 150 250 400 100 200 350 500 CSA, CSA, CSA, CSA, U.L. U.L. U.L. U.L. BDNF175A BDNF200A BDNF400 BDNF600A 2 Pole 175 200 400 600 30 60 100 150 30 60 100 150 40 75 125 200 75 150 250 400 100 200 350 500 CSA, CSA, CSA, CSA, U.L. U.L. U.L. U.L. BDNF175A2 BDNF200A2 BDNF4002 BDNF600A2 4 Pole 175 200 400 600 30 60 100 150 30 60 100 150 40 75 125 200 75 150 250 400 100 200 350 500 IEC CSA, U.L. CSA, U.L. CSA, U.L. BDNF175A4 BDNF200A4 BDNF4004 BDNF600A4 Catalog number & price includes switch only. Order handles, shafts and terminal lugs from tables below. Shafts Style Color Length (Inches) Marking Mounting Depth* Defeatable NEMA Type Padlockable Handles Catalog Number Yes No BDH64 BDH67 175-200 Amps ( 0.31 0.31) Pistol Pistol 1, 12 1, 3R, 4, 4X, 12 Blk Blk 3.15 3.15 Off/On Off/On Yes Yes 400 Amps ( 0.47 0.47) Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53 Yes No Yes No No BDH16 BDH35 BDH11 BDH36 BDH8 400-600 Amps ( 0.47 0.47) Pistol 1, 3R, 12 Pistol 1, 3R, 4, 4X, 12 Pistol 1, 3R, 12 Pistol 1, 3R, 4, 4X, 12 Metallic 1, 3R, 4, 4X, 12 Blk Blk R/Y R/Y Blk 5.71 5.71 5.71 5.71 8.66 Off/On Off/On O/l O/l Off/On Yes Yes Yes Yes Yes Terminal Lug Kits - Kit Includes 6 Lugs Amp Rating Wire Size Wire Type Kit Catalog Number 175 & 200 400 600 #6 - 300 kcmil #2 - 600 kcmil (2) #2 - 600 kcmil Cu/Al Cu/Al Cu/Al BDTL25 BDTL26 BDTL27 Shaft Length Catalog Number 175-200 Amps ( 0.31 0.31) 4.72 8.66 12.61 18.91 - 8.66 12.59 16.55 22.85 6.15 6.15 6.49 7.87 9.05 10.22 12.0 14.78 17.53 20.28 - 7.75 10.07 10.82 12.2 13.38 14.54 16.32 19.1 21.85 24.62 5.51 9.45 13.39 19.69 BDS140 BDS240 BDS340 BDS500 400-600 Amps ( 0.47 0.47) 4.21 6.54 7.28 8.66 9.84 11.02 12.80 15.55 18.31 21.06 BDS107 BDS166 BDS185 BDS220 BDS250 BDS280 BDS325 BDS395 BDS465 BDS535 *Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length. Agency Approvals: 40-175 Amps: U.L. 508, File 155129, CSA 22.2 No. 14; 200-800 Amps: U.L. 98, File 155130, CSA 22.2 No. 4 CSA File 58077M9; IEC 947-1 Accessories - 175-600A Terminal Shrouds (Line side) Auxiliary Contacts Switch Amp Rating Aux. Contact Amp Rating Voltage 1 NO & 1 NC Catalog Number 2 NO & 2 NC Catalog Number 175-200 400-600 10 10 600 600 BDAUX12 BDAUX1 BDAUX13 BDAUX2 Amp Rating Catalog Number 175 & 200 400 600 BDTS2 BDTS4 BDTS6A Note: Terminal shrouds can also be used on the load side. CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 12 Contents Previous Next Bussmann(R) Disconnect Switches Non-Fusible Disconnect Switches - 800-3150A, 600V Switches (800-3150 Amps, 600V) Maximum Horsepower Rating Amp Rating 200V 208V 240V 480V 600V Certification/ Listing Catalog Number 3 pole 800 1200 1600 2000 3150 200 -- -- -- -- 200 -- -- -- -- 250 -- -- -- -- 500 -- -- -- -- 600 -- -- -- -- CSA/U.L. CSA/U.L. CSA/U.L. CSA/U.L. IEC BDNF800A BDNF1200 BDNF1600 BDNF2000 BDNF31503 Other pole configurations 2 pole 800 1200 1600 2000 3150 200 -- -- -- -- 200 -- -- -- -- 250 -- -- -- -- 500 -- -- -- -- 600 -- -- -- -- CSA/U.L. CSA/U.L. CSA/U.L. CSA/U.L. IEC BDNF800A2 BDNF12002 BDNF16002 BDNF20002 BDNF31502 4 pole 800 1200 1600 2000 3150 200 -- -- -- -- 200 -- -- -- -- 250 -- -- -- -- 500 -- -- -- -- 600 -- -- -- -- IEC IEC IEC IEC IEC BDNF800A4 BDNF12004 BDNF16004 BDNF20004 BDNF31504 NEMA Shafts Color Length Marking Defeatable Handles - all padlockable Mounting Depth1 Catalog Number 800-3150 Amps ( 0.47 0.47) Pistol 1, 3R, 12 1, 3R, 12 1, 3R, 4, 4X, 12 1, 3R, 4, 4X, 12 Metallic 1, 3R, 4, 4X, 12 Blk R/Y Blk R/Y 5.71 5.71 5.71 5.71 Off/On O/l Off/On O/l Blk 8.66 Off/On * * BDH16 BDH11 BDH35 BDH36 BDH8 Terminal Lug Kits - Kit Includes 6 Lugs Amp Rating 800 1200 1600 2000 3150 Wire Size (2) (4) (4) (8) (8) #2 #2 #2 #2 #2 - 600 600 600 600 600 kcmil kcmil kcmil kcmil kcmil Wire Type Kit Catalog Number Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al BDTL30 BDTL28 BDTL28 BDTL28/2 BDTL28/2 Accessories - 800-3150 Amps Auxiliary Contacts Switch Amp Rating Aux. Contact Amp Rating Voltage 800-3150 10 600 1 NO & 1 NC Cat. No. 2 NO & 2 NC Cat. No. BDAUX1 BDAUX2 Terminal Shrouds (Line side) Amp Rating Catalog Number 800 1200 BDTS8A BDTS12 Shaft Length Catalog Number 800-1200 Amps ( 0.47 0.47) 7.4 7.4 7.9 9.3 10.4 11.6 13.7 16.2 18.9 21.7 - 8.6 10.9 11.6 13.0 14.2 15.3 17.1 19.9 22.6 25.4 4.2 6.5 7.3 8.7 9.8 11.0 12.8 15.6 18.3 21.1 BDS107 BDS166 BDS185 BDS220 BDS250 BDS280 BDS325 BDS395 BDS465 BDS535 1600-3150 Amps ( 0.47 0.47) 13.37 16.15 18.9 21.65 - 23.1 23.8 26.6 29.3 12.8 15.6 18.3 21.1 BDS325 BDS395 BDS465 BDS535 1Mounting depth is the distance from the outside of door to the disconnect switch mounting plate. Shaft can be cut to desired length. Agency Approvals: U.L. 98 U.L. File E101914, Guide WPZX CSA File LR58077, LR58247 IEC 947-1 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 13 Contents Previous Disconnect Switches Next Bussmann(R) Flange-Operated, Non-Fusible Disconnect Switches 30-200A, 600V Flange-Operated Switch Flange-Operated Switches1 Shafts Amperage Rating 30 60 100 175 200 1Contact Switch & Mechanism Catalog Number BDFLNF30F BDFLNF60F BDFLNF100F BDFLNF175F