0813 BU-SB13XXX Page 1 of 3 Data Sheet # 1023
Low-Peak™ Class CC
LP-CC — 600Vac/300Vdc, 12-30A Time-Delay Fuses
Description: Ultimate protection Class CC current-limiting,
time-delay fuses. Time-delay – 12 seconds (minimum) at
200% of rated current.
Catalog Symbol: LP-CC-(amp)
Ratings:
Volts — 600Vac,
— 300Vdc (12-2810A, 20-30A)
— 150Vdc (3-15A)
Amps 12-30A
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, Std. 248-4, Class CC, UL Listed, Guide JDDZ, File E4273
CSA Certified; Class 1422-02, File 53787
Catalog Numbers (amps)
LP-CC-12LP-CC-112LP-CC-3 LP-CC-6 LP-CC-12
LP-CC-610 LP-CC-1610 LP-CC-3210 LP-CC-614LP-CC-15
LP-CC-810 LP-CC-1810 LP-CC-312LP-CC-7 LP-CC-20
LP-CC-1 LP-CC-2 LP-CC-4 LP-CC-712LP-CC-25
LP-CC-118LP-CC-214LP-CC-412LP-CC-8 LP-CC-30
LP-CC-114LP-CC-212LP-CC-5 LP-CC-9
LP-CC-1410 LP-CC-2810 LP-CC-5610 LP-CC-10
Carton Quantity:
Amp Rating Carton Qty.
0-30 10
Features:
200kA interrupting rating complies with NEC®Section 110.9
for today's large capacity systems.
Fast short-circuit protection and dual-element, time-delay
performance provide ultimate protection.
Reduces existing fuse inventory by up to 33% when
upgrading to Low-Peak fuses.
Consistent 2:1 ampacity ratios for all Low-Peak fuses make
selective coordination easy.
Time-delay characteristic avoids unwanted fuse openings
from surge currents while fast response speed under short-
circuit conditions provides a high degree of current
limitation.
Current-limitation protects downstream components against
damaging thermal and magnetic effects of short-circuit
currents.
A superior, all-purpose, space-saving branch circuit fuse
that meets most protection requirements up to 30A.
Very compact, with a physical size only 1332" x 112"
(10.3 x 38.1mm) with rejction tip.
Proper sizing can provide "no damage" Type 2 coordinated
protection for NEMA and IEC motor controllers.
Can be used where either a time-delay or a fast-acting fuse
is needed, making selection easier and reducing spare fuse
inventories for substantial cost reduction.
Superior protection for small horsepower motor circuits.
Recommended Fuse Blocks and Holders
Fuse Amps 1-Pole 2-Pole 3-Pole
Open Blocks
0-30 BC6031_ BC6032_ BC6033_
DIN-Rail Holders
CHCC1D_ CHCC2D_ CHCC3D_
0-30 ——OPM-NG-_
——OPM-1038_
——OPM-1038_SW
Panel Mount Holders
0-30 HPS ——
HPF ——
In-Line Holders
0-30 HEY
HEZ ——
For additional information on the Class CC fuse blocks and
holders, see data sheets:
Open Blocks # 1105 (BC Series)
DIN-Rail Holders # 3185 (CHCC), # 1109 (OPM),
# 1102 (OPM-1038), 1103 (OPM-1038_SW),
Panel Mount Holders # 2113 (HPS), # 2114 (HPF)
In-Line Holders # 2126 (HEY), # 2130 (HEZ)
1.5" (± 0.031)
(38.1mm)
0.41" (± 0.005)
(10.3mm)
Dimensions - in (mm)
0813 BU-SB13XXX Page 2 of 3 Data Sheet # 1023
Low-Peak™ Class CC
Time-Current Curves - Average Melt
200
100
10
TIME IN SECONDS
1
0.1
0.01
1
3
4
6
8
10
12
15
20
25
30
AMP RATING
0.4
1
10
100
1000
CURRENT IN AMPS
1/2
6/10
8/10
1-1/4
3-1/2
4-1/2
LP-CC — 600Vac/300Vdc, 12-30A Time-Delay Fuses
0813 BU-SB13XXX Page 3 of 3 Data Sheet # 1023
Low-Peak™ Class CC
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended
to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product
has been selected, it should be tested by the user in all possible applications.
Current-Limitation Curves
B
A
Amp Rating
30
25
20
15
2-8/10
1-1/4
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
LP-CC — 600Vac/300Vdc, 12-30A Time-Delay Fuses
Current-Limiting Effects
Prosp. Let-Through Current
S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating)
—1
14A2
810A 15A 20A 25A 30A
1000 100 135 240 305 380 435
3000 140 210 350 440 575 580
5000 165 255 420 570 690 710
10,000 210 340 540 700 870 1000
20,000 260 435 680 870 1090 1305
30,000 290 525 800 1030 1300 1520
40,000 315 610 870 1150 1390 1700
50,000 340 650 915 1215 1520 1820
60,000 350 735 1050 1300 1650 1980
80,000 390 785 1130 1500 1780 2180
100,000 420 830 1210 1600 2000 2400
200,000 525 1100 1600 2000 2520 3050
NOTE: To calculate Ip(Ipeak) multiply IRMS value by 2.3.