https://www.phoenixcontact.com/us/products/2906847
04/10/2017Page1/4
Surge protection device-TTC-6-TVSD-C-12DC-PT-I-2906847
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Fine surge protection with integrated status indicator for a signal wire with grounded reference potential.
The figure shows the version with
24VDC
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Signaling without additional auxiliary power, thanks to the mechanical status indicator
Optional remote signaling module monitors up to 40 items, without additional wiring
Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
Safe behavior in the event of overload, thanks to the integrated disconnect device
Fine surge protection by means of suppressor diode
Key Commercial Data
Packing unit 1
GTIN
GTIN 4055626137032
Custom tariff number 85363010
Technical data
Dimensions
Height 92 mm
92 mm
Width 6.2 mm
https://www.phoenixcontact.com/us/products/2906847
04/10/2017Page2/4
Surge protection device-TTC-6-TVSD-C-12DC-PT-I-2906847
Technical data
Dimensions
Depth 69.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C3
Nominal voltage UN12 V DC
Maximum continuous voltage UC15 V DC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs (core-earth) 300 A
Voltage protection level Up (core-ground) ≤ 25 V (C1 - 0,6 kV / 300 A)
≤ 22 V (C3 - 25 A)
≤ 25 V (C3 - 60 A)
Response time tA (core-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 340 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 1.1 MHz
Capacity (core-earth) 2 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C1 - 0.6 kV/300 A
C3 - 60 A
Connection data
Connection method Push-in connection
Connection method IN Push-in connection
https://www.phoenixcontact.com/us/products/2906847
04/10/2017Page3/4
Surge protection device-TTC-6-TVSD-C-12DC-PT-I-2906847
Technical data
Connection data
Connection method OUT Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Diagram
I [A]
T [°C]
6
4
2
8
10
40 907050 60 80
Dimensional drawing
62
69,5
92 6,2
Circuit diagram
3
4
1
2
!
unprotected protected
Approvals
Approvals
Approvals
UL Listed
Ex Approvals
https://www.phoenixcontact.com/us/products/2906847
04/10/2017Page4/4
Surge protection device-TTC-6-TVSD-C-12DC-PT-I-2906847
Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com