BDFLNF200AF Length (Inches) 12 17 22.5 Door Hardware - NEMA 12 Item Safety door latch, 2 point with 69 handle. Roller for 3 point latch, add to FHDHK Bussmann for additional information. Handles NEMA Type 1, 3R, 4, 4X, 12 1, 3R, 12 Shaft Catalog Number BDFHS12 BDFHS17 BDFHS22 Handle Catalog Number BDFHNHS4 BDFHNHS12 Catalog Number BDDHK BD3RL CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. Conversion Kits - 16-3150A, 600V Conversion Kits for Combination Switches Catalog Numbers Description 6 pole Transfer (2 switches with center OFF position) Bypass (3 switches with center OFF position) CDZW8 16 - 100A 175 - 200A CDZW8 BDZW18 BDZW9 CDZW6 BDZW20 BDZW121 CDZW17 BDZW21 BDZW13 -- Mechanical Interlock 400 - 1200A 1600 - 3150A -- -- (Mechanical interlock of two switches) -- BDZW19 BDZW32 BDZW142 BDZW152 BDZW152 Shaft Extension Coupler -- -- BDZW95 BDZW95 1Includes metallic handle. 2Distance between center line of shafts: BDZW3 - 11.819; BDZW14 - 9.849; BDZW15 - 19.689. CDZW6 Conversion kit descriptions 6 Pole This conversion kit, in conjunction with two standard 3 pole switches, allows the switches to open or close simultaneously. Handle is not included. Bypass (three standard switches with center OFF position) This conversion kit operates three switches: Two switches in parallel and one changeover switch to allow power bypass. A 3 position handle is included. Switch Size Handle Part Number 16-100A BDH37 175-1200A BDH6 NEMA 1 & 12 only Mechanical interlock of two standard switches This conversion kit prevents one switch from closing when the other switch is in the ON position. Handle is not included. Transfer (two standard switches with center OFF position) This conversion kit, in conjunction with two 3 pole switches, manually transfers power from one switch to another with a center OFF position. A 3 position handle is included. Switch Size 16-100A 175-1200A Handle Part Number BDH37 NEMA 1 & 12 only BDH21 CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 14 Contents Previous Next Bussmann(R) Disconnect Switches Compact Disconnect Switches - Accessories Non-Fusible, 16-40A, 600V Auxiliary Contacts - Snap-On Mounting CDAUX10 For Switches Description Amps Volts Catalog Number CDNF16...45 1 NO Mounts on right hand side of switch (2 max.) 10 600 CDAUX10 CDNF16...45 1 NC Mounts on left hand side of switch (2 max.) 10 600 CDAUX01 CDAUX01 * Only one power pole per switch * Mounts on left or right side of switch CDS32P CDS63P I O I ON O Power Poles - Snap-On Mounting1 For Switches Fourth Pole CDNF16...32 CDNF16...32D CDNF45 Late-Break/Early Make CDNF16...32 CDNF16...32D (R) (R) Catalog Number CDS32P CDS32D CDS63P CDL32P CDL32D berg Strom IEC 947-3 AC-22A Ith 16A AC-23A 0Hz 50...6 Ue/V Ie/A Ie/A 415 16 14 500 690 16 16 14 12 Auxiliary Contacts Mounted on CDNF32 and CDNF45 Switches Additional Poles - Snap-On Mounting1 * Switch accepts one additional pole per side * Mounts on left or right side of switch For Switches Solid Neutral CDNF16...32 CDNF16...32D Manually Operated Neutral CDNF16...32 CDNF16...32D Ground Terminal CDNF16...32 CDNF16...32D Catalog Number CDN32P CDN32D CDD32P CDD32D CDE32P CDE32D Terminal Shrouds - Snap-On Mounting2 CDTS32T3 CDTS63T3 For Switches For 3-Pole Switches CDNF16...32 CDNF45 For Single Pole CDAUX32P CDAUX63P Catalog Number CDTS32T3 CDTS63T3 CDTS32T1 CDTS63T1 Bypass (three standard switches with center OFF position) This conversion kit operates three switches: Two switches in parallel and one changeover switch to allow power bypass. A 3 position handle is included, (NEMA 1 & 12 only.) Conversion Kits for Combination Switches2 Description 6 Pole Transfer (2 switches with center OFF position) Bypass CDZW8 (3 switches with center OFF position) Catalog Number CDZW83 CDZW64 CDZW174 Transfer (two standard switches with center OFF position) 6 Pole This conversion kit, in conjunction with two standard 3 pole switches, allows the switches to open or close simultaneously. Handle is not included. This conversion kit, in conjunction with two 3 pole switches, manually transfers power from one switch to another with a center OFF position. A 3 position handle is included. (NEMA 1 & 12 only). CDZW6 1 Switch accepts one power pole or one additional pole per side. Only one power pole per switch. Switches are not included. 3 One shaft is included. 