Bussmann®
1
Disconnect Switches
Selection Guide
Fusible 2
Non-Fusible 3
Handles 4
Disconnect Switches
Fusible (30-800A)
Features 5-6
Components 7
Accessories 8
Non-Fusible (16-3150A)
Features 9
Components 10-14
Accessories 15
Mounting Depths (Compact Disconnect) 16
Technical Data
Fusible 17-18
Non-Fusible 19-20
Auxiliary Contact Timing Diagrams 21-27
Approximate Dimensions
Fusible 28-29
Non-Fusible 30-34
Handles 35
Transfer & Bypass Switches 36-40
Page
Bussmann
Information Fax ~
314.527.1450
Get the latest, most up-to-date specification data on products
listed in this catalog by calling Bussmann Information Fax.
BIF is a simple to use automated fax response system. No
need to wait for normal business hours; BIF is available around
the clock for your convenience. All you need is a touch-tone
telephone and a fax machine to get specification data when
you want it.
A BIF document number is indicated with each product in
this catalog. To get a detailed specification sheet simply call
314-527-1450 and follow the prompts. In a matter of min-
utes, a data sheet will be faxed to you. It’s that simple!
© 1997 Cooper Industries, Inc. Bussmann Division Printed in U.S.A.
Bussmann
Worldwide Web ~
http://www.bussmann.com
North America’s leading supplier of fuses and fusible protection
systems, Bussmann continues its 80-year history of blazing new
trails of innovative technologies. Maker of the industry’s first
truly global product line, each item is backed by an efficient
worldwide network of distribution, customer service and
technical support. Bussmann products include the most
extensive circuit protection solutions approved for use in
a variety of major standards: UL, CSA, IEC. . . Not to
mention both European (DIN, British Standard) and
North American styled fuses for a wide range of
applications: industrial motor protection, power
conversion, medium voltage, power distribution,
telecommunications network equipment, electronics,
and automotive. Manufacturing operations in the U.S.,
Denmark, and the United Kingdom have earned ISO 9000
certification. Bussmann customers are assured of only
the utmost quality across every product line.
Knowledgeable. Responsive. Customer focused.
Bussmann continues to set the standard for circuit
protection solutions around the world.
Worldwide Circuit Protection Solutions
Bussmann®
This catalog is intended to present product data and provide technical information that will
help the end user with design application. Bussmann reserves the right, without notice,
to change design or construction of any products and to discontinue or limit distribution
of any products. Bussmann also reserves the right to change or update, without notice,
any technical information contained in this catalog. Once a product has been selected, it
should be tested by the user in all possible applications.
©1997 Cooper Industries, Bussmann Division
Printed in the U.S.A.
Bussmann®
Disconnect Switches
Bussmann Denmark
5 Literbuen
DK-2740 Skovlunde
Copenhagen, Denmark
Telephone: 45 4485 0900
Facsimile: 45 4485 0901
Bussmann France
Tour Mattei
207 Rue de Bercy
75587 Paris Cedex 12
France
Telephone: 33 1 4475 0033
Facsimile: 33 1 4475 0420
Bussmann Germany
Frankfurter Landstrasse 19
64546 Mörfelden
Germany
Telephone: 49 6105 951509
Facsimile: 49 6105 951510
Bussmann India
2nd Floor, Unit #5
White House
23-29, St. Marks Road
Bangalore – 560-001
India
Telephone: 91 80 227 0893
Facsimile: 91 80 224 0124
Bussmann Mexico
Arrow-Hart S.A. de C.V.
Poniente 148, No. 933
02300 Mexico, D.F. Mexico
Telephone: 52 5 587 0211
Facsimile: 52 5 567 4049
Headquarters
Cooper Industries
Bussmann Division
P.O. Box 14460
St. Louis, Missouri 63178-4460, USA
Telephone: 314 394 2877
Facsimile: 800 544 2570
Bussmann Circuit Components
7300 West Wilson Avenue
Chicago, IL 60656-4793, USA
Telephone: 708 867 4600
Facsimile: 708 867 2211
European Headquarters
Bussmann Division
Cooper (U.K.) Limited
Burton-on-the-Wolds
Leicestershire LE12 5th, England
Telephone: 44 1509 882737
Facsimile: 44 1509 882786
Bussmann Asia Pacific
331 North Bridge Road
#03-02 Odeon Towers
Singapore 188720
Republic of Singapore
Telephone: 65 336 3610
Facsimile: 65 336 4810
Bussmann Australia
Dock 5, Block X
391 Park Road
P.O. Box 257
Regents Park, Sydney
NSW 2143, Australia
Telephone: 61 2 9743 8333
Facsimile: 61 2 9743 8070
Bussmann Brasil
Bussmann do Brasil Ltda.
Rodovia Santos Dumont, Km 23
Cruz das Almas
Itu-Sao Paulo 13 300-000
Brasil
Telephone: 55 11 7824 1856
Facsimile: 55 11 7824 1721
©Cooper Industries, Bussmann Division, Printed in U.S.A.
Form No. BDS.1197
Bussmann®
2
Disconnect Switches
Fusible Selection Guide
Basic switch catalog numbering system — fusible devices1, 2
BDCF 30J6
Fusible device Fuse type
BDCF—30A
Amp rating
BDF — 60-100A
FD — 200-800A
+ + =
Basic Switch Shaft Handle Complete Device
(fusible)
1Shaft and handle must be ordered separately.
2Terminal lugs need to be ordered separately for 100A and above.
Ampere Rating 30 60 100 200 400 600 800
Poles available 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4
3 Pole dimensions (inches)
Width 4.17 6.89 7.48 10.25 11.18 14.68 14.68
Height 3.94 4.22 5.60 9.87 12.18 14.30 14.30
Depth 4.22 4.76 5.12 7.28 7.79 8.86 8.86
Fuse type J & CC J J & T J & T J & T J & T L
Line & load fuse isolation X X X X X X X
Auxiliary contacts X X X X X X X
Terminal shrouds STD STD X X X X X
Fuse covers STD X X STD STD STD STD
6 Pole kit X X X X X X X
Transfer kit X X X X X X X
Bypass kit X X X X
Mechanical interlock X X X X X
NEMA 1, 3R, 12 handles
Selector X –– –– –– –– –– ––
Pistol X X X X X X X
NEMA 4, 4X handles
Pistol X X X X X X X
Metallic X X X X
Flange-mounted operator X X X
U.L. Listed (3 pole) X X X X X X X
CSA Certified X X X X X X X
IEC Ratings X X X X X X X
Marked X X X X X X X
Includes terminals.
X = Available
= Not available
STD = Standard
Contents
Next
Bussmann®
3
Disconnect Switches
Non-Fusible Selection Guide
Ampere Rating 16 25 30 40 80 100 175 200 400 600 800 1200 1600 2000 3150
Frame size NF16 NF25 NF32 NF45 NF60 NF100 NF175 NF200A NF400 NF600A NF800A NF1200 NF1600 NF2000 NF3150
Poles available 3, 4 3, 4 3, 4 3, 4 3 3 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4
3 Pole dimensions (inches)
Width 1.4 1.4 1.4 2.1 2.08 3.06 7.86 8.64 10.23 11.90 14.29 14.29 18.42 18.42 18.42
Height 2.7 2.7 2.7 3.6 3.31 3.88 8.36 8.36 11.82 11.77 19.09 19.09 25.02 25.02 25.02
Depth 2.2 2.2 2.2 2.8 2.92 3.12 4.55 4.55 5.13 5.13 4.92 4.92 10.66 10.66 10.66
Visible blades X X X X X X X X X
Auxiliary contacts X X X X X X X X X X X X X X X
6 Pole kit X X X X X X X X X X X X
Transfer kit X X X X X X X X X X X X
Bypass kit X X X X X X X X X X X X
Mechanical interlock X X X X X X X X X
Terminal shrouds*X X X X X X X X X X X X
NEMA 1, 3R & 12 handles
Selector X X X X X X
Pistol X X X X X X X X X X X X
NEMA 4 & 4X handles
Pistol X X X X X X X X X X X X
Metallic X X X X X X X
Flange-mounted operator X
Door mounting kit X X X X
Toggle operator X X
U.L. Listed (3 pole) X X X X X X X X X X X X X X
CSA Certified X X X X X X X X X X X X X X
IEC Ratings X X X X X X X X X X X X X X X
Includes terminals.
*Compact switches (16-40A) are touch safe without terminal shrouds, but shrouds can be installed for extra protection.
X = Available
= Not available
Basic switch catalog numbering system — non-fusible devices1, 2
CDNF 30
Non-fusible device Frame size
CDNF - Compact Size (16-40A)
BDNF - Standard Size (80-3150A)
+ + =
Basic Switch Shaft Handle Complete Device
1Shaft and handle must be ordered separately.
2Terminal lugs need to be ordered separately for 100A and above.
Contents
Next
Previous
Bussmann®
4
Disconnect Switches
Handles – Fusible and Non-Fusible
Handles for Non-Fusible Switches
Grip
NEMA Length Catalog
Style Type Color (Inches) Marking Number
16-100A
Selector 1 Blk Off/On & O/l No No CDH1S
Selector 1 R/Y Off/On & O/l No No CDH2S
Selector 1, 3R, 12 Blk Off/On & O/l Yes No CDH3S
Selector 1, 3R, 12 R/Y Off/On & O/l Yes No CDH4S
Selector 1, 3R, 12 Blk Off/On & O/l Yes Yes CDH5S
Selector 1, 3R, 12 R/Y Off/On & O/l Yes Yes CDH6S
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH47
Pistol 1, 12 R/Y 3.15 O/l Yes Yes BDH48
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH99
Pistol 1, 3R, 12 R/Y 2.36 O/l Yes Yes BDH100
Pistol 1, 3R, 4, 4X, 12 Blk 2.36 Off/On Yes No BDH102
Pistol 1, 3R, 4, 4X, 12 R/Y 2.36 O/l Yes No BDH103
175-200A
Pistol 1, 3R, 12 Blk 3.15 Off/On Yes Yes BDH64
Pistol 1, 3R, 4, 4X, 12 Blk 3.15 Off/On Yes No BDH67
400A
Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53
400-1200A
Pistol 1, 3R, 12 Blk 5.71 Off/On Yes Yes BDH16
Pistol 1, 3R, 4, 4X, 12 Blk 5.71 Off/On Yes No BDH35
Pistol 1, 3R, 12 R/Y 5.71 O/l Yes Yes BDH11
Pistol 1, 3R, 4, 4X, 12 R/Y 5.71 O/l Yes No BDH36
400-3150A
Metallic 1, 3R, 4, 4X, 12 Blk 8.66 Off/On Yes No BDH8
Handles for Fusible Switches
Grip
NEMA Length Catalog
Style Type Color (Inches) Marking Number
30A
Selector 1, 3R, 12 Blk Off/On & O/l Yes No CDH3S
Selector 1, 3R, 12 R/Y Off/On & O/l Yes No CDH4S
Selector 1, 3R, 12 Blk Off/On & O/l Yes Yes CDH5S
Selector 1, 3R, 12 R/Y Off/On & O/l Yes Yes CDH6S
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH47
Pistol 1, 12 R/Y 3.15 O/l Yes Yes BDH48
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH99
Pistol 1, 3R, 12 R/Y 2.36 O/l Yes Yes BDH100
Pistol 1, 3R, 4, 4X, 12 Blk 2.36 Off/On Yes No BDH102
Pistol 1, 3R, 4, 4X, 12 R/Y 2.36 O/l Yes No BDH103
60-100A
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH20*
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH50*
Pistol 1, 3R, 4, 4X, 12 Blk 2.36 Off/On Yes No BDH57*
200A
Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53
200-800A
Pistol 1, 3R, 12 R/Y 5.71 O/l Yes Yes BDH11
Pistol 1, 3R, 12 Blk 5.71 Off/On Yes Yes BDH16
Pistol 1, 3R, 4, 4X, 12 Blk 5.71 Off/On Yes No BDH35
Pistol 1, 3R, 4, 4X, 12 R/Y 5.71 O/l Yes No BDH36
Metallic 1, 3R, 4, 4X, 12 Blk 8.66 Off/On Yes No BDH8
*Consult factory for red, yellow, “O/l”.
