https://www.phoenixcontact.com/us/products/2906860
04/11/2017Page2/4
Surge protection device-TTC-6-GDT-C-24AC-PT-I-2906860
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 V AC
Maximum continuous voltage UC36 V AC
Rated current 2 A (60°C)
Operating effective current IC at UC≤ 1 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (core-earth) 5 kA
Pulse discharge current Iimp (10/350)µs (core-ground) 0.5 kA
Voltage protection level Up (core-ground) ≤ 800 V (C1 - 2 kV)
≤ 1 kV (C2 - 10 kV)
≤ 800 V (C3 - 25 A)
≤ 900 V (C3 - 100 A)
Response time tA (core-earth) ≤ 100 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 8 MHz / 150 Ω)
typ. 0.3 dB (≤ 30 MHz / 50 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system typ. 130 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 25 MHz
Capacity (core-earth) 5 pF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C1 - 1 kA
C2 - 5 kA