4 Shafts included. CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 2 15 Contents Previous Disconnect Switches Next Bussmann(R) Compact Disconnect Switches - Mounting Depths Non-Fusible, 16-40A, 600V Shaft Catalog Number Shaft Length Inches/mm CDH1S & CDH2S CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS330S 3.3/85 4.1/105 4.7/120 5.1/130 7.1/180 9.8/250 13.0/330 4.2 5.0 5.6 6.0 7.9 10.7 13.8 CDNF16-32 CDH3S-6S CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS330S 3.3/85 4.1/105 4.7/120 5.1/130 7.1/180 9.8/250 13.0/330 CDNF16-32 Pistol CDS48P CDS67P CDS49P CDS50P Switch Sizes Handles Mounting Depth Inches 5 3.6 - 4.3 4.4 - 5.1 5.0 - 5.7 5.4 - 6.1 7.4 - 8.1 10.1 - 10.8 13.3 - 14.0 92 - 110 112 - 130 127 - 145 137 - 155 187 - 205 257 - 275 337 - 355 5 5.9/150 6.7/170 10.4/265 15.8/400 6.2 7.0 10.7 16.0 - - - - 6.7 7.5 11.3 16.6 157 177 272 407 - - - - 171 191 286 421 5 CDH1S & CDH2S CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS330S 3.3/85 4.1/105 4.7/120 5.1/130 7.1/180 9.8/250 13.0/330 4.9 5.7 6.3 6.7 8.6 11.4 14.6 - - - - - - - 5.6 6.4 7.0 7.4 9.4 12.1 15.3 124.5 144.5 159.5 169.5 219.5 289.5 369.5 - - - - - - - 142.5 162.5 177.5 187.5 237.5 307.5 387.5 5 CDNF45 CDH3S-6S CDS85S CDS105S CDS120S CDS130S CDS180S CDS250S CDS330S 3.3/85 4.1/105 4.7/120 5.1/130 7.1/180 9.8/250 13.0/330 4.4 5.1 5.7 6.1 8.1 10.9 14.0 - - - - - - - 5.0 5.8 6.4 6.8 8.7 11.5 14.7 110.5 130.5 145.5 155.5 205.5 275.5 355.5 - - - - - - - 126.5 146.5 161.5 171.5 221.5 291.5 371.5 5 CDNF45 Pistol CDS48P CDS67P CDS49P CDS50P 5.9/150 6.7/170 10.4/265 15.8/400 6.9 7.7 11.4 16.7 - - - - 7.4 8.1 11.9 17.2 175 195 290 425 - - - - 187 207 302 437 5 CDNF45 5.0 5.8 6.4 6.7 8.7 11.5 14.6 106 126 141 151 201 271 351 - - - - - - - Shaft Dimensions M mm 126 146 161 171 221 291 371 CDNF16-32 - - - - - - - Mounting Depth mm IEC Utilization Categories Nature of Current Utilization Category Typical Applications Frequent Operation Infrequent Operation AC-20A AC-21A AC-22A AC-23A AC-20B AC-21B AC-22B AC-23B * Connecting and disconnecting under no-load conditions * Switching of resistive loads including moderate overloads * Switching of mixed resistive and inductive loads, including moderate overloads * Switching of motor loads or other highly inductive loads DC-20A DC-21A DC-22A DC-23A DC-20B DC-21B DC-22B DC-23B * Connecting and disconnecting under no-load conditions * Switching of resistive loads including moderate overloads * Switching of mixed resistive and inductive loads, including moderate overloads (e.g., shunt motors) * Switching of highly inductive loads (e.g., series motors) Rated Thermal Current No. Mechanical Operations No. Mechanical Operations 0-50A 10,000 2,000 Alternating Current Direct Current Category AC-23 includes occasional switching of individual motors. The switching of capacitors or tungsten filament lamps shall be subject to agreement between manufacturer and user. 16 Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Fusible, 30-800 Amps U.L. & CSA Ratings Ampere Rating 30 60 100 200 400 600 800 200V 208V 240V 480V 600V -- U.L. 98 -- 100 30 J/T 6,000 10,000 5 7.5 7.5 15 20 U.L. 98 U.L. 98 -- 100 60 J/T 6,000 10,000 15 15 15 30 40 U.L. 98 U.L. 98 -- 100 100 J/T 6,000 8,000 25 25 30 60 60 U.L. 98 U.L. 98 -- 100 200 J/T 6,000 6,000 50 50 60 125 150 U.L. 98 U.L. 98 -- 100 400 J/T 1,000 6,000 100 125 125 250 350 U.L. 98 U.L. 98 -- 100 600 T/L 1,000 6,000 150 150 200 400 500 U.L. 98 U.L. 98 -- 100 800 -- 1,000 -- 200 200 250 500 600 50 Hz, 1 min kV kV A/W A/W A Cu mm2 30 10 12 32/3.5 32/3.5 32 6 60 8 12 63/7.5 63/7.5 7.5 16 100 8 12 125/12 125/12 125 50 200 10 12 250/32 250/23,250/27 315 120 400 10 12 400/45 400/34,360/37 450 240 600 10 12 630/60 600/45,570/50 700 2 x 185 800 10 12 800/65 720/55 900 2 x 240 V up to 500V A 690V A up to 500V A 690V A up to 500V A 690V A 48V A 100/220V A 440V A 500-750V A 1000V A 48V A 100/220V A 440V A 500-750V A 1000V A 48V A 110/220V A 440V A 500-750V A 1000V A 230V kW 400V kW 415V kW 500V kW 690V kW 1,000 32 32 32 32 32 32 32/24 32/2 32/4 -- -- 32/24 32/2 32/4 -- -- 32/24 32/2 32/4 -- -- 8 14 15 18 25 750 63 632 63 632 63 402 -- 63/3 63/4 -- -- -- 63/3 63/4 -- -- -- 63/3 -- -- -- 15 30 30 30 30 750 125 1252 125 1252 125 502 -- 125/3 125/42 -- -- -- 125/3 125/42 -- -- -- 125/3 100/42 -- -- 30 55 55 70 45 1,000 250 250 250 250 250 250 250/2 250/2 250/2 250/3 250/4 250/2 250/2 250/2 250/3 250/4 250/2 250/2 250/2 250/3 -- 70 132 140 170 230 1,000 400 400 400 400 400 400 400/2 400/2 400/2 400/3 400/4 400/2 400/2 400/2 400/3 400/4 400/2 400/2 400/2 400/3 -- 110 210 230 280 330 1,000 630 630 630 630 630 630 630/2 630/2 630/2 630/3 630/4 630/2 630/2 630/2 630/3 630/4 630/2 630/2 630/2 630/3 630/4 180 315 340 400 540 1,000 800 800 800 800 720 720 800/2 800/2 800/2 800/3 800/4 800/2 800/2 800/2 800/3 800/4 800/2 800/2 800/2 800/3 800/4 200 350 380 470 600 2 pole 3 pole 4 pole kA A J/CC U.L. Standard Short-circuit rating with fuse Fuse size Fuse class Electrical endurance Mechanical endurance Maximum Horsepower Ratings IEC Ratings Ampere Rating Dielectric strength Rated impulse withstand voltage Rated thermal current in ambient 40C/in open air Max. fuse power dissipation1 in enclosure In enclosure with solid links With minimum cable cross section Rated operational voltage AC-20 and DC-20 Rated operational current, AC-21A Rated operational current, AC-22A Rated operational current, AC-23A Rated operational current/poles in series DC-21A Rated operational current/poles in series DC-22A Rated operational current/poles in series DC-23A Rated operational power, AC-233 --The kW ratings are accurate for 3-phase 1500 R.P.M. standard asynchronous motors 1Ambient temperature 60C: derating 20%. Mounting on "ceiling": derating 10%. Mounting on wall, horizontal fuses: derating 8%. category B. 3Some fuse links limit these figures further. Starting current characteristics must be considered separately. 