Padlock-
able
Defeat-
able
Padlock-
able
Defeat-
able
Contents
Previous
Next
Bussmann®
5
Fusible Disconnect Switches
Disconnect Switches
30-800 Amps
Features:
Compact, space saving design
Complete line of fusible disconnect switches 30A
through 800A
J fusible switches (30-600A)
T fusible switches (100-600A)
L fusible switch (800A)
Rotary and variable-depth handle mechanisms for through-
the-door operation
NEMA rated handles 1, 3R, 4, 4X & 12
Handles are lockable with three padlocks
NEMA 1, 3R, 4 & 12 flange-mounted operators (30-100A)
Type 1, 3R, 4 & 12 flange-mounted operators include inter-
lock defeater for emergency maintenance purpose
NEMA 1, 3R & 12 handles are defeatable in “ON” position
30-800A double break contacts
Auxiliary contacts
Terminal shrouds and fuse covers available for “touch-safe”
protection
Agency Approvals:
U.L. Listed & CSA Certified (2 Pole & 3 Pole):
U.L. 98 (CSA 22.2 No. 4): Suitable for use on service
equipment, panel boards, switchboards, industrial control
equipment, motor control centers, etc. (30-800A)
U.L. File E155129 (30-100A), E155130 (200-800A)
CSA File 58077M9
IEC 947-1
More about the Compact 30A:
Compact size (2narrower than present 30A fusible switch)
J & CC class fuse clips
DIN rail mounting
Fuseholder cannot be removed under load
Finger-protected fuse holder
Rotary and variable depth handle mechanism for through-
the-door operation
NEMA rated handles 1, 3R, 4, 4X & 12
Test position handle permits the operation of the auxiliary
contacts without main contacts being closed. The door can
be opened in handle test position
Auxiliary contacts (up to eight auxiliary contacts, including
two auxiliary contacts/test contacts which are mounted in the
body of the switch)
Contents
Previous
Next
Bussmann®
6
Disconnect Switches
Fusible Disconnect Switches – 30-800A, 600V
U.L. Listed & CSA Certified:
U.L. 98 (CSA 22.2 No. 4): Suitable for use on service equipment,
panel boards, switchboards, industrial control equipment, motor con-
trol centers, etc.
(30-800A), U.L. File E155129; (30-100A), E155130; (200-800A), Guide
WPZX; CSA File 58077M9; IEC 947-1.
Description
Bussmann fusible disconnect switches allow the user to select the
appropriate fuse which best suits the tripping characteristic for the
application. The various classes of fuses are described below.
Changing the fuse is convenient as the fuse links are isolated on both
the line and load side of the fuse.
Fuse Classes
Class J (LPS)
This fuse provides both time-delay for motor loads and a high degree
of current-limitation. Suitable for the protection of service entrance
equipment, feeder circuits, and branch circuits serving both motor
and non-motor loads.
Class T (JJS)
Suitable for the protection of service entrance equipment, feeder cir-
cuits, and branch circuits serving both motor and non-motor loads.
Class CC (LP-CC)
The Class CC fuse was developed specifically for a growing need in
the industry: a compact, space saving branch circuit fuse for motor
circuits. CC fuses can be used for protection of motors from ⁄Ω¢ to
10HP. A major feature of the CC fuse is that they are current-limiting.
This provides the benefit of protecting downstream components
against the damaging thermal and magnetic effects of short-circuit
currents. Class CC fuses are branch circuit rated and can be used on
branch circuits of electrical distribution systems.
Class L (KRP-C)
This 100% rated fuse is a high interrupting rating, current-limiting
device for the protection of service entrance equipment, feeder cir-
cuits and circuit breakers. It may be applied at continuous currents
up to its ampere rating. The 4 second minimum time-delay provided
allows this fuse to pass normal surges and to coordinate with ground
fault relays.
Class T Fuse Adaptor Kits for 600V Class J Switches
Amp Rating Catalog Number Amp Rating Catalog Number
30A, 600V N/A 200A, 600V BDTA2
60A, 600V Contact Factory 400A, 600V BDTA4
100A, 600V BDTA1 600A, 600V BDTA6
Rotary Type Switches (30-800 Amps, 600V)*
Amp Fuse Maximum Horsepower Rating Certification/ Catalog*BIF
Rating Type 200V 208V 240V 480V 600V Listing Number Document
3 pole
30 CC 5 7.5 7.5 15 20 CSA, U.L. BDCF30CC6 1120
30 J 5 7.5 7.5 15 20 CSA, U.L. BDCF30J6
60A J115 15 15 30 40 CSA, U.L. BDF60J6 1121
100A J125 25 30 60 60 CSA, U.L. BDF100JT6
200 J150 50 60 125 150 CSA, U.L. FD200J3
400 J1100 125 125 250 350 CSA, U.L. FD400J3
600 J1150 150 200 400 500 CSA, U.L. FD600J3 1122
800 L 200 200 250 500 600 CSA, U.L. FD800L3
Other pole configurations
2 pole
60 J115 15 15 30 40 CSA, U.L. BDF60J62
100 J125 25 30 40 50 CSA, U.L. BDF100JT62
200 J150 50 60 125 150 CSA, U.L. FD200J2
400 J1100 125 125 250 350 CSA, U.L. FD400J2
600 J1150 150 200 400 500 CSA, U.L. FD600J2
800 L 200 200 250 500 600 CSA, U.L. FD800L2
4 pole
30 J 5 7.5 7.5 15 20 IEC BDCF30J64
30 CC 5 7.5 7.5 15 20 IEC BDCF30CC64
60 J115 15 15 30 40 IEC BDF60J64
100 J125 25 30 40 50 IEC BDF100JT64
200 J150 50 60 125 150 IEC FD200J4
400 J1100 125 125 250 350 IEC FD400J4
600 J1150 150 200 400 500 IEC FD600J4
800 L 200 200 250 500 600 IEC FD800L4
*Catalog number includes switch only. Order handle, shaft and terminal lugs from tables on next page.
1Class J fuses are standard. If a 600V Class T fuse is desired, select the necessary fuse adaptor from the Class T Fuse Adaptor Kit chart below.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Contents
Previous
Next
Handles – 30A Fusible
Style NEMA Type Color Grip Length (Inches) Marking Padlockable Defeatable Catalog Number
30 Amps ( 0.20∑ ≈ 0.20∑)
Selector 1, 3R, 12 Blk O/l and Off/On Yes No CDH3S
Selector 1, 3R, 12 Red/Yel O/l and Off/On Yes No CDH4S
Selector 1, 3R, 12 Blk O/l and Off/On Yes Yes CDH5S
Selector 1, 3R, 12 Red/Yel O/l and Off/On Yes Yes CDH6S
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH47
Pistol 1, 12 Red/Yel 3.15 O/l Yes Yes BDH48
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH99
Pistol 1, 3R, 12 Red/Yel 2.36 O/l Yes Yes BDH100
Pistol 1, 3R, 4, 4X, 12 Blk 2.36 Off/On Yes No BDH102
Pistol 1, 3R, 4, 4X, 12 Red/Yel 2.36 O/l Yes No BDH103
Pistol 1 Blk 2.36 Off/On/Test Yes No BDH4
Pistol*1 Blk 2.00 O/I/Test Yes No BDH79*
*Mounts directly to switch. No shaft required.
Bussmann®
7
Disconnect Switches
Fusible Disconnect Switch Components
Shafts
Mounting Depth** Shaft Length (inches) Catalog Number
30 Amps ( 0.20∑ ≈ 0.20∑) Selector
5.5 - 5.7 3.3 CDS85S
5.5 - 6.5 4.1 CDS105S
5.5 - 7.1 4.7 CDS120S
5.5 - 7.5 5.1 CDS130S
6.3 - 9.4 7.1 CDS180S
9.1 - 12.2 9.8 CDS250S
12.2 - 15.4 13.0 CDS330S
30 Amps ( 0.20∑ ≈ 0.20∑) Pistol
6.89 - 7.48 5.91 BDS150P
7.67 - 8.27 6.69 BDS170
11.42 - 12.00 10.43 BDS265
16.72 - 17.32 15.75 BDS400
60-100 Amps ( 0.24∑ ≈ 0.24∑)
5.50 - 8.50 5.90 BDS150
8.00 - 11.00 8.26 BDS210
11.00 - 14.00 11.41 BDS290
13.75 - 16.75 14.17 BDS360
16.54 - 19.69 16.93 BDS430
200-400 Amps ( 0.47∑ ≈ 0.47∑)
7.87 - 12.20 8.66 BDS220
9.05 - 13.38 9.84 BDS250
10.22 - 14.54 11.00 BDS280
12.0 - 16.32 12.78 BDS325
14.78 - 19.10 15.56 BDS395
17.53 - 21.85 18.31 BDS465
20.28 - 24.62 21.06 BDS535
600-800 Amps ( 0.47∑ ≈ 0.47∑)
10.04 - 12.83 9.84 BDS250
11.20 - 14.00 11.00 BDS280
12.98 - 15.77 12.78 BDS325
15.76 - 18.55 15.56 BDS395
18.51 - 21.30 18.31 BDS465
21.06 - 24.08 21.06 BDS535
**Mounting depth is the distance from the outside of door to the disconnect switch mounting
plate. Shaft can be cut to desired length.
Handles – 60-800A Fusible
Grip
NEMA Length Catalog
Style Type Color (Inches) Marking Number
60-100 Amps ( 0.24∑ ≈ 0.24∑)
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH20
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH50
Pistol 1, 3R, 4X, 12 Blk 2.36 Off/On Yes No BDH57
200 Amps ( 0.47∑ ≈ 0.47∑)
Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53
200-800 Amps ( 0.47∑ ≈ 0.47∑)
Pistol 1, 3R, 12 Blk 5.71 Off/On Yes Yes BDH16
Pistol 1, 3R, 4, 4X, 12 Blk 5.71 Off/On Yes No BDH35
Pistol 1, 3R, 12 R/Y 5.71 O/l Yes Yes BDH11
Pistol 1, 3R, 4, 4X, 12 R/Y 5.71 O/l Yes No BDH36
Metallic 1, 3R, 4, 4X, 12 Blk 8.66 Off/On Yes No BDH8
Terminal Lug Kits – Kit Includes 6 Lugs
Amp Rating Wire Size Wire Type Kit Catalog Number
30 & 60 Lugs come standard with switch
100 #14 - 2/0 Cu/Al BDTL24
200 #6 - 300 kcmil Cu/Al BDTL25
400 #2 - 600 kcmil Cu/Al BDTL26
600 & 800 (2) #2 - 600 kcmil Cu/Al BDTL27
Padlock-
able
Defeat-
able
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Contents
Previous
Next
Bussmann®
8
Disconnect Switches
Fusible Disconnect Switch Accessories & Flange-Mounted Operators
Fuse Covers and Terminal Shrouds (line-side)
Switch Type Fuse Covers Terminal Shrouds
Amp Fuse Catalog Catalog
Rating Class Voltage Number Number
60 J 600V BDFC60J Not Required
100 J or T 600V BDFC100 BDTSF1
200 J or T 600V BDFC200*BDTSF2
400 J 600V BDFC400*BDTSF4
600, 800 J or L 600V BDFC600*BDTSF6
*3-pole 30, 200-800 amp fusible switches come with the fuse cover as standard.
