https://www.phoenixcontact.com/us/products/2906857
04/10/2017Page2/4
Surge protection device-TTC-6-MOV-C-60DC-PT-I-2906857
Technical data
Dimensions
Depth 69.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
Nominal voltage UN60 V DC
Maximum continuous voltage UC75 V DC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 100 µA
Residual current IPE ≤ 100 µA
Nominal discharge current In (8/20) µs (core-earth) 2 kA
Voltage protection level Up (core-ground) ≤ 200 V (C1 - 600 A)
≤ 270 V (C2 - 4 kV)
≤ 190 V (C3 - 25 A)
≤ 200 V (C3 - 35 A)
Response time tA (core-earth) ≤ 25 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 650 kHz
Capacity (core-earth) 5 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C1 - 600 A
C2 - 2 kA