4Use 4-pole switches with 2 + 2 parallel contacts in series. LOAD 2Utilization Figure 1 17 Contents Previous Disconnect Switches Next Bussmann(R) Technical Data - Fusible, 30-800 Amps IEC Ratings Ampere Rating Rated breaking capacity in category AC-23 Rated breaking capacity/poles in series in category DC-23 Rated conditional short-circuit current RMS and corresponding max. allowed cut-off current, peak-values --The cut-off currents refer to single phase fuse tests --Fuse selection tables on request Rated short-time withstand current, 1s. Rated capacitor power --The capacitor rating of the switch-fuse is limited by the fuse link Power loss/pole With rated current, without fuse Mechanical endurance Divide by two for operation cycles Fuse types, IEC 269-2 DIN 43620 NFC BS88 -size/distance of fuse link bolts- Weight without accessories 3-pole switch fuses 4-pole switch fuses Built-in terminal size Terminal bolt size Metric thread diameter x length Terminal tightening torque Counter torque required Fuse-links bolts tightening torque Operating torque Typical for 3-pole switch fuses 18 up to 500V A 690V A up to 220V A 400V A 500-750V A 1000V A 80kA, 415V kA 30 256 256 128/2 128/4 -- -- 9 60 504 320 256/3 -- -- -- 12 100 800 405 640/3 400/4 -- -- 23 200 2,000 2,000 1,000/2 1,000/2 1,000/3 -- 40 400 3,200 3,200 1,600/2 1,600/2 1,600/3 -- 40 600 5,760 5,760 3,200/2 3,200/2 3,200/3 3,200/4 75 800 5,760 5,760 3,200/2 3,200/2 3,200/3 3,200/4 75 100kA, 500V kA 7.5 9 17 40 40 75 75 50kA, 690V kA 6 8 14 35 35 60 RMS -value kA 400V kVAr 1 15 2 30 5 50 8 105 10 180 16 250 16 310 415V kVAr 690V kVAr W 15 25 2 32 50 4 55 90 5 115 190 11 200 325 30 270 450 55 340 550 77 mm 20,000 -- 14 x 51 A1.F1 M4/44.5 20,000 00 14 x 51 A2-A3 M5/73 20,000 00 22 x 58 A2-A4AB1-B2 M5/73, M8/94 16,000 0-1 0-1 B1-B4 M8/111 16,000 0-2 0-2 B1-B4 M8/111 10,000 3 3 C1-C2 M10/133, 184 10,000 3 -- C1-C3 M10/133, 184 kg kg Cu mm2 0.7 0.9 0.5...10 1.6 1.9 2.5...25 1.8 2.3 6.9 7.9 7.8 8.8 15.5 19.0 17.0 21.0 M8 x 25 M10 x 40 M10 x 40 M12 x 40 M12 x 40 Oper mm Nm Nm 2 2 5 3.5 15...22 M5:3.5/M8:10 30...44 15 30...44 15 50...75 40 50...75 40 Nm 3 3 5 22 22 28 28 Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Non-Fusible, 16-3150 Amps U.L. & CSA Ratings Ampere Rating U.L. Standard Short-circuit rating with fuse Fuse size Fuse class Short-circuit rating with MCCB Maximum Horsepower Ratings 2 Pole 3 Pole 4 Pole kA A kA 200V 208V 240V 480V 600V Electrical endurance Mechanical endurance 16 -- U.L. 508 U.L. 508 10/5 30 -- 2 2 2 7.5 7.5 6,000 6,000 25 32 -- -- U.L. 508 U.L. 508 U.L. 508 U.L. 508 10/5 10/5 30 30 CC, J, T, RK1/RK5 -- -- 3 5 3 5 3 5 7.5 10 10 15 6,000 6,000 6,000 6,000 40 -- U.L. 508 U.L. 508 10/5 60 80 -- U.L. 508 100 -- U.L. 508 175 -- U.L. 508 400 U.L. 98 U.L. 98 U.L. 98 100 600 RK5 50 100 100 125 250 350 1,000 6,000 600 U.L. 98 U.L. 98 U.L. 98 100 600 RK5 50 150 150 200 400 500 1,000 6,000 800 U.L. 98 U.L. 98 1200 U.L. 98 U.L. 98 1600 U.L. 98 U.L. 98 2000 U.L. 98 U.L. 98 100 200 J 25 30 30 40 75 100 6,000 6,000 200 U.L. 98 U.L. 98 U.L. 98 100 200 RK5 25 60 60 75 150 200 6,000 8,000 10 110 -- 10 10 10 20 20 6,000 6,000 -- 15 15 20 40 50 6,000 6,000 100 110 H or K -- 20 20 25 50 60 6,000 6,000 100 1,200 RK5 50 200 200 250 500 600 1,000 6,000 100 1,200 L 50 -- -- -- -- -- 1,000 6,000 100 2,000 L 65 -- -- -- -- -- 1,000 6,000 100 2,000 L 65 -- -- -- -- -- 1,000 6,000 3150 L -- IEC Ratings sets of parallel poles in series (Figure 1) 2Three poles in series (Figure 2) 25 32 40 80 100 175 200 400 600 800 1200 1600 2000 3150 750 8 750 8 750 8 750 8 690 8 690 8 1,000 12 1,000 12 1,000 12 1,000 12 1,000 8 1,000 8 1,000 8 1,000 8 1,000 8 25 25 25 32 32 32 40 40 40 50 50 50 100 80 63 125 125 100 250 200 175 350 315 260 630 630 500 800 720 600 1,250 1,250 1,000 1,600 1,600 1,250 2,500 2,300 1,950 3,150 2,600 2,300 3,150 2,600 2,300 16 16 -- 16 16 -- 16 16 8 -- 25 25 -- 25 25 -- 20 20 11 -- 32 32 -- 32 32 -- 23 23 12 -- 45 45 -- 45 45 -- 30 30 20 -- 80 80 -- 80 80 -- 63 45 406 -- 801 125 125 -- 125 80 -- 75 56 356 -- 200 200 200 200 200 200 200 200 200 125 315 315 315 315 315 250 315 315 315 125 630 630 630 630 630 400 630 580 350 200 800 800 -- 800 800 -- 720 600 350 200 1,250 1,250 -- 1,250 -- -- 800 800 -- -- 1,600 1,600 -- 1,600 -- -- 800 800 -- -- 2,5004 2,5004 -- 1,6004 -- -- 8004 8004 -- -- 3,1504 3,1504 -- 3,1504 3,1504 -- 1,6004 -- -- 8004 8004 -- -- 1,6004 -- -- 8004 8004 -- -- 1251 200 315 630 800 1,250 1,600 1,600 1,600 1,600 80 125 200 315 630 800 1,250 1,600 1,600 1,600 1,600 80 -- -- 801 -- -- -- 751 200 200 200 200 315 315 315 315 630 -- -- 630 800 -- -- 800 1,250 -- -- -- 1,600 -- -- -- 1,600 -- -- -- 1,600 -- -- -- 1,600 -- -- -- 80 50 200 315 630 630 -- -- -- -- -- 50 -- -- 801 35 25 -- -- -- -- -- 751 50 -- -- -- 200 200 200 200 200 200 200 200 315 315 315 315 315 315 315 315 400 400 -- -- 630 630 400 -- 500 500 -- -- 800 