Terminal shrouds can also be used on the load side.
Auxiliary Contacts – 30 Amps
Type of Amp Catalog
Auxiliary Contact Rating Voltage Number
Form C 6 250 BDAUX157
Aux. Contact Bracket BDAUXB
Aux. Contact (NO) NEMA, A600, P600 BDAUXCB10
Aux. Contact (NC) BDAUXCB01
Auxiliary Contacts – 60-800 Amps
Switch Aux. Contact Voltage 1 NO & 1 NC 2 NO & 2 NC
Amp Rating Amp Rating Catalog Number Catalog Number
60 6 250 BDAUX7 BDAUX8
100 6 250 BDAUX7 BDAUX8
200-800 10 600 BDAUX1 BDAUX2
Conversion Kits for Combination Switches**
30 Amp 60-100 Amp 200-800 Amp
Description Catalog Number Catalog Number Catalog Number
6 Pole BDZW5 BDZW2 BDZW9
Transfer BDZW30 BDZW1 BDZW121
(2 switches with center OFF position)
Bypass BDZW13
(3 switches with center OFF position)
Mechanical Interlock BDZW4 BDZW32
(Mechanical interlock of two BDZW142
switches) BDZW152
Shaft Extension Coupler BDZW95
1Includes metallic handle.
2Distance between center line of shafts: BDZW3 = 11.819; BDZW14 = 9.849;
BDZW15 = 19.689.
**See page 14 for descriptions of conversion kits.
Flange-Operated Switches
Amp Switch & Mechanism
Rating Catalog Number
30 BDFLCF30J6-F
60 BDFLF60J6-F
100 BDFLF100J6-F
Shaft and handle must be ordered separately.
Flange Switch Handles
NEMA
Rating Handle
4, 4X BDFNHS4
12 BDFNHS12
Flange Switch Shafts
Length Shaft
(inches) Catalog Number
12 BDFHS12
17 BDFHS17
22.5 BDFHS22
Door Hardware – NEMA 12
Item Catalog Number
Safety door latch, 2 point with 69handle BDDHK
Roller for 3 point latch, add to FH-DHK BD3RL
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Contents
Previous
Next
Bussmann®
9
Disconnect Switches
Non-Fusible Disconnect Switches
16-3150 Amps
Features:
Compact, heavy-duty, space saving design
Complete line of non-fusible disconnect switches 16A
through 3150A
Convenient through-the-door operation
Rotary and variable-depth handle mechanisms for through-
the-door operation
NEMA rated handles 1, 3R, 4, 4X & 12
NEMA 1, 3R & 12 handles are defeatable in “ON” position
Handles available with interlock defeater for emergency
maintenance purpose
Handles are lockable with three padlocks
DIN rail mountable switches (16-80A), base and door
mountable switches
Snap-on auxiliary contacts, power poles and additional poles
Terminal shrouds available for “touch-safe” protection
Agency Approvals:
U.L. 508 (CSA 22.2 No. 14): Suitable for use in equipment,
machinery, or industrial control panels as a motor controller;
and are provided with horsepower and ampere ratings.
(16-175A, 3 Pole), (16-40A, 4 Pole)
U.L. 98 (CSA 22.2 No. 4): Suitable for use on service
equipment, panel boards, switchboards, industrial
control equipment, motor control centers, etc. (200-2000A,
2 & 3 Pole), (200-600A, 4 Pole)
U.L. File 155129 (16-175A)
U.L. File 155130 (200-2000A)
CSA File 58077M9
IEC 947-1, 3
Contents
Previous
Next
Bussmann®
10
Disconnect Switches
Compact Disconnect Switches – 16-40A, 600V
Door Mounted Switches
(16-30A, 600V) 3 pole1
Maximum Horsepower Rating Terminal Lugs
Amp Single Phase Three Phase Wire Wire Catalog
Rating 120V 240V 200V 240V 480V 600V Size Type Number
16 ⁄Ω™ 1.5 2 2 7.5 7.5 #18-#8 Cu CDNF16D
25 ‹Ω¢ 2 3 3 7.5 10 #18-#8 Cu CDNF25D
30 1 3 5 5 10 15 #18-#8 Cu CDNF32D
Shafts not required with door mounted switches.
CDNF32 CDNF45
CDH1S
BDH47
CDH6S
Base & DIN Rail Mounted Switches
(16-40A, 600V) 3 pole1
Maximum Horsepower Rating Terminal Lugs
Amp Single Phase Three Phase Wire Wire Certification/ Catalog
Rating 120V 240V 200V 240V 480V 600V Size Type Listing Number
16 ⁄Ω™ 1.5 2 2 7.5 7.5 #18-#8 Cu CSA/U.L. CDNF16
25 ‹Ω¢ 2 3 3 7.5 10 #18-#8 Cu CSA/U.L. CDNF25
30 1 3 5 5 10 15 #18-#8 Cu CSA/U.L. CDNF32
40 2 5 10 10 20 20 #14-#4 Cu CSA/U.L. CDNF45
Selector Handles
NEMA Catalog
Ratings Color Padlockable Defeatable Number
All marked both O/l and OFF/ON
1 Blk CDH1S
1 R/Y CDH2S
1, 3R, 12 Blk CDH3S
1, 3R, 12 R/Y CDH4S
1, 3R, 12 Blk CDH5S
1, 3R, 12 R/Y CDH6S
Shafts for use with
CDH Selector Handles2(M5 ≈ 5mm)
Length3Catalog
inches/mm Number
3.3/85 CDS85S
4.1/105 CDS105S
4.7/120 CDS120S
5.1/130 CDS130S
7.1/180 CDS180S
9.8/250 CDS250S
13.0/330 CDS330S
Shafts for use with
Pistol Handles2(M5 ≈ 5mm)
Length3Catalog
inches/mm Number
5.9/150 CDS48P
6.7/170 CDS67P
10.4/265 CDS49P
15.8/400 CDS50P
19.7/500 CDS99P
Pistol Handles
NEMA Length Padlock- Defeat- Catalog
Ratings Color Marking mm able able Number
1, 12 Blk Off/On 80 BDH47
1, 12 R/Y O/l 80 BDH48
1, 3R, 12 Blk Off/On 60 BDH99
1, 3R, 12 R/Y O/l 60 BDH100
1, 3R, 4, 4X, 12 Blk Off/On 60 BDH102
1, 3R, 4, 4X, 12 R/Y O/l 60 BDH103
Switch Shaft2Handle
Selector Handles for Door Mounted Switches
NEMA Catalog
Ratings Color Padlockable Defeatable Number
All marked both O/l and OFF/ON
1 Blk CDH7S
1 R/Y CDH8S
1, 3R, 12 Blk CDH9S
1, 3R, 12 R/Y CDH10S
Select one of each
1A snap-on fourth pole may be added. See Accessories.
2Door mounted switches do not require shafts.
3For mounting depth please see page 16.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Non-Fusible, 16-40A, 600V
+ +
Contents
Previous
Next
Bussmann®
11
Disconnect Switches
Non-Fusible Disconnect Switches – 80-100A, 600V
Rotary Type Switches (80-100 Amps, 600V)
Maximum Horsepower Rating Wire Size 3 Pole
Amp Single Phase Three Phase For Terminal Certification/ Catalog
Rating 120V 200V 240V 200V 208V 240V 480V 600V Lugs Listing Number
80 3 7.5 10 15 15 20 40 50 #14 - #1 Cu CSA, U.L. BDNF60
100 5 10 15 20 20 25 50 60 #6 - 2/0 Cu CSA, U.L. BDNF100
Catalog number & price includes switch and lugs only. Order handles and shafts from tables below.
Handles
80-100 Amps ( 0.20∑ ≈ 0.20∑)
Style NEMA Type Color Grip Length (Inches) Marking Padlockable Defeatable Catalog Number
Selector 1, 3R, 12 Blk O/l and Off/On Yes No CDH3S
Selector 1, 3R, 12 Red/Yel O/l and Off/On Yes No CDH4S
Selector 1, 3R, 12 Blk O/l and Off/On Yes Yes CDH5S
Selector 1, 3R, 12 Red/Yel O/l and Off/On Yes Yes CDH6S
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH47
Pistol 1, 12 Red/Yel 3.15 O/l Yes Yes BDH48
Pistol 1, 3R, 12 Blk 2.36 Off/On Yes Yes BDH99
Pistol 1, 3R, 12 Red/Yel 2.36 O/l Yes Yes BDH100
Pistol 1, 3R, 4, 4X, 12 Blk 2.36 Off/On Yes No BDH102
Pistol 1, 3R, 4, 4X, 12 Red/Yel 2.36 O/l Yes No BDH103
Rotary Handles – Mounted Directly to Switch
Switch Type Poles NEMA Type Color Marking Padlockable Defeatable Catalog Number
BDNF60 3 1 Blk O/l Yes No BDH127
No shaft required
Toggle Type Switch (80-100 Amps, 600V)
Maximum Horsepower Rating Wire Size 3 Pole
Amp Single Phase Three Phase For Terminal Certification/ Catalog
Rating 120V 200V 240V 200V 208V 240V 480V 600V Lugs Listing Number
80 3 7.5 10 15 15 20 40 50 #14 - #1 Cu CSA, U.L. BDNF60T
100 5 10 15 20 20 25 50 60 #6 -2/0 Cu CSA, U.L. BDNF100T
Agency Approvals: 40-175 Amps: U.L. 508, File 155129,
CSA 22.2 No. 14; 200-800 Amps: U.L. 98, File 155130, CSA
22.2 No. 4, Guide WPZX: CSA File 58077M9; IEC 947-1
Extended Shafts (0.20∑ ≈ 0.20∑)
For Handle Mounting Shaft Catalog
Type Depth*Length Number
4.61 - 5.39 3.3 CDS85S
5.39 - 6.18 4.1 CDS105S
NEMA 1, 3R 5.98 - 6.77 4.7 CDS120S
& 12 6.38 - 7.17 5.1 CDS130S
Selector 8.35 - 9.13 7.1 CDS180S
11.10 - 11.89 9.8 CDS250S
14.25 - 15.04 13 CDS350S
NEMA 1, 3R, 6.89 - 7.48 5.91 BDS150P
4, 4X & 12 7.67 - 8.27 6.69 BDS170
Pistol 11.42 - 12.00 10.43 BDS265
16.72 - 17.32 15.75 BDS400
*Mounting depth is the distance from the outside of the door to the disconnect switch
mounting plate. Shaft can be cut to desired length.
Auxiliary Contacts – 80A
Switch Auxiliary Amp Catalog
Amp Rating Contact Rating Voltage Number
80 Aux. contact base BDAUXB80
80 Aux. contact (NO) NEMA A600, P600 BDAUXCA10
80 Aux. contact (NC) NEMA A600, P600 BDAUXCA01
Auxiliary Contacts – 80-100A
Switch Aux. Contact Voltage 1 NO & 1 NC 2 NO & 2 NC
Amp Rating Amp Rating Catalog Number Catalog Number
80 6 250 BDAUX79 BDAUX80
100 6 250 BDAUX52 BDAUX53
Terminal Shrouds (Line side)
Amp Rating Catalog Number
100 BDTS1
Note: Terminal shrouds can also be used on the load side.