630 400 -- --7 -- -- -- -- --7 -- -- --7 -- -- -- -- --7 -- -- --7 -- -- -- -- --7 -- -- --7 -- -- -- -- --7 -- -- --7 -- -- -- -- --7 -- -- 3Four 5IEC 4IEC poles in series 947-3, utilization category B, infrequent operation 6Size 408 4 7Available upon request Figure 1 LOAD 1Two 16 LOAD Ampere Rating Rated insulation voltage and operational voltage, AC 20 and DC 20 V Rated impulse withstand voltage kV Rated Thermal Current Ith: AC 20 and DC 20 open A 40C enclosed A 60C enclosed A Rated Operational Currents: AC21A 500V A 690V A 1000V5 A AC22A 500V A 690V A 1000V5 A AC23A 415V A 500V A 690V A 1000V5 A DC21A 48V A 3-poles in series 16-100A 110V A 2-poles in series 175-3150A 220V A 440V2 A 750V3 A DC22A 48V A 3-poles in series 16-100A 110V A 2-poles in series 175-3150A 220V A 440V2 A 750V3 A DC23A 48V A 3-poles in series 16-100A 110V A 2-poles in series 175-3150A 220V2 A 440V3 A 750V3 A Figure 2 19 Contents Previous Disconnect Switches Next Bussmann(R) Technical Data - Non-Fusible, 16-3150 Amps IEC Ratings Ampere Rating Rated operational power 16 25 32 40 80 100 175 200 400 600 800 1200 1600 2000 3150 230V kW AC23 400/415V kW The kW-ratings are accurate 500V kW for three-phase 1500 r.p.m. 690V kW standard asynchronous motors. Short-circuit current with kA back-up fuses of size11 A Rated voltage Ue V/V Rated conditional short-circuit current kA/kA Max. allowed fuse size, type OFAA A/A Max. allowed cut-off current, peak value kA/kA Rated short-circuit making capacity, kA prospective peak value, Icm Rated short-time withstand current, 0.25 kA RMS lcw 1.05 kA AC breaking capacity 415V A Pf 0.35 500V A 690V A 1000V11 A DC breaking capacity 48V A L/R = 8ms, 3-poles 110V A in series 220V A 440V A 750V2 A Electrical endurance at rated operational current. pf 0.65 operation cycles Mechanical endurance operations Weight 3-pole lb 4-pole lb Power loss per one pole W Operating torque11 Nm Suitable conductor cross section Cu mm2 3 7.5 7.5 7.5 4 9 9 9 5.5 11 11 11 7.5 15 15 15 18.5 30 30 3012 22 37 37 3012 55 90 132 170 90 160 200 250 180 315 355 355 200 355 400 355 250 400 450 -- 250 400 450 -- 250 400 450 -- 250 400 450 -- 250 400 450 -- 50 25 415 50 16 4 50 32 415 50 32 4.3 50 40 415 50 40 4.6 50 50 415 50 50 5.5 50 100 415/690 10/18 100/63 5.8/5.5 50 125 500/690 10/10 80/63 4.2/5.6 100 400 500/690 100/50 400 30 100 400 500/690 100/50 400 30 80 150 630 800 500/690 100/50 80013 62 80 800 500/690 100/50 80013 62 50 1,000 690 45 -- -- 50 8 1,250 690 45 -- -- 50 5 1,250 690 50 -- -- 50 5 1,250 690 50 -- -- 50 5 1,250 690 50 -- -- 1 1 1 1 2.7 3.6 35/35 35 80 80 95 95 115 115 115 1 1 1 1 1.5 1.5 2.5 2.5 17 8 17 8 38 17 38 17 45 33 45 33 50 37 50 37 50 37 128 128 54 -- 160 160 88 -- 184 184 96 -- 240 240 150 -- 510 400 320 -- 600 450 280 -- 1,600 1,600 1,600 1,000 2,520 2,520 2,520 1,000 5,760 4,800 2,800 1,200 5,780 4,800 2,5006 1,200 6,400 6,400 2,5006 -- 6,400 6,400 4,80010 -- 6,400 6,400 4,80010 -- 6,400 6,400 -- -- 6,400 6,400 -- -- 325 5504 2154 304 -- -- 300 200 -- -- 1,2609 1,2609 1,2601 1,260 1,2603 1,2609 1,2609 1,2601 1,260 1,2603 -- -- 1,6001 1,600 -- -- -- 2,0001 2,000 -- -- -- 1,9001,4 -- -- -- -- 2,6001,4 -- -- -- -- 2,6001,4 -- -- 1Two poles in series 2Three poles in series (Figure 2) poles in series 4L/R = 2.5 ms 3Four circuit breaker, time-delay 1 sec. max. 3,000 3,000 3,000 3,000 1,500 1,500 1,000 1,000 1,000 500 500 500 1007 1007 1007 20,000 .24 .33 .3 1 20,000 .24 .33 .6 1 20,000 .24 .33 1.0 1 20,000 .60 .77 1.4 1.2 20,000 .66 .72 7 2.0 16,000 .99 1.38 7 1.6 16,000 6.17 7.93 3.5 8.2 16,000 13.66 7.93 8.5 8.2 10,000 13.33 16.75 22 21 10,000 35.93 16.75 40 21 10,000 38.58 45.19 40 21 10,000 143 49.60 67 21 6,000 143 165 90 50 6,000 143 165 140 50 6,000 143 165 140 50 .75...10 .75...10 1.5...25 1.5...35 10...70 8 x 25 10 x 30 12 x 40 12 x 40 12 x 60 12 x 60 12 x 60 12 x 60 12 x 60 .75...10 6Pf 0.95 9One 7IEC 947-3, utilization category B, infrequent operation 8With circuit breaker, time-delay 0.5 sec. max. (in closed position) pole 10Pf 0.65 408 12Available upon request 11IEC 13Size 4 Figure 1 20 LOAD LOAD 5With -- -- -- -- 2,6001,4 2,6001,4 -- -- -- -- Figure 2 Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Auxiliary Contact Timing Diagrams Fusible - 30 Amps 0 Legend 30 60 90 Main contact ON NO auxiliary contact I NC auxiliary contact OFF closing O 1 opening O 1 O OFF O ON I Contacts closing 1 Main contacts close 2 NO auxiliary contacts close 3 NC auxiliary contacts open Contacts opening 4 Main contacts open 5 NO auxiliary contacts open 6 NC auxiliary contacts close 30 Amps 0 Catalog Number Auxiliary Contact Contact Configuration BDCF30 BDAUX157 BDAUXCB01 BDAUXCB10 1 NO & 1 NC 1 NO 1 NC 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O 0 BDAUX157 30 ON I 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O BDAUXCB01 BDAUXCB10 ON I 21 Contents Previous Disconnect Switches Next Bussmann(R) Technical Data - Auxiliary Contact Timing Diagrams Fusible - 60-100 Amps 60-100 Amps 0 Catalog Numbers Auxiliary Contact Contact Configuration Form C BDF60 & BDF100 BDAUX7 BDAUX8 1 NO & 1 NC 2 NO & 2 NC ON I OFF 22 O Main contact NO auxiliary contact 30 60 90 closing O 1 opening O 1 NC auxiliary contact OFF O ON I Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Auxiliary Contact Timing Diagrams Fusible - 200-800 Amps 200-400 Amps 0 Catalog Numbers Auxiliary Contact Contact Configuration FD200 & FD400 BDAUX1 BDAUX2 1 NO & 1 NC 2 NO & 2 NC 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact ON OFF O I OFF 30 ON I O 600-800 Amps Catalog Numbers Auxiliary Contact Contact Configuration FD600 & FD800 BDAUX1 BDAUX2 1 NO & 1 NC 2 NO & 2 NC 0 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O ON I 23 Contents Previous Disconnect Switches Next Bussmann(R) Technical Data - Auxiliary Contact Timing Diagrams Non-Fusible - 16-40 Amps 0 Legend 30 60 90 Main contact ON NO auxiliary contact I closing O 1 opening O 1 NC auxiliary contact OFF O OFF O ON I Contacts closing 1 Main contacts close 2 NO auxiliary contacts close 3 NC auxiliary contacts open Contacts opening Main contacts open NO auxiliary contacts open 6 NC auxiliary contacts close 4 5 16-30 Amps 0 Catalog Number Auxiliary Contact Contact Configuration CDNF16-32 CDAUX10 CDAUX01 NO NC 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O 40 Amps 0 Catalog Number Auxiliary Contact Contact Configuration CDNF45 CDAUX10 CDAUX01 NO NC ON I 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O 24 ON I Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Auxiliary Contact Timing Diagrams Non-Fusible - 80 Amps 80 Amps 0 Catalog Number Auxiliary Contact Contact Configuration BDNF60 BDAUXCA10 BDAUXCA01 NO NC 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact ON OFF O I OFF 30 ON I O 80 Amps Catalog Number Auxiliary Contact Contact Configuration Form C BDNF60 BDAUX79 BDAUX80 1 NO & 1 NC 2 NO & 2 NC 0 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O ON I 25 Contents Previous Disconnect Switches Next Bussmann(R) Technical Data - Auxiliary Contact Timing Diagrams Non-Fusible - 100-200 Amps 100 Amps Catalog Number Auxiliary Contact Contact Configuration Form C BDNF100 BDAUX52 BDAUX53 1 NO & 1 NC 2 NO & 2 NC 0 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact ON OFF O I OFF ON I O 175-200 Amps Catalog Numbers BDNF175A & BDNF200A Auxiliary Contact BDAUX12 BDAUX13 Contact Configuration 1 NO & 1 NC 2 NO & 2 NC 0 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O 26 ON I Contents Previous Next Bussmann(R) Disconnect Switches Technical Data - Auxiliary Contact Timing Diagrams Non-Fusible - 400-3150 Amps 400-600 Amps 0 Catalog Numbers Auxiliary Contact Contact Configuration BDNF400 & BDNF600A BDAUX1 BDAUX2 1 NO & 1 NC 2 NO & 2 NC 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O ON ON I I OFF O 800-3150 Amps Catalog Numbers BDNF800A through BDNF3150 0 Auxiliary Contact Contact Configuration BDAUX1 BDAUX2 1 NO & 1 NC 2 NO & 2 NC 30 60 90 Main contact NO auxiliary contact closing O 1 opening O 1 NC auxiliary contact OFF O ON I 27 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Fusible 00.00 00.00 Inches Inches 00.00 00.00 Millimeters Millimeters 30 Amps 3.84 97.5 2.75 70.0 0.93 4.10 1.27 104.0 32.5 0.17 23.6 4.3 35mm DIN RAIL 3.66 2.44 93.0 62.0 2.95..3.15 75.0...80.0 3.70 94.0 1.83 46.5 1.52 3.66 38.5 93.0 4.15 2.00 105.5 51.0 60 Amps 0.23 0.27 Dia. 5.9 7.1 74.1 4.74 3.70 120.4 2.36 2.92 60.0 1.18 94.0 30.0 3.19 81.0 .80 1.54 20.3 39.1 1.46 4.85 37.0 123.1 5.57 141.4 6.85 ( 3 POLE ) 8.31 ( 4 POLE ) 2.00 174.0 50.8 211.0 5.50 ... 8.63 140.0 ... 219.0 100 Amps 1.75 2.13 44.4 54.1 0.26 Dia. 6.6 M6 x 1.0 0.23 5.9 0.27 Dia. 6.9 4.76 1.18 3.58 30.0 121.0 6.80 5.61 172.5 91.0 2.36 142.5 60.0 3.90 99.2 2.15 54.6 .79 20.0 130.8 195.5 8.39 213.0 8.78 223.0 28 5.15 7.70 2.01 5.50...8.62 51.0 139.7....219.0 1.14 29.0 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Fusible 00.00 Inches 200 Amps 2.02 0.27 Dia. 0.47 6.8 11.9 1.84 8.88 5.91 46.7 225.5 00.00 Millimeters 51.3 150.1 5.91 150.1 9.87 4.38 250.7 111.2 6.89 175.0 145.0 2.25 0.95 24.1 0.28 57.1 7.1 7.84 1.51 38.3 1.90 7.86 199.6 5.71 48.2 7.24 1.81 0.20 45.9 5.0 183.9 2.40 199.1 9.25 ... 13.58 234.9 ... 344.9 60.9 7.80 (2 Pole) 10.25 (3 Pole) 12.68 (4 Pole) 198.1 400 Amps 322.0 260.3 1.97 0.27 Dia. 11.9 6.8 12.18 50.0 0.47 1.84 309.3 8.62 46.7 218.9 5.25 133.3 5.91 150.1 10.82 274.8 0.28 7.1 2.73 50.0 5.71 194.8 145.0 225.8 1.38 69.3 1.97 8.89 7.67 35.0 8.79 2.40 223.2 70.0 8.43 (2 Pole) 11.19 (3 Pole) 13.94 (4 Pole) 214.1 284.2 0.20 1.77 7.80 5.0 44.9 198.1 9.25 ... 13.58 234.9 ... 344.9 354.0 600 & 800 Amps 1.83 0.35 Dia. 46.4 8.8 0.47 14.30 363.2 10.12 11.9 7.48 3.74 257.0 189.9 95.0 5.97 151.9 12.97 329.4 11.11 9.84 249.9 282.1 5.71 145.0 0.92 2.57 3.55 23.3 65.2 90.1 1.58 12.14 40.1 308.0 11.14 (2 Pole) 14.69 (3 Pole) 18.23 (4 Pole) 282.9 373.1 8.71 0.95 54.1 2.43 60.9 221.2 0.23 1.59 5.8 40.3 10.23 ... 13.78 259.8 ... 