Accessories – 80-100 Amps
Contents
Previous
Next
Bussmann®
12
Disconnect Switches
Non-Fusible Disconnect Switches – 175 -600A, 600V
Rotary Type Switches (175-600 Amps, 600V)
Amp Maximum Horsepower Rating Certification/ Catalog
Rating 200V 208V 240V 480V 600V Listing Number
3 Pole
175 30 30 40 75 100 CSA, U.L. BDNF175A
200 60 60 75 150 200 CSA, U.L. BDNF200A
400 100 100 125 250 350 CSA, U.L. BDNF400
600 150 150 200 400 500 CSA, U.L. BDNF600A
2 Pole
175 30 30 40 75 100 CSA, U.L. BDNF175A2
200 60 60 75 150 200 CSA, U.L. BDNF200A2
400 100 100 125 250 350 CSA, U.L. BDNF4002
600 150 150 200 400 500 CSA, U.L. BDNF600A2
4 Pole
175 30 30 40 75 100 IEC BDNF175A4
200 60 60 75 150 200 CSA, U.L. BDNF200A4
400 100 100 125 250 350 CSA, U.L. BDNF4004
600 150 150 200 400 500 CSA, U.L. BDNF600A4
Catalog number & price includes switch only. Order handles, shafts and terminal lugs from tables below.
Auxiliary Contacts
Switch Aux. Contact Voltage 1 NO & 1 NC 2 NO & 2 NC
Amp Rating Amp Rating Catalog Number Catalog Number
175-200 10 600 BDAUX12 BDAUX13
400-600 10 600 BDAUX1 BDAUX2
Handles
NEMA Length Catalog
Style Type Color (Inches) Marking Number
175-200 Amps ( 0.31∑ ≈ 0.31∑)
Pistol 1, 12 Blk 3.15 Off/On Yes Yes BDH64
Pistol 1, 3R, 4, 4X, 12 Blk 3.15 Off/On Yes No BDH67
400 Amps ( 0.47∑ ≈ 0.47∑)
Pistol 1, 3R, 12 Blk 4.72 Off/On Yes Yes BDH53
400-600 Amps ( 0.47∑ ≈ 0.47∑)
Pistol 1, 3R, 12 Blk 5.71 Off/On Yes Yes BDH16
Pistol 1, 3R, 4, 4X, 12 Blk 5.71 Off/On Yes No BDH35
Pistol 1, 3R, 12 R/Y 5.71 O/l Yes Yes BDH11
Pistol 1, 3R, 4, 4X, 12 R/Y 5.71 O/l Yes No BDH36
Metallic 1, 3R, 4, 4X, 12 Blk 8.66 Off/On Yes No BDH8
Terminal Lug Kits – Kit Includes 6 Lugs
Amp Rating Wire Size Wire Type Kit Catalog Number
175 & 200 #6 - 300 kcmil Cu/Al BDTL25
400 #2 - 600 kcmil Cu/Al BDTL26
600 (2) #2 - 600 kcmil Cu/Al BDTL27
Padlock-
able
Defeat-
able
Shafts
Mounting Depth*Shaft Length Catalog Number
175-200 Amps ( 0.31∑ ≈ 0.31∑)
4.72 - 8.66 5.51 BDS140
8.66 - 12.59 9.45 BDS240
12.61 - 16.55 13.39 BDS340
18.91 - 22.85 19.69 BDS500
400-600 Amps ( 0.47∑ ≈ 0.47∑)
6.15 - 7.75 4.21 BDS107
6.15 - 10.07 6.54 BDS166
6.49 - 10.82 7.28 BDS185
7.87 - 12.2 8.66 BDS220
9.05 - 13.38 9.84 BDS250
10.22 - 14.54 11.02 BDS280
12.0 - 16.32 12.80 BDS325
14.78 - 19.1 15.55 BDS395
17.53 - 21.85 18.31 BDS465
20.28 - 24.62 21.06 BDS535
*Mounting depth is the distance from the outside of the door to the disconnect switch
mounting plate. Shaft can be cut to desired length.
Terminal Shrouds (Line side)
Amp Rating Catalog Number
175 & 200 BDTS2
400 BDTS4
600 BDTS6A
Note: Terminal shrouds can also be used on the load side.
Accessories – 175-600A
Agency Approvals:
40-175 Amps: U.L. 508, File 155129, CSA 22.2 No. 14; 200-800 Amps: U.L. 98, File 155130, CSA 22.2 No. 4
CSA File 58077M9; IEC 947-1
CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Contents
Previous
Next
Bussmann®
13
Disconnect Switches
Non-Fusible Disconnect Switches – 800-3150A, 600V
Switches (800-3150 Amps, 600V)
Amp Maximum Horsepower Rating Certification/ Catalog
Rating 200V 208V 240V 480V 600V Listing Number
3 pole
800 200 200 250 500 600 CSA/U.L. BDNF800A
1200 CSA/U.L. BDNF1200
1600 CSA/U.L. BDNF1600
2000 CSA/U.L. BDNF2000
3150 IEC BDNF31503
Other pole configurations
2 pole
800 200 200 250 500 600 CSA/U.L. BDNF800A2
1200 CSA/U.L. BDNF12002
1600 CSA/U.L. BDNF16002
2000 CSA/U.L. BDNF20002
3150 IEC BDNF31502
4 pole
800 200 200 250 500 600 IEC BDNF800A4
1200 IEC BDNF12004
1600 IEC BDNF16004
2000 IEC BDNF20004
3150 IEC BDNF31504
Handles – all padlockable
Catalog
NEMA Color Length Marking Number
800-3150 Amps ( 0.47∑ ≈ 0.47∑)
Pistol
1, 3R, 12 Blk 5.71 Off/On BDH16
1, 3R, 12 R/Y 5.71 O/l BDH11
1, 3R, 4, 4X, 12 Blk 5.71 Off/On BDH35
1, 3R, 4, 4X, 12 R/Y 5.71 O/l BDH36
Metallic
1, 3R, 4, 4X, 12 Blk 8.66 Off/On BDH8
Terminal Lug Kits – Kit Includes 6 Lugs
Amp Wire Wire Kit Catalog
Rating Size Type Number
800 (2) #2 - 600 kcmil Cu/Al BDTL30
1200 (4) #2 - 600 kcmil Cu/Al BDTL28
1600 (4) #2 - 600 kcmil Cu/Al BDTL28
2000 (8) #2 - 600 kcmil Cu/Al BDTL28/2
3150 (8) #2 - 600 kcmil Cu/Al BDTL28/2
Defeat-
able
Shafts
Mounting Depth1Shaft Length Catalog Number
800-1200 Amps ( 0.47∑ ≈ 0.47∑)
7.4 - 8.6 4.2 BDS107
7.4 - 10.9 6.5 BDS166
7.9 - 11.6 7.3 BDS185
9.3 - 13.0 8.7 BDS220
10.4 - 14.2 9.8 BDS250
11.6 - 15.3 11.0 BDS280
13.7 - 17.1 12.8 BDS325
16.2 - 19.9 15.6 BDS395
18.9 - 22.6 18.3 BDS465
21.7 - 25.4 21.1 BDS535
1600-3150 Amps ( 0.47∑ ≈ 0.47∑)
13.37 - 23.1 12.8 BDS325
16.15 - 23.8 15.6 BDS395
18.9 - 26.6 18.3 BDS465
21.65 - 29.3 21.1 BDS535
1Mounting depth is the distance from the outside of door to the
disconnect switch mounting plate. Shaft can be cut to desired
length.
CE logo denotes compliance with European Union
Low Voltage Directive (50-1000 Vac, 75-1500 Vdc).
Refer to BIF document #8002 or contact Bussmann
Application Engineering at 314-527-1270 for more
information.
Agency Approvals:
U.L. 98
U.L. File E101914, Guide WPZX
CSA File LR58077, LR58247
IEC 947-1
Auxiliary Contacts
Switch Aux. 1 NO & 2 NO &
Amp Contact Voltage 1 NC 2 NC
Rating Amp Rating Cat. No. Cat. No.
800-3150 10 600 BDAUX1 BDAUX2
Terminal Shrouds (Line side)
Amp Rating Catalog Number
800 BDTS8A
1200 BDTS12
Accessories – 800-3150 Amps
Contents
Previous
Next
Bussmann®
14
Disconnect Switches
Flange-Operated, Non-Fusible Disconnect Switches
Conversion Kits – 16-3150A, 600V
Flange-Operated Switches1
Amperage Switch & Mechanism
Rating Catalog Number
30 BDFLNF30F
60 BDFLNF60F
100 BDFLNF100F
175 BDFLNF175F
200 BDFLNF200AF
1Contact Bussmann for additional information.
Handles
NEMA Handle
Type Catalog Number
1, 3R, 4, 4X, 12 BDFHNHS4
1, 3R, 12 BDFHNHS12
Shafts
Length Shaft
(Inches) Catalog Number
12 BDFHS12
17 BDFHS17
22.5 BDFHS22
Door Hardware – NEMA 12
Item Catalog Number
Safety door latch, 2 point with 69handle. BDDHK
Roller for 3 point latch, add to FHDHK BD3RL
Flange-Operated Switch
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Conversion Kits for Combination Switches
Catalog Numbers
Description 16 - 100A 175 - 200A 400 - 1200A 1600 - 3150A
6 pole CDZW8 BDZW18 BDZW9
Transfer CDZW6 BDZW20 BDZW121
(2 switches with center OFF position)
Bypass CDZW17 BDZW21 BDZW13
(3 switches with center OFF position)
Mechanical Interlock BDZW32
(Mechanical interlock of two switches) BDZW19 BDZW142BDZW152
BDZW152
Shaft Extension Coupler BDZW95 BDZW95
1Includes metallic handle.
2Distance between center line of shafts: BDZW3 - 11.819;
BDZW14 - 9.849; BDZW15 - 19.689.
Conversion kit descriptions
6 Pole
This conversion kit, in conjunction with two
standard 3 pole switches, allows the switches
to open or close simultaneously. Handle is
not included.
Mechanical interlock of two
standard switches
This conversion kit prevents one switch from
closing when the other switch is in the ON
position. Handle is not included.
Bypass (three standard switches with center
OFF position)
This conversion kit operates three switches: Two
switches in parallel and one changeover switch
to allow power bypass. A 3 position handle is
included.
Switch Size Handle Part Number
16-100A BDH37
NEMA 1 & 12 only
175-1200A BDH6
Transfer (two standard switches with center
OFF position)
This conversion kit, in conjunction with two
3 pole switches, manually transfers power
from one switch to another with a center OFF
position. A 3 position handle is included.
Switch Size Handle Part Number
16-100A BDH37
NEMA 1 & 12 only
175-1200A BDH21
CE logo denotes compliance with European Union Low Voltage Directive (50-1000 Vac, 75-1500 Vdc). Refer to BIF document
#8002 or contact Bussmann Application Engineering at 314-527-1270 for more information.
CDZW8
CDZW6
30-200A, 600V
Contents
Previous
Next
Bussmann®
15
Disconnect Switches
Compact Disconnect Switches – Accessories
Non-Fusible, 16-40A, 600V
Conversion Kits for
Combination Switches2
Description Catalog Number
6 Pole CDZW83
Transfer CDZW64
(2 switches with center OFF position)
Bypass CDZW174
(3 switches with center OFF position)
O
I
O
ION
Strömberg
IEC 947-3 Ue/V 415 500 690
Ith 16A AC-22A Ie/A 16 16 16
50...60Hz AC-23A Ie/A 14 14 12
®®
CDAUX01CDAUX10
CDS32P
CDZW8
CDTS63T3
CDS63P
CDZW6
Auxiliary Contacts
Mounted on CDNF32 and
CDNF45 Switches
Additional Poles – Snap-On Mounting1
Switch accepts one additional pole per side
Mounts on left or right side of switch
For Switches Catalog Number
Solid Neutral
CDNF16...32 CDN32P
CDNF16...32D CDN32D
Manually Operated Neutral
CDNF16...32 CDD32P
CDNF16...32D CDD32D
Ground Terminal
CDNF16...32 CDE32P
CDNF16...32D CDE32D
Auxiliary Contacts – Snap-On Mounting
Catalog
For Switches Description Amps Volts Number
1 NO
CDNF16...45 Mounts on right hand 10 600 CDAUX10
side of switch (2 max.)
1 NC
CDNF16...45 Mounts on left hand 10 600 CDAUX01
side of switch (2 max.)
Power Poles – Snap-On Mounting1
Only one power pole per switch
Mounts on left or right side of switch
For Switches Catalog Number
Fourth Pole
CDNF16...32 CDS32P
CDNF16...32D CDS32D
CDNF45 CDS63P
Late-Break/Early Make
CDNF16...32 CDL32P
CDNF16...32D CDL32D
Terminal Shrouds – Snap-On Mounting2
For Switches Catalog Number
For 3-Pole Switches
CDNF16...32 CDTS32T3
CDNF45 CDTS63T3
For Single Pole
CDAUX32P CDTS32T1
CDAUX63P CDTS63T1
Bypass (three standard switches with
center OFF position)
This conversion kit operates three switches: Two
switches in parallel and one changeover switch to
allow power bypass. A 3 position handle is
included, (NEMA 1 & 12 only.)
Transfer (two standard switches with
center OFF position)
This conversion kit, in conjunction with two 3 pole
switches, manually transfers power from one switch
to another with a center OFF position. A 3 position
handle is included. (NEMA 1 & 12 only).
6 Pole
This conversion kit, in conjunction with two
standard 3 pole switches, allows the switches
to open or close simultaneously. Handle is not
included.
CDTS32T3
1Switch accepts one power pole or one additional pole per side.
Only one power pole per switch.
2Switches are not included.
3One shaft is included.
4Shafts included.
CE logo denotes compliance with European Union
Low Voltage Directive (50-1000 Vac, 75-1500 Vdc).
Refer to BIF document #8002 or contact Bussmann
Application Engineering at 314-527-1270 for more
information.
Contents
Previous
Next
Bussmann®
16
Disconnect Switches
Compact Disconnect Switches – Mounting Depths
Non-Fusible, 16-40A, 600V
Shaft Shaft Length Mounting Depth Mounting Depth Shaft Dimensions
Switch Sizes Handles Catalog Number Inches/mm Inches mm Mmm
CDS85S 3.3/85 4.2 – 5.0 106 – 126
CDS105S 4.1/105 5.0 – 5.8 126 – 146
CDS120S 4.7/120 5.6 – 6.4 141 – 161
CDNF16–32 CDH1S & CDH2S CDS130S 5.1/130 6.0 – 6.7 151 – 171 5
CDS180S 7.1/180 7.9 – 8.7 201 – 221
CDS250S 9.8/250 10.7 – 11.5 271 – 291
CDS330S 13.0/330 13.8 – 14.6 351 – 371
CDS85S 3.3/85 3.6 – 4.3 92 – 110
CDS105S 4.1/105 4.4 – 5.1 112 – 130
CDS120S 4.7/120 5.0 – 5.7 127 – 145
CDNF16–32 CDH3S-6S CDS130S 5.1/130 5.4 – 6.1 137 – 155 5
CDS180S 7.1/180 7.4 – 8.1 187 – 205
CDS250S 9.8/250 10.1 – 10.8 257 – 275
CDS330S 13.0/330 13.3 – 14.0 337 – 355
CDS48P 5.9/150 6.2 – 6.7 157 – 171
CDS67P 6.7/170 7.0 – 7.5 177 – 191
CDNF16–32 Pistol CDS49P 10.4/265 10.7 – 11.3 272 – 286 5
CDS50P 15.8/400 16.0 – 16.6 407 – 421
CDS85S 3.3/85 4.9 – 5.6 124.5 – 142.5
CDS105S 4.1/105 5.7 – 6.4 144.5 – 162.5
CDS120S 4.7/120 6.3 – 7.0 159.5 – 177.5
CDNF45 CDH1S & CDH2S CDS130S 5.1/130 6.7 – 7.4 169.5 – 187.5 5
CDS180S 7.1/180 8.6 – 9.4 219.5 – 237.5
CDS250S 9.8/250 11.4 – 12.1 289.5 – 307.5
CDS330S 13.0/330 14.6 – 15.3 369.5 – 387.5
CDS85S 3.3/85 4.4 – 5.0 110.5 – 126.5
CDS105S 4.1/105 5.1 – 5.8 130.5 – 146.5
CDS120S 4.7/120 5.7 – 6.4 145.5 – 161.5
CDNF45 CDH3S-6S CDS130S 5.1/130 6.1 – 6.8 155.5 – 171.5 5
CDS180S 7.1/180 8.1 – 8.7 205.5 – 221.5
CDS250S 9.8/250 10.9 – 11.5 275.5 – 291.5
CDS330S 13.0/330 14.0 – 14.7 355.5 – 371.5
CDS48P 5.9/150 6.9 – 7.4 175 – 187
CDS67P 6.7/170 7.7 – 8.1 195 – 207
CDNF45 Pistol CDS49P 10.4/265 11.4 – 11.9 290 – 302 5
CDS50P 15.8/400 16.7 – 17.2 425 – 437
IEC Utilization Categories
Utilization Category
Nature of Current Frequent Operation Infrequent Operation Typical Applications
AC-20A AC-20B Connecting and disconnecting under no-load conditions
AC-21A AC-21B Switching of resistive loads including moderate overloads
Alternating Current AC-22A AC-22B Switching of mixed resistive and inductive loads, including
AC-23A AC-23B moderate overloads
Switching of motor loads or other highly inductive loads
DC-20A DC-20B Connecting and disconnecting under no-load conditions
DC-21A DC-21B Switching of resistive loads including moderate overloads
Direct Current DC-22A DC-22B Switching of mixed resistive and inductive loads, including
DC-23A DC-23B moderate overloads (e.g., shunt motors)
Switching of highly inductive loads (e.g., series motors)
Rated Thermal Current No. Mechanical Operations No. Mechanical Operations
0-50A 10,000 2,000
Category AC-23 includes occasional switching of individual motors. The switching of capacitors or tungsten filament lamps shall be subject to agreement between manufacturer and user.
Contents
Previous
Next
Bussmann®
17
Disconnect Switches
Technical Data – Fusible, 30-800 Amps
U.L. & CSA Ratings
Ampere Rating 30 60 100 200 400 600 800
2 pole U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98
U.L. Standard 3 pole U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98
4 pole
Short-circuit rating with fuse kA 100 100 100 100 100 100 100
Fuse size A 30 60 100 200 400 600 800
Fuse class J/CC J/T J/T J/T J/T J/T T/L
Electrical endurance 6,000 6,000 6,000 6,000 1,000 1,000 1,000
Mechanical endurance 10,000 10,000 8,000 6,000 6,000 6,000
200V 5 15 25 50 100 150 200
Maximum 208V 7.5 15 25 50 125 150 200
Horsepower 240V 7.5 15 30 60 125 200 250
Ratings 480V 15 30 60 125 250 400 500
600V 20 40 60 150 350 500 600
IEC Ratings
Ampere Rating 30 60 100 200 400 600 800
Dielectric strength 50 Hz, 1 min kV 10 8 8 10 10 10 10
Rated impulse withstand voltage kV 12 12 12 12 12 12 12
Rated thermal current in ambient 40°C/in open air A/W 32/3.5 63/7.5 125/12 250/32 400/45 630/60 800/65
Max. fuse power dissipation1in enclosure A/W 32/3.5 63/7.5 125/12 250/23,250/27 400/34,360/37 600/45,570/50 720/55
In enclosure with solid links A 32 7.5 125 315 450 700 900
With minimum cable cross section Cu mm26 16 50 120 240 2 x 185 2 x 240
Rated operational voltage AC-20 and DC-20 V 1,000 750 750 1,000 1,000 1,000 1,000
Rated operational current, AC-21A up to 500V A 32 63 125 250 400 630 800
690V A 32 6321252250 400 630 800
Rated operational current, AC-22A up to 500V A 32 63 125 250 400 630 800
690V A 32 6321252250 400 630 800
Rated operational current, AC-23A up to 500V A 32 63 125 250 400 630 720
690V A 32 402502250 400 630 720
Rated operational current/poles in series 48V A 32/24 250/2 400/2 630/2 800/2
DC-21A 100/220V A 32/2 63/3 125/3 250/2 400/2 630/2 800/2
440V A 32/4 63/4 125/42250/2 400/2 630/2 800/2
500-750V A 250/3 400/3 630/3 800/3
1000V A 250/4 400/4 630/4 800/4
Rated operational current/poles in series 48V A 32/24 250/2 400/2 630/2 800/2
DC-22A 100/220V A 32/2 63/3 125/3 250/2 400/2 630/2 800/2
440V A 32/4 63/4 125/42250/2 400/2 630/2 800/2
500-750V A 250/3 400/3 630/3 800/3
1000V A 250/4 400/4 630/4 800/4
Rated operational current/poles in series 48V A 32/24 250/2 400/2 630/2 800/2
DC-23A 110/220V A 32/2 63/3 125/3 250/2 400/2 630/2 800/2
440V A 32/4 100/42250/2 400/2 630/2 800/2
500-750V A 250/3 400/3 630/3 800/3
1000V A 630/4 800/4
Rated operational power, AC-233230V kW 8 15 30 70 110 180 200
—The kW ratings are accurate for 3-phase 400V kW 14 30 55 132 210 315 350
1500 R.P.M. standard asynchronous motors 415V kW 15 30 55 140 230 340 380
500V kW 18 30 70 170 280 400 470
690V kW 25 30 45 230 330 540 600
1Ambient temperature 60°C: derating 20%. Mounting on “ceiling”: derating 10%. Mounting on wall, horizontal fuses: derating 8%.
2Utilization category B.
3Some fuse links limit these figures further. Starting current characteristics must be considered separately.
4Use 4-pole switches with 2 + 2 parallel contacts in series.