350.0 463.0 29 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Non-Fusible, Toggle Type 00.00 Inches 80 Amps 00.00 Millimeters 0.14 1.49 37.8 3.6 1.61 2.98 40.9 75.6 1.49 37.8 1.55 1.77 45.0 2.11 1.87 39.4 53.6 47.5 2.48 63.0 100 Amps 1.96 3.15 50.0 1.81 80.0 46.0 0.59 0.25 15.0 5.79 147.0 6.35 0.15 3.81 3.03 1.96 77.0 1.68 42.6 50.0 1.18 0.10 0.81 30.0 2.5 20.5 2.75 2.34 70.0 3.06 78.0 59.4 3.06 78.0 30 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Compact, Non-Fusible Non-Fusible, 16-40A, 600V 00.00 Inches 00.00 Millimeters Base and DIN rail mounted switches CDNF16, CDNF25, & CDNF32 1.8 .4 0.4 0.4 45 11 11 11 0.6 15 I ON 2.4 2.1 1.4 54 35 2.7 1.4 35 1.5 O 37 60 1.6 40 68 .5 13 5 0.9 22 4.5 1.4 0.4 0.5 11 o.18 35 13 0.4 11 CDNF45 0.4 0.7 2.4 11 0.7 17.5 17.5 61.0 0.6 1.8 15 45 0.5 13 I ON 2.8 1.4 35 1.5 O OFF 72 3.6 37 3.2 2.1 82.5 54 91.5 5 1.7 43.5 0.4 2.1 0.4 4.5 11 52.5 11 o.18 0.7 17 Door mounted switches CDNF16D, CDNF25D, & CDNF32D 1.69 43 1.42 36 1.69 1.42 43 2.13 36 54 o .13 3.2 .43 2.68 .22 68 5.7 11 1.06 27 .21 5.4 1.97(50) 1 2.56 (65) 1.46 1.57 2 37 .12 3 .87 .98 (25) 1 1.36 (34.5) 2 1 CDH7S + CDH8S 2 CDH9S + CDH10S 40 .43 .53 11 13.4 22 1.38 35 .43 11 31 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Non-Fusible 80 Amps L 00.00 Inches 2.02 51.3 0.20 5.08 00.00 Millimeters Auxiliary Switches 0.16 4.0 1.66 42.1 2.75 69.8 3.31 84.0 1.66 42.1 3.15 80.0 1.97 50.0 2.08 52.8 1.69 42.9 2.29 58.1 2.92 74.1 2.92 (2no + 2nc) 74.1 3.34 (4no + 4nc) 84.8 3.55 90.1 1.99 50.5 H 100 Amps 1.89 3.55 48.0 L 90.1 Auxiliary Switches 0.59 1.81 45.9 0.20 14.9 5.0 0.25 6.3 DIMENSION 3.03 0.16 4.0 76.9 1.69 1.97 42.9 2.75 50.0 L 3.88 98.5 HANDLE TYPE PISTOL SELECTOR 3.55 5.91 150.1 H 90.1 6.88 - 7.50 5.50 - 6.12 174.8 - 190.5 139.7 - 155.4 69.8 3.15 80.0 1.18 29.9 0.10 2.5 2.75 69.8 3.06 0.81 2.42 20.5 61.9 3.12 (2no + 2nc) 77.7 79.2 4.33 (4 Pole) 109.9 3.54 (2no + 2nc) 89.9 50.5 89.9 (4no + 4nc) 175 Amps 3.54 (4no + 4nc) 1.99 1.81 1.81 45.9 45.9 H 4.55 8.8 0.27 115.5 0.35 36.0 6.8 6.8 1.42 0.27 0.31 7.8 1.41 35.8 4.32 8.36 4.33 109.7 212.3 7.45 5.37 186.4 136.4 109.9 6.35 3.15 161.2 80.0 24.8 6.21 6.02 (2 Pole) 7.86 (3 Pole) 9.65 (4 Pole) 32 199.6 4.0 10.9 157.7 152.9 0.16 0.43 0.98 245.1 1.99 4.56...8.50 50.5 115.8...215.9 1.26 3.67 93.2 32.0 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Non-Fusible 00.00 Inches 200 Amps 00.00 Millimeters 2.21 2.21 56.1 56.1 4.55 115.5 0.35 8.8 0.27 6.8 6.8 1.42 36.07 0.27 0.31 7.87 1.41 35.8 8.36 4.32 4.33 212.34 109.7 109.9 7.34 186.44 5.37 3.15 136.4 80.0 6.35 161.2 0.16 0.43 0.98 24.8 4.06 10.9 7.00 1.26 3.67 32.0 93.2 177.8 6.42 (2 Pole) 8.64 (3 Pole) 10.82 (4 Pole) 163.0 219.4 274.8 1.99 4.56...8.50 50.5 115.8 ... 215.9 400 Amps 1.97 50.0 0.62 0.27 Dia. 15.7 6.8 0.47 11.9 1.84 46.7 11.82 5.52 300.2 140.2 5.91 150.1 7.31 185.6 10.48 8.55 5.71 217.1 145.0 266.1 0.70 17.7 0.28 2.74 7.1 1.14 1.95 69.6 28.9 7.88 1.58 200.9 40.1 5.08 5.12 44.96 130.05 50.0 7.48 (2 Pole) 10.25 (3 Pole) 12.99 (4 Pole) 189.9 1.77 0.20 325.9 260.3 2.40 7.88 ... 12.19 60.9 200.1 ... 309.6 600 Amps 1.97 0.62 50.0 15.7 0.47 0.27 Dia. 11.9 6.8 1.84 11.77 46.7 298.9 5.91 5.52 150.1 140.2 10.42 264.6 8.55 7.31 185.6 217.1 5.71 145.0 0.28 7.1 0.70 17.7 3.56 1.97 50.0 1.14 90.4 28.9 1.58 0.20 40.1 5.0 9.56 302.2 44.9 130.0 242.8 8.39 (2 Pole) 11.90 (3 Pole) 15.47 (4 Pole) 213.1 1.77 5.12 392.9 2.40 7.88 ... 12.19 60.9 200.1 .. 309.6 33 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Non-Fusible 00.00 Inches 800 Amps 00.00 Millimeters 2.04 0.59 51.8 14.9 0.35 Dia. 8.8 0.47 11.9 19.10 3.74 485.1 95.0 7.48 8.27 189.9 210.0 10.00 14.65 254.0 372.1 5.71 145.0 1.55 39.3 0.96 2.32 3.54 24.3 58.9 89.9 1.97 50.0 11.73 0.35 297.9 8.8 362.2 1.57 11.9 39.8 4.92 124.9 10.75 (2 Pole) 14.29 (3 Pole) 17.83 (4 Pole) 273.0 0.47 452.8 2.40 10.04 ... 12.80 60.9 255.0 ... 325.1 1200 Amps 1.91 0.59 48.5 14.9 0.35 Dia. 8.8 19.09 484.8 0.47 11.9 3.74 8.27 95.0 210.0 7.48 17.71 189.9 449.8 14.65 10.00 372.1 254.0 15.19 5.71 385.8 145.0 1.55 39.3 0.96 2.31 3.55 24.3 58.9 89.9 1.25 0.66 11.73 16.7 0.48 297.9 12.1 10.75 (2 Pole) 14.29 (3 Pole) 17.83 (4 Pole) 2.40 10.04 ... 12.80 273.0 60.9 255.0 ... 325.1 362.9 452.8 1600, 2000, 3150 Amps 0.69 3.94 17.5 100.0 31.7 4.92 124.9 10.67 271.0 6.57 166.8 1.28 32.5 3.43 3.43 87.1 87.1 1.75 1.38 44.4 35.0 0.35 Dia. 25.02 8.8 635.5 0.47 11.9 3.74 23.95 7.48 95.0 189.9 8.35 21.50 600.3 212.0 546.1 21.44 14.65 544.5 372.1 8.66 219.9 1.00 25.4 0.92 2.45 5.47 23.3 62.2 138.9 15.84 0.48 402.3 12.1 12.95 (2 Pole) 18.43 (3 Pole) 23.90 (4 Pole) 328.9 34 468.1 607.0 0.59 4.44 14.9 112.7 3.94 13.38 ... 21.06 100.0 339.8 ... 