LOAD
Figure 1
Contents
Previous
Next
Bussmann®
18
Disconnect Switches
Technical Data – Fusible, 30-800 Amps
IEC Ratings
Ampere Rating 30 60 100 200 400 600 800
Rated breaking capacity in category AC-23 up to 500V A 256 504 800 2,000 3,200 5,760 5,760
690V A 256 320 405 2,000 3,200 5,760 5,760
Rated breaking capacity/poles in series up to 220V A 128/2 256/3 640/3 1,000/2 1,600/2 3,200/2 3,200/2
in category DC-23 400V A 128/4 400/4 1,000/2 1,600/2 3,200/2 3,200/2
500-750V A 1,000/3 1,600/3 3,200/3 3,200/3
1000V A 3,200/4 3,200/4
Rated conditional short-circuit current RMS 80kA, 415V kA 9 12 23 40 40 75 75
and corresponding max. allowed
cut-off current, peak-values 100kA, 500V kA 7.5 9 17 40 40 75 75
—The cut-off currents refer to single
phase fuse tests 50kA, 690V kA 6 8 14 35 35 60
—Fuse selection tables on request
Rated short-time withstand current, 1s. RMS -value kA 1 2 5 8 10 16 16
Rated capacitor power 400V kVAr 15 30 50 105 180 250 310
The capacitor rating of the switch-fuse is
limited by the fuse link 415V kVAr 15 32 55 115 200 270 340
690V kVAr 25 50 90 190 325 450 550
Power loss/pole With rated current, without fuse W 2 4 5 11 30 55 77
Mechanical endurance
Divide by two for operation cycles Oper 20,000 20,000 20,000 16,000 16,000 10,000 10,000
Fuse types, IEC 269-2 DIN 43620 00 00 0-1 0-2 3 3
NFC 14 x 51 14 x 51 22 x 58 0-1 0-2 3
BS88 A1.F1 A2-A3 A2-A4AB1-B2 B1-B4 B1-B4 C1-C2 C1-C3
–size/distance of fuse link bolts– mm M4/44.5 M5/73 M5/73, M8/94 M8/111 M8/111 M10/133, 184 M10/133, 184
Weight without accessories
3-pole switch fuses kg 0.7 1.6 1.8 6.9 7.8 15.5 17.0
4-pole switch fuses kg 0.9 1.9 2.3 7.9 8.8 19.0 21.0
Built-in terminal size Cu mm20.5...10 2.5…25
Terminal bolt size
Metric thread diameter x length mm M8 x 25 M10 x 40 M10 x 40 M12 x 40 M12 x 40
Terminal tightening torque
Counter torque required Nm 2 5 15…22 30…44 30…44 50…75 50…75
Fuse-links bolts tightening torque Nm 2 3.5 M5:3.5/M8:10 15 15 40 40
Operating torque
Typical for 3-pole switch fuses Nm 3 3 5 22 22 28 28
Contents
Previous
Next
Bussmann®
19
Disconnect Switches
Technical Data – Non-Fusible, 16-3150 Amps
1Two sets of parallel poles in series
(Figure 1)
2Three poles in series (Figure 2)
3Four poles in series
4IEC 947-3, utilization category B, infrequent
operation
5IEC 408
6Size 4
7Available upon request
LOAD
LOAD
Figure 1 Figure 2
U.L. & CSA Ratings
Ampere Rating 16 25 32 40 80 100 175 200 400 600 800 1200 1600 2000 3150
2 Pole U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98
U.L. Standard 3 Pole U.L. 508 U.L. 508 U.L. 508 U.L. 508 U.L. 508 U.L. 508 U.L. 508 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98 U.L. 98
4 Pole U.L. 508 U.L. 508 U.L. 508 U.L. 508 U.L. 98 U.L. 98 U.L. 98
Short-circuit rating with fuse kA 10/5 10/5 10/5 10/5 10 100 100 100 100 100 100 100 100 100
Fuse size A 30 30 30 60 110 110 200 200 600 600 1,200 1,200 2,000 2,000
Fuse class CC, J, T, RK1/RK5 H or K J RK5 RK5 RK5 RK5 L L L L
Short-circuit rating with MCCB kA 25 25 50 50 50 50 65 65
200V 2 3 5 10 15 20 30 60 100 150 200
Maximum 208V 2 3 5 10 15 20 30 60 100 150 200
Horsepower 240V 2 3 5 10 20 25 40 75 125 200 250
Ratings 480V 7.5 7.5 10 20 40 50 75 150 250 400 500
600V 7.5 10 15 20 50 60 100 200 350 500 600
Electrical endurance 6,000 6,000 6,000 6,000 6,000 6,000 6,000 6,000 1,000 1,000 1,000 1,000 1,000 1,000
Mechanical endurance 6,000 6,000 6,000 6,000 6,000 6,000 6,000 8,000 6,000 6,000 6,000 6,000 6,000 6,000
IEC Ratings
Ampere Rating 16 25 32 40 80 100 175 200 400 600 800 1200 1600 2000 3150
Rated insulation voltage and operational
voltage, AC 20 and DC 20 V 750 750 750 750 690 690 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Rated impulse withstand voltage kV 8 8 8 8 8 8 12 12 12 12 8 8 8 8 8
Rated Thermal Current Ith:
AC 20 and DC 20 open A 25 32 40 50 100 125 250 350 630 800 1,250 1,600 2,500 3,150 3,150
40°C enclosed A 25 32 40 50 80 125 200 315 630 720 1,250 1,600 2,300 2,600 2,600
60°C enclosed A 25 32 40 50 63 100 175 260 500 600 1,000 1,250 1,950 2,300 2,300
Rated Operational Currents:
AC21A 500V A 16 25 32 45 80 125 200 315 630 800 1,250 1,600 2,50043,15043,1504
690V A 16 25 32 45 80 125 200 315 630 800 1,250 1,600 2,50043,15043,1504
1000V5A 200 315 630
AC22A 500V A 16 25 32 45 80 125 200 315 630 800 1,250 1,600 1,60041,60041,6004
690V A 16 25 32 45 80 80 200 315 630 800
1000V5A 200 250 400
AC23A 415V A 16 20 23 30 63 75 200 315 630 720 800 800 800480048004
500V A 16 20 23 30 45 56 200 315 580 600 800 800 800480048004
690V A 8 11 12 20 406356200 315 350 350
1000V5A 125 125 200 200
DC21A 48V A 8011251200 315 630 800 1,250 1,600 1,600 1,600 1,600
3-poles in series
16-100A 110V A 80 125 200 315 630 800 1,250 1,600 1,600 1,600 1,600
2-poles in series
175-3150A 220V A 80 200 315 630 800 1,250 1,600 1,600 1,600 1,600
440V2A 200 315
750V3A 200 315
DC22A 48V A 801751200 315 630 800
3-poles in series
16-100A 110V A 80 50 200 315 630 630
2-poles in series
175-3150A 220V A 50 200 315 400 500 77777
440V2A 200 315 400 500
750V3A 200 315
DC23A 48V A 801751200 315
3-poles in series 16-100A 110V A 35 50 200 315 630 800
2-poles in series 175-3150A 220V2A 25 200 315 630 630 77777
440V3A 200 315 400 400
750V3A 200 315
Contents
Previous
Next
Bussmann®
20
Disconnect Switches
Technical Data – Non-Fusible, 16-3150 Amps
IEC Ratings
Ampere Rating 16 25 32 40 80 100 175 200 400 600 800 1200 1600 2000 3150
Rated operational power
230V kW 3 4 5.5 7.5 18.5 22 55 90 180 200 250 250 250 250 250
AC23 400/415V kW 7.5 9 11 15 30 37 90 160 315 355 400 400 400 400 400
The kW-ratings are accurate 500V kW 7.5 9 11 15 30 37 132 200 355 400 450 450 450 450 450
for three-phase 1500 r.p.m. 690V kW 7.5 9 11 15 30
12
30
12
170 250 355 355
standard asynchronous motors.
Short-circuit current with kA 50 50 50 50 50 50 100 100 80 150 80 50 50
8
50
5
50
5
50
5
back-up fuses of size
11
A25 32 40 50 100 125 400 400 630 800 800 1,000 1,250 1,250 1,250 1,250
Rated voltage Ue V/V 415 415 415 415 415/690 500/690 500/690 500/690 500/690 500/690 690 690 690 690 690
Rated conditional short-circuit current kA/kA 50 50 50 50 10/18 10/10 100/50 100/50 100/50 100/50 45 45 50 50 50
Max. allowed fuse size, type OFAA A/A 16 32 40 50 100/63 80/63 400 400 800
13
800
13
Max. allowed cut-off current, peak value kA/kA 4 4.3 4.6 5.5 5.8/5.5 4.2/5.6 30 30 62 62
Rated short-circuit making capacity,
prospective peak value, Icm kA 1 1 1 1 2.7 3.6 35/35 35 80 80 95 95 115 115 115
Rated short-time withstand current,
RMS lcw 0.25kA 1.5 2.5 17 17 38 38 45 45 50 50 50
1.05kA 1 1 1 1 1.5 2.5 8 8 17 17 33 33 37 37 37
AC breaking capacity
415V A 128 160 184 240 510 600 1,600 2,520 5,760 5,780 6,400 6,400 6,400 6,400 6,400
Pf 0.35 500V A 128 160 184 240 400 450 1,600 2,520 4,800 4,800 6,400 6,400 6,400 6,400 6,400
690V A 54 88 96 150 320 280 1,600 2,520 2,800 2,500
6
2,500
6
4,800
10
4,800
10
1000V
11
A 1,000 1,000 1,200 1,200
DC breaking capacity
48V A 325 1,260
9
1,260
9
L/R = 8ms, 3-poles 110V A 550
4
300 1,260
9
1,260
9
in series 220V A 215
4
200 1,260
1
1,260
1
1,600
1
2,000
1
1,900
1,4
2,600
1,4
2,600
1,4
2,600
1,4
2,600
1,4
440V A 30
4
1,260 1,260 1,600 2,000
750V
2
A 1,260
3
1,260
3
Electrical endurance at rated
operational current.
pf 0.65 operation cycles 3,000 3,000 3,000 3,000 1,500 1,500 1,000 1,000 1,000 500 500 500 100710071007
Mechanical endurance
operations 20,000 20,000 20,000 20,000 20,000 16,000 16,000 16,000 10,000 10,000 10,000 10,000 6,000 6,000 6,000
Weight 3-pole lb .24 .24 .24 .60 .66 .99 6.17 13.66 13.33 35.93 38.58 143 143 143 143
4-pole lb .33 .33 .33 .77 .72 1.38 7.93 7.93 16.75 16.75 45.19 49.60 165 165 165
Power loss per one pole W .3 .6 1.0 1.4 7 7 3.5 8.5 22 40 40 67 90 140 140
Operating torque
11
Nm 1 1 1 1.2 2.0 1.6 8.2 8.2 21 21 21 21 50 50 50
Suitable conductor
cross section Cu mm2.75…10 .75…10 .75…10 1.5…25 1.5…35 10…70 8 x 25 10 x 30 12 x 40 12 x 40 12 x 60 12 x 60 12 x 60 12 x 60 12 x 60
1
Two poles in series
2
Three poles in series (Figure 2)
3
Four poles in series
4
L/R = 2.5 ms
5
With circuit breaker, time-delay 1 sec. max.
6
Pf 0.95
7
IEC 947-3, utilization category B, infrequent
operation
8
With circuit breaker, time-delay 0.5 sec. max.
(in closed position)
9
One pole
10
Pf 0.65
11
IEC 408
12
Available upon request
13
Size 4
LOAD
LOAD
Figure 1 Figure 2
Contents
Previous
Next
Bussmann®
21
Disconnect Switches
Technical Data – Auxiliary Contact Timing Diagrams
30 Amps
Catalog Auxiliary Contact
Number Contact Configuration
BDAUX157 1 NO & 1 NC
BDCF30 BDAUXCB01 1 NO
BDAUXCB10 1 NC
ON
OFF O
I
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Legend
Contacts closing
1Main contacts close
2NO auxiliary contacts close
3NC auxiliary contacts open
Contacts opening
4Main contacts open
5NO auxiliary contacts open
6NC auxiliary contacts close
Fusible – 30 Amps
ON
OFF O
I
BDAUX157
BDAUXCB01
BDAUXCB10
Contents
Previous
Next
Bussmann®
22
Disconnect Switches
60-100 Amps
Contact
Catalog Auxiliary Configuration
Numbers Contact Form C
BDF60 & BDAUX7 1 NO & 1 NC
BDF100 BDAUX8 2 NO & 2 NC
Fusible – 60-100 Amps
Technical Data – Auxiliary Contact Timing Diagrams
ON
OFF O
I
Contents
Previous
Next
Bussmann®
23
Technical Data – Auxiliary Contact Timing Diagrams
Disconnect Switches
200-400 Amps
Catalog Auxiliary Contact
Numbers Contact Configuration
FD200 & BDAUX1 1 NO & 1 NC
FD400 BDAUX2 2 NO & 2 NC
Fusible – 200-800 Amps
600-800 Amps
Catalog Auxiliary Contact
Numbers Contact Configuration
FD600 & BDAUX1 1 NO & 1 NC
FD800 BDAUX2 2 NO & 2 NC
ON
OFF O
I
Contents
Previous
Next
Bussmann®
24
Disconnect Switches
Technical Data – Auxiliary Contact Timing Diagrams
ON
OFF O
I
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Legend
16-30 Amps
Catalog Auxiliary Contact
Number Contact Configuration
CDNF16-32 CDAUX10 NO
CDAUX01 NC
40 Amps
Catalog Auxiliary Contact
Number Contact Configuration
CDNF45 CDAUX10 NO
CDAUX01 NC
Contacts closing
1Main contacts close
2NO auxiliary contacts close
3NC auxiliary contacts open
Contacts opening
4Main contacts open
5NO auxiliary contacts open
6NC auxiliary contacts close
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Non-Fusible – 16-40 Amps
Contents
Previous
Next
Bussmann®
25
Disconnect Switches
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Technical Data – Auxiliary Contact Timing Diagrams
80 Amps
Contact
Catalog Auxiliary Configuration
Number Contact Form C
BDNF60 BDAUX79 1 NO & 1 NC
BDAUX80 2 NO & 2 NC
80 Amps
Catalog Auxiliary Contact
Number Contact Configuration
BDAUXCA10 NO
BDNF60 BDAUXCA01 NC
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Non-Fusible – 80 Amps
ON
OFF O
I
Contents
Previous
Next
Bussmann®
26
Disconnect Switches
Technical Data – Auxiliary Contact Timing Diagrams
100 Amps
Contact
Catalog Auxiliary Configuration
Number Contact Form C
BDNF100 BDAUX52 1 NO & 1 NC
BDAUX53 2 NO & 2 NC
175-200 Amps
Catalog Auxiliary Contact
Numbers Contact Configuration
BDNF175A & BDAUX12 1 NO & 1 NC
BDNF200A BDAUX13 2 NO & 2 NC
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Non-Fusible – 100-200 Amps
ON
OFF O
I
Contents
Previous
Next
Bussmann®
27
Disconnect Switches
Technical Data – Auxiliary Contact Timing Diagrams
400-600 Amps
Catalog Auxiliary Contact
Numbers Contact Configuration
BDNF400 & BDAUX1 1 NO & 1 NC
BDNF600A BDAUX2 2 NO & 2 NC
800-3150 Amps
Catalog Auxiliary Contact
Numbers Contact Configuration
BDNF800A through BDAUX1 1 NO & 1 NC
BDNF3150 BDAUX2 2 NO & 2 NC
0°30°60°90°
OFF
OON
I
Main contact
NO auxiliary
contact
NC auxiliary
contact
closing O 1
opening O 1
Non-Fusible – 400-3150 Amps
ON
OFF O
I
Contents
Previous
Next
Bussmann®
28
Disconnect Switches
Approximate Dimensions – Fusible
2.75
3.84
0.93
97.5
70.0
23.6
4.15
105.5
1.52
38.5
3.66
93.0
1.83
46.5
0.17
4.3
2.95..3.15
75.0...80.0
1.27
32.5
3.70
94.0
2.44
62.0
2.00
51.0
3.66
93.0
4.10
104.0
35mm
DIN RAIL
30 Amps
4.85
123.1
5.50 ... 8.63
140.0 ... 219.0
3.19
81.0
1.46
37.0
2.00
50.8
4.74
120.4
3.70
94.0
0.23
5.9
0.27 Dia.
7.1
2.36
60.0
5.57
141.4
1.18
30.0
.80
20.3
1.54
39.1
2.92
74.1
6.85 ( 3 POLE ) 8.31 ( 4 POLE )
174.0 211.0
60 Amps
2.13
54.1
2.36
60.0
8.78
223.0
1.18
30.0
M6 x 1.0
0.27 Dia.
6.9
8.39
213.0
7.70
195.5
.79
20.0
2.15
54.6
0.26 Dia.
6.6
0.23
5.9
3.58
91.0
5.61
142.5
6.80
172.5
3.90
99.2
1.14
29.0
5.15
130.8
5.50...8.62
139.7....219.0
2.01
51.0
4.76
121.0
1.75
44.4
100 Amps
00.00 Inches
00.00 Millimeters
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
29
Disconnect Switches
Approximate Dimensions – Fusible
9.25 ... 13.58
234.9
...
344.9
0.47
11.9
5.91
150.1
9.87
250.7
8.88
225.5
0.27 Dia.
6.8
7.80 (2 Pole) 10.25 (3 Pole) 12.68 (4 Pole)
198.1 260.3 322.0
6.89
175.0
4.38
111.2
1.90
48.2
1.51
38.3
0.28
7.1
2.25
57.1
0.95
24.1
2.02
51.3
7.86
199.6
1.81
45.9
5.71
145.0
2.40
60.9
7.24
183.9
0.20
5.0
5.91
150.1
7.84
199.1
1.84
46.7
200 Amps
0.27 Dia.
6.8
0.47
11.9
9.25 ... 13.58
234.9
...
344.9
2.40
70.0
8.62
218.9
1.97
50.0
10.82
274.8
8.43 (2 Pole) 11.19 (3 Pole) 13.94 (4 Pole)
214.1 284.2 354.0
12.18
309.3
1.84
46.7
0.28
7.1
1.97
50.0
2.73
69.3
8.79
223.2
1.38
35.0
5.25
133.3
5.91
150.1
7.67
194.8
5.71
145.0
8.89
225.8
1.77
44.9
0.20
5.0
7.80
198.1
400 Amps
10.23 ... 13.78
259.8
...
350.0
0.35 Dia.
8.8
0.47
11.9
10.12
257.0
12.97
329.4
14.30
363.2
11.14 (2 Pole) 14.69 (3 Pole) 18.23 (4 Pole)
282.9 373.1 463.0
3.74
95.0
0.92
23.3
2.57
65.2
3.55
90.1
12.14
308.0
1.58
40.1
0.95
54.1
7.48
189.9
9.84
249.9
5.71
145.0
2.43
60.9
8.71
221.2
0.23
5.8
1.59
40.3
11.11
282.1
1.83
46.4
5.97
151.9
600 & 800 Amps
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
30
Disconnect Switches
Approximate Dimensions – Non-Fusible, Toggle Type
80 Amps
3.15
80.0
0.59
15.0
5.79
147.0
0.15
3.81
1.18
30.0
2.75
70.0
3.06
78.0
3.06
78.0
2.34
59.4
0.81
20.5
0.10
2.5
1.96
50.0
3.03
77.0
1.96
50.0
1.81
46.0
0.25
6.35
1.68
42.6
100 Amps
00.00 Inches
00.00 Millimeters
39.4
53.6
63.0
3.6
45.0
47.5
40.9
1.61
1.77
1.87
0.14 1.49
37.8
1.49
37.8
2.98
75.6
1.55
2.11
2.48
Contents
Previous
Next
Bussmann®
31
Disconnect Switches
0.4
11
O
ø.18
4.5
I ON
1.8
45
.4
11
1.4
35
.5
13
1.4
35
0.6
15
2.1
54
0.4
11
0.4
11
1.5
37
0.5
13
1.4
35
0.9
22
1.6
40
2.4
60
0.4
11
2.7
68
5
O
OFF
I ON
2.4
61.0
0.4
11
1.8
45
0.5
13
1.4
35
3.6
91.5
0.6
15
2.8
72
0.7
17.5
0.7
17.5
0.7
17
2.1
52.5
0.4
11
0.4
11
1.5
37
2.1
54
3.2
82.5
1.7
43.5
ø.18
4.5
5
.87
22
.43
11
1.97
(50)
2.56
(65)
1.69
43
1.42
36
1.69
43
1.42
36
2.13
54
.13
3.2
ø
2.68
68
.22
5.7
1.06
27
.12
3
.98
(25)
1.36
(34.5)
.21
5.4
.43
11
.53
13.4
1.38
35
.43
11
1.46
37
1.57
40
1
2
1
1 CDH7S + CDH8S
2 CDH9S + CDH10S
2
Approximate Dimensions – Compact, Non-Fusible
Non-Fusible, 16-40A, 600V
CDNF45
Door mounted switches
CDNF16D, CDNF25D, & CDNF32D
Base and DIN rail mounted switches
CDNF16, CDNF25, & CDNF32
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
L
H
3.34 (4no + 4nc)
2.92 (2no + 2nc)
0.20
Auxiliary Switches
3.15
4.0
50.0
52.8
90.1
58.1 74.1
74.1
84.8
80.0
5.08
51.3
1.99
50.5
2.75
0.16
1.66
3.31
1.66
1.97
2.08
3.55
69.8
42.1
84.0
42.1
2.02
2.92
2.29 1.69
42.9
Bussmann®
32
Disconnect Switches
Approximate Dimensions – Non-Fusible
80 Amps
Auxiliary Switches
DIMENSION HANDLE TYPE
PISTOL SELECTOR
L
H
5.91 3.55
6.88 - 7.50 5.50 - 6.12
150.1 90.1
174.8 - 190.5 139.7 - 155.4
90.1
(2no + 2nc)
(4no + 4nc)
3.55
0.59
14.9
0.16
4.0
2.75
69.8
2.75
69.8
1.18
29.9
3.06
77.7
1.69
42.9
4.33 (4 Pole)
109.9
3.54
89.9
1.89
48.0
L1.81
45.9
0.25
6.3
0.20
5.0
3.03
76.9
1.97
50.0
0.81
20.5
3.88
98.5
0.10
2.5
3.15
80.0
2.42
61.9
1.99
50.5
H
3.54 (4no + 4nc)
89.9
3.12 (2no + 2nc)
79.2
100 Amps
0.31
7.8
4.33
109.9
1.26
32.0
1.42
36.0
8.36
212.3
7.45
186.4
6.02 (2 Pole) 7.86 (3 Pole) 9.65 (4 Pole)
152.9 199.6 245.1
4.56...8.50
115.8...215.9
1.41
35.8
0.27
6.8
1.81
45.9
1.81
45.9
0.35
8.8
0.27
6.8
4.32
109.7
5.37
136.4
0.98
24.8
0.43
10.9
6.21
157.7
3.15
80.0
1.99
50.5
0.16
4.0
3.67
93.2
6.35
161.2
4.55
115.5
175 Amps
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
33
Disconnect Switches
Approximate Dimensions – Non-Fusible
4.56...8.50
115.8 ... 215.9
0.31
7.87
6.42 (2 Pole) 8.64 (3 Pole) 10.82 (4 Pole)
8.36
212.34
7.34
186.44
1.42
36.07
163.0 219.4 274.8
1.41
35.8
0.27
6.8
2.21
56.1
2.21
56.1
0.35
8.8
0.27
6.8
4.32
109.7
5.37
136.4
0.98
24.8
7.00
177.8
0.43
10.9
1.99
50.5
3.67
93.2
0.16
4.06
1.26
32.0
3.15
80.0
6.35
161.2
4.33
109.9
4.55
115.5
200 Amps
2.74
69.6
0.27 Dia.
6.8
7.88 ... 12.19
200.1 ... 309.6
0.62
15.7
0.47
11.9
8.55
217.1
7.48 (2 Pole) 10.25 (3 Pole) 12.99 (4 Pole)
11.82
300.2
10.48
266.1
1.97
50.0
189.9 260.3 325.9
1.84
46.7
1.95
50.0
1.14
28.9
1.58
40.1
7.88
200.9
0.70
17.7
7.31
185.6
5.91
150.1
5.71
145.0
5.52
140.2
0.20
5.08
2.40
60.9
5.12
130.05
1.77
44.96
0.28
7.1
400 Amps
00.00 Inches
00.00 Millimeters
7.88 ... 12.19
200.1 .. 309.6
0.47
11.9
8.55
217.1
1.97
50.0
11.77
298.9
10.42
264.6
8.39 (2 Pole) 11.90 (3 Pole) 15.47 (4 Pole)