534.9 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Handles Handles for base & DIN rail mounted switches 00.00 Inches 00.00 Millimeters CDH1S & CDH2S 0.6 1 BDH47 & BDH99 15 25.4 0.3 1.9 6.5 48 0.1 2.54 I ON 2.7 68 O1.6 40.6 30.5 1 O OFF 1.2 25.4 3.2 81 2.0 0.9 50.8 22.8 CDH3S, CDH4S, CDH5S & CDH6S 0.6 1 25.4 15 0.3 1.9 6.5 48 0.1 BDH100, BDH102, BDH103, & BDH104 2.54 I ON 1 O OFF 1.2 O1.6 40.6 30.5 25.4 2.7 68 2.4 61 0.9 22.8 Handles for door mounted switches 2.0 50.8 CDH7S & CDH8S 1 1 25.4 25.4 1.9 0.3 0.1 48 6.5 2.54 Mounting dimensions, pistol handle 1.2 1.6 O40 40.6 30.5 O OFF I ON 1 25.4 0.3 O 7 0.9 22.8 CDH9S & CDH10S 1.3 33 2.6 1 66 25.4 0.1 2.54 0.39 10 45 1.8 45 I ON 2.2 56 1.6 O40.6 O OFF 1 1.6 40.6 25.4 0.9 22.8 35 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Transfer & Bypass Switches Transfer & bypass switches CDZW8 CDZW6 00.00 Inches 00.00 Millimeters 2.84 72.0 1.54 B 39.0 1.77 DIA 2.16 4.57 55.0 116.0 0.20 .71 45.0 5.00 18.0 1.53 11.02 39.0 280.0 1.18 min. + 30.0 Max. 13 steps of 0.59 15.0 A 3.15 80.0 0.20 5.0 0.24 6.0 0.59 15.0 A = 3.54 + 10 steps of 0.59 steps 90.0 15.0 B = 0.32 min.; 2.55 max. 8.0 65.0 CDZW17 2.84 72.0 1.54 2.16 39.0 55.0 1.77 DIA 1.18 30.0 .71 45.0 18.0 1.53 39.0 B 11.02 280.0 0.20 Max. 5.0 3.15 80.0 0.24 A 6.0 0.59 15.0 0.32 ... 2.55 8.0 ... 65.0 0.20 5.0 A = 4.72 + 8 steps of 0.59 120.0 15.0 B = 3.54 + 6 steps of 0.59 90.0 36 15.0 0.59 15.0 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Transfer Switches BDZW1 00.00 Inches 00.00 Millimeters BDZW2 0.47 12.00 2.84 1.57 72.0 1.54 B 39.0 2.16 4.57 55.0 116.0 40.0 1.77 DIA 45.0 7.72 0.71 18.0 0.24 196.0 0.24 6.00 6.00 1.53 4.72 39.0 120.0 A 11.02 280.0 3.15 80.0 Max. 0.24 6.0 0.24 6.0 45.0 0.59 0.59 15.0 15.0 1.77 min. + 13 steps of 0.59 15.0 A = 3.54 + 10 steps of 0.59 steps 90.0 15.0 B = 0.32 min.; 2.55 max. 8.0 65.0 BDZW3 - ZW14 and - ZW15 BDZW4 9.50 241.3 8.74 222.0 4.13 4.60 105.0 116.8 B A Dimensions in Inches & mm A B BDZW3 BDZW14 BDZW15 BDZW19 11.81 300.0 9.84 250.0 19.69 500.0 11.02 280.0 0.47 12.0 0.47 12.0 0.47 12.0 0.31 8.0 4.63 117.5 0.55 14.0 37 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Transfer Switches BDZW5 00.00 Inches 00.00 Millimeters BDZW9 and CDZW9 9.50 241.3 8.74 222.0 4.60 0.47 116.8 12.00 4.13 105.0 0.79 2.36 min. + 19 steps of 0.79 20.0 60.0 4.63 117.5 0.55 14.0 38 15.0 Contents Previous Next Bussmann(R) Disconnect Switches Approximate Dimensions - Transfer Switches BDZW11 BDZW12 3.27 83.0 2.08 1.35 00.00 Inches 00.00 Millimeters 4.84 3.54 2.28 4.84 123.0 90.0 58.0 123.0 53.0 1.57 34.0 40.0 1.30 1.30 33.0 33.0 0.47 0.47 12.0 12.0 3.31 84.0 B 3.31 0.47 84.0 12.0 27.17 690.0 Max. 5.71 145.0 A 20.08 A 8.66 510.0 0.79 20.0 0.79 Max. 220.0 20.0 0.31 ... 0.59 8.0...15.0 0.31 ... 0.59 8.0 ...15.0 B 0.47 12.0 B = BDZW11 = 0.47 12.0 BDZW20 = 0.31 8.0 A = 8.27 + 11 steps of 0.79 210.0 20.0 A = 8.27 + 18 steps of 0.79 210.0 20.0 BDZW13 3.54 2.28 4.4 90.0 58.0 123.0 1.57 40.0 1.30 33.0 0.47 12.0 3.31 0.47 84.0 12.0 A 8.66 220.0 0.79 20.0 27.17 690.0 1.42 ... 1.69 Max. 36.0 ... 43.0 B 0.47 12.0 0.47 12.0 A = 8.27 + 18 steps of 0.79 210.0 20.0 B = 9.84 + 18 steps of 0.79 250.0 20.0 39 Contents Previous Disconnect Switches Next Bussmann(R) Approximate Dimensions - Transfer Switches BDZW18 00.00 Inches 00.00 Millimeters BDZW20 0.47 3.27 12.00 83.0 1.57 4.84 40.0 123.0 2.08 1.35 53.0 34.0 1.30 33.0 6.93 0.47 176.0 0.24 0.24 12.0 8.00 8.00 3.31 84.0 B 3.94 100.0 20.08 510.0 Max. 5.71 145.0 A 0.79 20.0 3.15 0.31 ... 0.59 80.0 8.0 ...15.0 0.59 15.0 3.15 min. + 10 steps of 0.79 15.0 B BDZW21 3.27 4.84 83.0 123.0 1.35 2.08 35.0 53.0 A = 8.27 + 11 steps of 0.79 210.0 1.30 B = BDZW11 = 0.47 12.0 BDZW20 = 0.31 33.0 0.47 8.0 12.0 3.31 84.0 0.31 8.0 B 5.71 145.0 0.79 0.31 20.0 8.0 A 20.0 510.0 0.31 ... 0.59 7.0 ... 43.0 Max. 0.31 8.0 A = 9.84 + 9 steps of 0.79 250.0 20.0 B = 8.27 + 9 steps of 0.79 210.0 40 20.0 20.0 Contents Previous Headquarters Cooper Industries Bussmann Division P.O. Box 14460 St. Louis, Missouri 63178-4460, USA Telephone: 314 394 2877 Facsimile: 800 544 2570 Bussmann Circuit Components 7300 West Wilson Avenue Chicago, IL 60656-4793, USA Telephone: 708 867 4600 Facsimile: 708 867 2211 European Headquarters Bussmann Division Cooper (U.K.) Limited Burton-on-the-Wolds Leicestershire LE12 5th, England Telephone: 44 1509 882737 Facsimile: 44 1509 882786 Bussmann Asia Pacific 331 North Bridge Road #03-02 Odeon Towers Singapore 188720 Republic of Singapore Telephone: 65 336 3610 Facsimile: 65 336 4810 Bussmann Australia Dock 5, Block X 391 Park Road P.O. Box 257 Regents Park, Sydney NSW 2143, Australia Telephone: 61 2 9743 8333 Facsimile: 61 2 9743 8070 Bussmann Brasil Bussmann do Brasil Ltda. Rodovia Santos Dumont, Km 23 Cruz das Almas Itu-Sao Paulo 13 300-000 Brasil Telephone: 55 11 7824 1856 Facsimile: 55 11 7824 1721 (c) Cooper Industries, Bussmann Division, Printed in U.S.A. Form No. BDS.1197 Bussmann Denmark 5 Literbuen DK-2740 Skovlunde Copenhagen, Denmark Telephone: 45 4485 0900 Facsimile: 45 4485 0901 Bussmann France Tour Mattei 207 Rue de Bercy 75587 Paris Cedex 12 France Telephone: 33 1 4475 0033 Facsimile: 33 1 4475 0420 Bussmann Germany Frankfurter Landstrasse 19 64546 Morfelden Germany Telephone: 49 6105 951509 Facsimile: 49 6105 951510 Bussmann India 2nd Floor, Unit #5 White House 23-29, St. Marks Road Bangalore - 560-001 India Telephone: 91 80 227 0893 Facsimile: 91 80 224 0124 Bussmann Mexico Arrow-Hart S.A. de C.V. Poniente 148, No. 933 02300 Mexico, D.F. Mexico Telephone: 52 5 587 0211 Facsimile: 52 5 567 4049 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Cooper Bussmann: BDDHK