213.1 302.2 392.9
0.27 Dia.
6.8
1.84
46.7
0.28
7.1
1.97
50.0
1.14
28.9
3.56
90.4
9.56
242.8
1.58
40.1
0.70
17.7
7.31
185.6
5.91
150.1
5.71
145.0
0.62
15.7
5.52
140.2
1.77
44.9
5.12
130.0
0.20
5.0
2.40
60.9
600 Amps
Contents
Previous
Next
23.95
600.3
0.35 Dia.
8.8
0.47
11.9
12.95 (2 Pole) 18.43 (3 Pole) 23.90 (4 Pole) 13.38 ... 21.06
339.8 ... 534.9
0.59
14.9
0.69
17.5
3.94
100.0
3.43
87.1
1.28
32.5
21.50
546.1
1.38
35.0
3.43
87.1
6.57
166.8
25.02
635.5
21.44
544.5
2.45
62.2
328.9 468.1 607.0
1.75
44.4
3.74
95.0
7.48
189.9
14.65
372.1
0.48
12.1
15.84
402.3
5.47
138.9
0.92
23.3
8.66
219.9
3.94
100.0
4.44
112.7
8.35
212.0
10.67
271.0
1.00
25.4
Bussmann®
34
Disconnect Switches
Approximate Dimensions – Non-Fusible
10.04 ... 12.80
255.0 ... 325.1
0.59
14.9
0.35 Dia.
8.8
0.47
11.9
19.10
485.1
2.04
51.8
10.75 (2 Pole) 14.29 (3 Pole) 17.83 (4 Pole)
273.0 362.2 452.8
3.74
95.0
0.96
24.3
2.32
58.9
3.54
89.9
1.97
50.0
11.73
297.9
0.35
8.8
1.55
39.3
10.00
254.0
7.48
189.9
5.71
145.0
14.65
372.1
8.27
210.0
1.57
39.8
0.47
11.9
4.92
124.9
2.40
60.9
800 Amps
0.47
11.9
0.35 Dia.
8.8
0.59
14.9
10.75 (2 Pole) 14.29 (3 Pole) 17.83 (4 Pole)
15.19
385.8
17.71
449.8
19.09
484.8
1.91
48.5
273.0 362.9 452.8
7.48
189.9
10.00
254.0
1.55
39.3
0.48
12.1
11.73
297.9
0.96
24.3
3.55
89.9
2.31
58.9
5.71
145.0
0.66
16.7
1.25
31.7
4.92
124.9
2.40
60.9
8.27
210.0
14.65
372.1
10.04 ... 12.80
255.0 ... 325.1
3.74
95.0
1200 Amps
1600, 2000, 3150 Amps
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
35
Disconnect Switches
Approximate Dimensions – Handles
Handles
for base & DIN rail mounted switches
CDH1S & CDH2S
Handles
for door mounted switches
CDH7S & CDH8S
CDH9S & CDH10S
CDH3S, CDH4S, CDH5S & CDH6S
BDH47 & BDH99
BDH100, BDH102, BDH103, &
BDH104
Mounting dimensions,
pistol handle
45°1.8
45
2.2
56
0.3
7
O
2.7
68
3.2
81
2.0
50.8
2.7
68
2.4
61
2.0
50.8
Ø40
1.2
30.5
1
25.4
0.3
6.5
1.6
40.6
1
25.4
0.1
2.54
0.9
22.8
1
25.4
O OFF
I ON
1.9
48
Ø
1.2
30.5
1
25.4
0.3
6.5
1.6
40.6
1
25.4
0.1
2.54
0.9
22.8
0.6
15
O OFF
I ON
1.9
48
Ø
1.2
30.5
1
25.4
0.3
6.5
1.6
40.6
1
25.4
0.1
2.54
0.9
22.8
0.6
15
O OFF
I ON
1.9
48
Ø
1.6
40.6
1.3
33
1.6
40.6
1
25.4
0.1
2.54
0.9
22.8
1
25.4
0.39
10
O OFF
I ON
2.6
66
00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
36
Approximate Dimensions – Transfer & Bypass Switches
Disconnect Switches
1.77 DIA
1.54
A
2.16
B
1.53
3.15
.71
0.20
0.24
4.57
0.59
2.84
72.0
39.0
15.0
80.0
11.02
Max.
280.0
45.0
55.0 116.0
18.0
39.0
5.0
6.0
A = 3.54 + 10 steps of 0.59 steps
B = 0.32 min.; 2.55 max.
90.0 15.0
8.0 65.0
1.77 DIA
1.54
2.84
A
1.18
2.16
1.53
3.15
.71
0.20
0.24
0.32 ... 2.55
B
72.0
39.0
15.0
80.0
11.02
Max.
280.0
45.0
55.0 30.0
18.0
39.0
5.0
6.0
8.0 65.0
0.59
A = 4.72 + 8 steps of 0.59
B = 3.54 + 6 steps of 0.59
120.0 15.0
15.0
90.0
0.20
5.0
...
1.18 min. +
13 steps of 0.59
0.20
0.59
5.00
15.0
30.0
15.0
Transfer & bypass switches
CDZW6
CDZW17
CDZW8 00.00 Inches
00.00 Millimeters
Contents
Previous
Next
Bussmann®
37
Approximate Dimensions –
Transfer Switches
Disconnect Switches
00.00 Inches
00.00 Millimeters
1.77 DIA
11.02
280.0
Max.
1.54
2.84
A
B
0.71
0.24
0.24
4.57
A = 3.54 + 10 steps of 0.59 steps
90.0 15.0
B = 0.32 min.; 2.55 max.
8.0 65.0
0.59
39.0
72.0
15.0
45.0
2.16
55.0 116.0
18.0
39.0
1.53
6.0
6.0
3.15
80.0
BDZW1
4.72
7.72
0.24
0.47
0.24
1.77 min. +
45.0
13 steps of 0.59
15.0
1.57
0.59
6.00 6.00
12.00
40.0
196.0
120.0
15.0
BDZW2
A
B
BDZW3 – ZW14 and – ZW15
8.74
222.0
9.50
241.3
4.60
116.8
4.13
105.0
0.55
14.0
4.63
117.5
BDZW4
Dimensions in Inches & mm
A B
BDZW3 11.81 0.47
300.0 12.0
BDZW14 9.84 0.47
250.0 12.0
BDZW15 19.69 0.47
500.0 12.0
BDZW19 11.02 0.31
280.0 8.0
Contents
Previous
Next
Bussmann®
38
Approximate Dimensions –
Transfer Switches
Disconnect Switches
00.00 Inches
00.00 Millimeters
8.74
222.0
9.50
241.3
4.60
116.8
4.13
105.0
0.55
14.0
4.63
117.5
BDZW5
2.36 min. +
60.0
19 steps of 0.79
20.0
0.47
12.00
0.79
15.0
BDZW9 and CDZW9
Contents
Previous
Next
Bussmann®
39
Approximate Dimensions –
Transfer Switches
Disconnect Switches
00.00 Inches
00.00 Millimeters
A = 8.27 + 11 steps of 0.79
210.0 20.0
A
3.27
B = BDZW11 = 0.47
12.0
BDZW20 = 0.31
8.0
83.0
1.35
34.0
1.30
33.0
3.31
84.0
0.79
20.0
20.08
510.0
Max.
145.0
8.0...15.0
0.31 ... 0.59
5.71
0.47
12.0
2.08
53.0
4.84
123.0
B
B
BDZW11
3.54
90.0
1.57
40.0
A
1.30
33.0
3.31
84.0
0.79
20.0
27.17
690.0
Max.
220.0
8.66
4.84
123.0
2.28
58.0
0.47
12.0
0.47
12.0
0.47
12.0
8.0 ...15.0
0.31 ... 0.59
A = 8.27 + 18 steps of 0.79
210.0 20.0
BDZW12
A = 8.27 + 18 steps of 0.79
210.0 20.0
0.47
12.0
0.47
12.0
B = 9.84 + 18 steps of 0.79
250.0 20.0
3.54
90.0
1.57
40.0
1.30
33.0
3.31
84.0
0.79
20.0
A
B
27.17
690.0
Max.
36.0 ... 43.0
1.42 ... 1.69
220.0
8.66
0.47
12.0
4.4
123.0
2.28
58.0
0.47
12.0
BDZW13
Contents
Previous
Next
Bussmann®
40
Approximate Dimensions –
Transfer Switches
Disconnect Switches
00.00 Inches
00.00 Millimeters
3.15 min. +
80.0
10 steps of 0.79
15.0
0.24
8.00
0.24
8.00
3.94
100.0
0.59
3.15
15.0
0.47
12.00
6.93
176.0
1.57
40.0
BDZW18
A = 8.27 + 11 steps of 0.79
210.0 20.0
A
3.27
B = BDZW11 = 0.47
12.0
BDZW20 = 0.31
8.0
83.0
1.35
34.0
1.30
33.0
3.31
84.0
0.79
20.0
20.08
510.0
Max.
145.0
8.0 ...15.0
0.31 ... 0.59
5.71
0.47
12.0
2.08
53.0
4.84
123.0
B
B
BDZW20
2.08
7.0 ... 43.0
0.31 ... 0.59
3.27
83.0
1.35
35.0
1.30
33.0
3.31
84.0
0.79
20.0
B
20.0
510.0
Max.
A = 9.84 + 9 steps of 0.79
250.0 20.0
B = 8.27 + 9 steps of 0.79
210.0 20.0
0.47
12.0
4.84
123.0
145.0
5.71
A
53.0
0.31
0.31
8.0
8.0
0.31
8.0
BDZW21
Contents
Previous
Next
Bussmann Denmark
5 Literbuen
DK-2740 Skovlunde
Copenhagen, Denmark
Telephone: 45 4485 0900
Facsimile: 45 4485 0901
Bussmann France
Tour Mattei
207 Rue de Bercy
75587 Paris Cedex 12
France
Telephone: 33 1 4475 0033
Facsimile: 33 1 4475 0420
Bussmann Germany
Frankfurter Landstrasse 19
64546 Mörfelden
Germany
Telephone: 49 6105 951509
Facsimile: 49 6105 951510
Bussmann India
2nd Floor, Unit #5
White House
23-29, St. Marks Road
Bangalore – 560-001
India
Telephone: 91 80 227 0893
Facsimile: 91 80 224 0124
Bussmann Mexico
Arrow-Hart S.A. de C.V.
Poniente 148, No. 933
02300 Mexico, D.F. Mexico
Telephone: 52 5 587 0211
Facsimile: 52 5 567 4049
Headquarters
Cooper Industries
Bussmann Division
P.O. Box 14460
St. Louis, Missouri 63178-4460, USA
Telephone: 314 394 2877
Facsimile: 800 544 2570
Bussmann Circuit Components
7300 West Wilson Avenue
Chicago, IL 60656-4793, USA
Telephone: 708 867 4600
Facsimile: 708 867 2211
European Headquarters
Bussmann Division
Cooper (U.K.) Limited
Burton-on-the-Wolds
Leicestershire LE12 5th, England
Telephone: 44 1509 882737
Facsimile: 44 1509 882786
Bussmann Asia Pacific
331 North Bridge Road
#03-02 Odeon Towers
Singapore 188720
Republic of Singapore
Telephone: 65 336 3610
Facsimile: 65 336 4810
Bussmann Australia
Dock 5, Block X
391 Park Road
P.O. Box 257
Regents Park, Sydney
NSW 2143, Australia
Telephone: 61 2 9743 8333
Facsimile: 61 2 9743 8070
Bussmann Brasil
Bussmann do Brasil Ltda.
Rodovia Santos Dumont, Km 23
Cruz das Almas
Itu-Sao Paulo 13 300-000
Brasil
Telephone: 55 11 7824 1856
Facsimile: 55 11 7824 1721
©Cooper Industries, Bussmann Division, Printed in U.S.A.